NP = Not Permitted
Note:
Not all models have these sizes.
The Standard Method
Use the
Standard Method
if:
1. The space has no less volume than 50 cubic feet per 1,000 BTUh of
the maximum input ratings for all gas appliances installed in the
space and
2. The air infiltration rate is not known to be less than 0.40 air changes
per hour (ACH).
Use the
Known Air Infiltration Rate Method
if the infiltration rate is
known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The minimum
required volume of the space varies with the number of ACH and shall
be determined per
or Equations 1 and 2. Determine the minimum
required volume for each appliance in the space and add the volumes
together to get the total minimum required volume for the space.
were determined by using the
following equations from the National Fuel Gas Code ANSI
Z223.1/NFPA 54, 9.3.2.2:
1. For other than fan-assisted appliances, such as a draft
hood-equipped water heater:
A04002
2. For fan-assisted appliances such as this furnace:
A04003
If the following is applied to either equation:
•
I
other = combined input of all other than fan-assisted appliances in
BTUh/hr
•
I
fan = combined input of all fan-assisted appliances in BTUh/hr
• ACH = air changes per hour (ACH shall not exceed 0.60.)
Then the following requirements apply to the
Standard Method
and to
the
Known Air Infiltration Rate Method
.
1. Adjoining rooms can be considered part of a space if:
a. There are no closeable doors between rooms.
b. Combining spaces on same floor level. Each opening shall have
free area of at least 1 in.
2
/1,000 BTUh (2,000 mm
2
/kW) of the
total input rating of all gas appliances in the space, but not less
than 100 in.
2
(0.06 m
2
). One opening shall commence within 12
in. (300 mm) of the ceiling and the second opening shall
commence within 12 in. (300 mm) of the floor. The minimum
dimension of air openings shall be at least 3 in. (80 mm), see
.
c. Combining space on different floor levels. The volumes of
spaces on different floor levels shall be considered as
communicating spaces if connected by one or more permanent
openings in doors or floors having free area of at least 2
in.
2
/1,000 BTUh (4,400 mm
2
/kW) of total input rating of all gas
appliances
.
* Minimum opening size is 100 sq in. (64516 sq. mm) with minimum dimensions of
3 in. (76 mm)
† Minimum of 3 in. (76 mm) when type-B1 vent is used.
a03175
Fig. 7 – Air for Combustion, Ventilation,
and Dilution from Indoors
2. An attic or crawlspace may be considered a space that freely
communicates with the outdoors provided there are adequate
permanent ventilation openings directly to outdoors having free
area of at least 1-in.
2
/4,000 BTUh of total input rating for all gas
appliances in the space.
3. In spaces that use the
Indoor Combustion Air Method
, infiltration
should be adequate to provide air for combustion, permanent
ventilation and dilution of flue gases. However, in buildings with
unusually tight construction, additional air
MUST
be provided
using the methods described in the
Outdoor Combustion Air
Method
section.
4. Unusually tight construction is defined as Construction with:
a. Walls and ceilings exposed to the outdoors have a continuous,
sealed vapor barrier. Openings are gasketed or sealed and
Table 2 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
30
40
50
44
66
88
110
132
154
Space Volume Ft
3
(M
3
)
0.60
1,050 (29.7)
1,400 (39.6)
1,750 (49.5)
1,100 (31.1)
1,650 (46.7)
2,200 (62.2)
2,750 (77.8)
3,300 (93.4)
3,850 (109.0)
0.50
1,260 (35.6)
1,680 (47.5)
2,100 (59.4)
1,320 (37.3)
1,980 (56.0)
2,640 (74.7)
3,300 (93.4)
3,960 (112.1) 4,620 (130.8)
0.40
1,575 (44.5)
2,100 (59.4)
2,625 (74.3)
1,650 (46.7)
2,475 (70.0)
3,300 (93.4)
4,125 (116.8) 4,950 (140.1) 5,775 (163.5)
0.30
2,100 (59.4)
2,800 (79.2)
3,500 (99.1)
2,200 (62.2)
3,300 (93.4)
4,400 (124.5) 5,500 (155.7) 6,600 (186.8) 7,700 (218.0)
0.20
3,150 (89.1)
4,200 (118.9)
5,250 (148.6)
3,300 (93.4)
4,950 (140.1) 6,600 (186.8) 8,250 (233.6) 9,900 (280.3) 11,550 (327.0)
0.10
6,300 (178.3)
8,400 (237.8) 10,500 (297.3) 6,600 (186.8) 9,900 (280.3) 13,200 (373.7) 16,500 (467.2) 19,800 (560.6) 23,100 (654.1)
0.00
NP
NP
NP
NP
NP
NP
NP
NP
NP
Volume
Other
= 21ft
3
ACH
I
other
1000 Btu/hr
Volume
Fan
= 15ft
3
ACH
I
fan
1000 Btu/hr
CIRCULATING AIR
DUCTS
6" MIN
(FRONT)
Ü
CIRCULATING AIR DUCTS
VENT THROUGH ROOF
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
12" MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
12" MAX
UNCONFINED
SPACE
INTERIOR
HEATED
SPACE
CLEARANCE IN FRONT OF COMBUSTION AIR
O
P
E
N
IN
G
S
S
H
A
L
L
BE A
T LEAST 3 IN.
(305mm)
(152mm)
(305mm)