background image

For Example:

58DFA FURNACE

INPUT BTUH

MINIMUM SQ FT

WITH 7-1/2 FT

CEILING

66,000

440

88,000

587

110,000

734

132,000

880

If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space. A minimum opening with a total of at least 1 sq in. per 5000
Btuh of total input rating for all equipment must be provided.
Return air must not be taken from the room unless an equal or
greater amount of air is supplied to the room.

CONFINED SPACE — A confined space is defined as one whose
volume is less than 50 cu ft for each 1000 Btuh of the total input
ratings of all appliances installed in that space. A confined space
MUST have 2 permanent openings, 1 within 12 in. of the ceiling,
and the other within 12 in. of the floor. (See Fig. 2.)

NOTE:

In determining the free area of an opening, the blocking

effect of the louvers, grilles, and screens must be considered. If the
free area of a louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.

The size of the openings depends upon whether the air comes from
inside or outside of the structure.

1. All air from inside the structure:

Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of the total input for all equipment within the
confined space, but not less than 100 sq in. per opening. (See
Fig. 2.)

For Example:

58DFA FURNACE IN-

PUT BTUH

FREE AREA PER

OPENING (SQ IN.)

66,000

100

88,000

100

110,000

110

132,000

132

If the building is constructed unusually tight, a permanent opening
directly communicating with the outdoors should be provided.
This opening should have a minimum free area of 1 sq in. per 5000
Btuh of total input rating for all equipment in the enclosure.

If the furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from the hallway
or space adjacent to the furnace, all air for combustion must come
from outdoors. (See Fig. 3.)

2. All air from outdoors:

a. If combustion air is taken from outdoors through vertical

ducts, the openings and ducts MUST have at least 1 sq in.
of free area per 4000 Btuh of the total input for all
equipment within the confined space.

Fig. 2—Air for Combustion and Ventilation

(Inside Air)

A93387

RETURN

AIR

6

 MIN

(FRONT) 

SUPPLY AIR

VENT THROUGH ROOF
(CATEGORY I)

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL 

12

 MAX 

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

 MAX 

INTERIOR

HEATED

SPACE 

* Minimum opening size is 100 square in. with
  minimum dimensions of 3-In. 

† 

Minimum of 3-In. when type B-1 vent is used.

UNCONFINED
SPACE

Fig. 3—Air for Combustion and Ventilation

(Outside Air)

A93388

DUCTS TO

OUTDOORS

1 SQ IN.
PER 4000
BTUH

*

RETURN

AIR

VENT
THROUGH
ROOF
(CATEGORY I)

D

B

A

C

E  

1 SQ IN.
PER 4000
BTUH

DUCT

TO

OUTDOORS

SUPPLY AIR

1 SQ IN.
PER 2000
BTUH*

DUCTS

TO

OUTSIDE

12

 MAX

12

 MAX

CONFINED

SPACE

12

MAX

12

MAX

1 SQ IN.
PER 4000
BTUH

*

OUTDOORS

1 SQ IN.
PER 4000
BTUH

*

1 SQ IN.
PER 2000
BTUH*

12

 MAX

Use any of the following
combinations of openings:
A & B     C & D    D & E     F & G

NOTE:

*Minimum dimensions of 3-In.

F

G

4

Summary of Contents for 58DFA

Page 1: ...lation Codes NSCNGPIC Wear safety glasses and work gloves Have fire extinguisher available during start up and adjustment procedures and service calls Understand the signal word DANGER WARNING or CAU TION These words are used with the safety alert symbol DAN GER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards that could result in p...

Page 2: ... further information the National Fuel Gas Code is available from National Fire Protection Association Inc Battery march Park Quincy MA 02269 American Gas Association 1515 Wilson Boulevard Arlington VA 22209 or from Literature Distribution Table 2 Dimensions In UNIT SIZE A D E VENT CONN SHIP WT 071 08 14 3 16 12 9 16 12 11 16 4 135 071 12 14 3 16 12 9 16 12 11 16 4 139 091 12 17 1 2 15 7 8 16 4 14...

Page 3: ... are manually operated they must be equipped with means to prevent operation of either unit unless the damper is in the full heat or full cool position HAZARDOUS LOCATIONS When the furnace is installed in a residential garage it must be installed so that the burners and ignition source are located at least 18 in above the floor The furnace should be protected from physical damage by vehicles When ...

Page 4: ... for all equipment within the confined space but not less than 100 sq in per opening See Fig 2 For Example 58DFA FURNACE IN PUT BTUH FREE AREA PER OPENING SQ IN 66 000 100 88 000 100 110 000 110 132 000 132 If the building is constructed unusually tight a permanent opening directly communicating with the outdoors should be provided This opening should have a minimum free area of 1 sq in per 5000 B...

