Advanced Setup Table

• MINIMUM HEAT/COOL SET POINT DIFFERENCE

— The Heat and Cool set points will not be allowed to
come any closer to each other than the value set in
Advanced Setup

Step 6, on page 2

. This minimum

difference is enforced during Auto changeover and
Program On operation.

• ENERGY SAVING SMART FAN — If Fan On is

selected, the fan will run continuously at all times,
except in Off mode, and will only run if there is a
heating or cooling demand.

• OVERRIDE — Press the Override button during a

programmed, unoccupied period to force the thermo-
stat into the Occupied 1 period, temporarily, up to
4 hours. If the Override button is pressed during an
Occupied period, the thermostat will be forced into
Unoccupied and the occupied period

(1,2 or 3)

, it

was forced out of will be turned off, only for that day.

• During Override periods the set points may be adjust-

ed, but they will not be remembered after Override
ends.

• FAN PURGE TIMER — When this feature is activated,

the fan will turn on during the Unoccupied period at a
preset amount of time prior to the Occupied 1 period.
This preoccupancy fan purge timer may be set as
instructed in

Step 13

from 0 to 3 hours. 0 = this feature

turned off.

• KEYPAD LOCK — To prevent unauthorized use of

the thermostat, the front panel buttons may be dis-
abled. To disable, or ‘lock’ the keypad, press and hold
the Mode button. While holding the Mode button,
simultaneously press the Up and Down buttons.

Locked

will appear on the display.

To

unlock

the buttons, again press and hold the

Mode button. While holding the Mode button, simul-
taneously press the Up and Down buttons.

Locked

will disappear from the display.

• DRY CONTACT SWITCH — The terminals are

‘normally open.’ Closing or completing the circuit will
cause the thermostat to enter Occupied 1. This fea-
ture allows an external device such as a central time
clock, occupancy sensor, or a telephone-activated
device to force one or more thermostats into Occu-
pied 1. For the dry contact to work the thermostat
must be in

Program On

.

Set Occupied 1 