Page 5: ... ON A CONCRETE SLAB 1 Construct hole in floor per dimensions in Fig 4 and Table 3 2 Install plenum and furnace as shown in Fig 5 INSTALLATION ON A COMBUSTIBLE FLOOR 1 Cut and frame hole in floor per dimensions in Installation Instructions packaged with downflow subbase 2 When completed downflow subbase plenum and furnace or coil casing when used should be installed as shown in Fig 6 Fig 4 Floor Op...

Page 6: ...has been attached If the pressure exceeds 0 5 psig 14 in wc the gas supply pipe must be disconnected from the furnace and capped before the pressure test If the test pressure is equal to or less than 0 5 psig 14 in wc close the manual shut off valve located on the gas valve before the test It is recommended that the ground joint union be loosened before pressure testing Never purge a line into a c...

Page 7: ...ment after installation Step 8 Start up Adjustment and Safety Check GENERAL The furnace must have a 115 v power supply properly connected and grounded Thermostat wire connections at R W C and Y must be made at the 24 v terminal block on the control board The gas service pressure must not exceed 0 5 psig 14 in wc but must be no less than 0 16 psig 4 5 in wc Before operating the furnace check each m...

Page 8: ... gas valve GV Gas flow to the pilot and main burners stops until the pilot is manually relit NOTE When gas valve GV is energized R W circuit is closed After a power interruption the gas valve closes within 7 sec and the furnace skips the blower on delay and immediately starts the blower 2 Cooling mode When the thermostat calls for cooling R G and Y circuits close Simultaneously the R Y circuit sta...

Page 9: ...TIVE BLADE TYPE FUSE FIELD INSTALLED FUSIBLE LINK GAS VALVE REDUNDANT HEATING FAN RELAY SPST N O INDUCED DRAFT MOTOR INDUCER DRAFT RELAY DPST N O BLOWER DOOR INTERLOCK SWITCH SPST N O JUNCTION BOX LIMIT SWITCH OVER TEMP SPST N C AUTO RESET PRINTED CIRCUIT BOARD FURNACE CONTROL 9 CIRCUIT CONNECTOR PCB1 2 CIRCUIT CONNECTOR L1 L2 5 CIRCUIT PLUG CONNECTOR BLWM PRESSURE SWITCH SPDT TRANSFORMER 115VAC 2...

Page 10: ...wc for natural gas When adjusting input rate do not set manifold pressure above 3 8 in wc or below 3 2 in wc a Check gas input rate using Table 6 1 Obtain average yearly heat value for local gas supply 1 Obtain average yearly specific gravity for local gas supply 1 Verify furnace model Table 6 can only be used for model 58DFA Furnaces 1 Check and verify orifice size in furnace NEVER ASSUME THE ORI...

Page 11: ...3 4 3 6 38 39 40 3 2 3 5 3 7 38 39 40 3 3 3 6 3 8 875 42 3 4 41 42 3 2 3 6 41 42 3 3 3 7 41 42 40 3 4 3 8 3 2 41 40 3 5 3 3 41 39 40 3 6 3 2 3 4 41 39 40 3 8 3 3 3 5 39 40 3 3 3 6 38 39 40 3 2 3 4 3 7 890 42 3 3 42 3 4 41 42 3 2 3 6 41 42 3 3 3 7 41 42 3 4 3 8 41 40 3 5 3 2 41 40 3 6 3 3 41 39 40 3 7 3 2 3 4 41 39 40 3 8 3 3 3 5 905 42 3 2 42 3 3 42 3 4 41 42 3 2 3 6 41 42 3 3 3 7 41 42 3 4 3 8 41...

Page 12: ...s per hr CHECK SAFETY CONTROLS 1 Check operation of gas shut off control for 100 percent shutoff NOTE The furnace pilot must be lit so the thermocouple energizes the thermal magnet circuit of gas valve GV which permits gas flow to the remaining portion of the valve If the pilot flame is extinguished the thermocouple will no longer energize the thermal magnet circuit of the gas valve Gas flow to th...

Page 13: ...n off 115 v power to furnace b Remove control door and disconnect inducer motor lead wires from wire harness c Turn on 115 v power to furnace d Close thermostat switch as if making normal furnace start If the burners do not light the pressure switch is function ing properly e Turn off 115 v power to furnace f Reconnect inducer motor wires replace control door and turn on 115 v power 5 Check auxili...

Page 14: ...46231 35006c Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 6a 8a PC 101 Catalog No 565 812 Printed in U S A Form 58DF 9SI Pg 14 11 93 Replaces 58DF 6SI ...

Reviews: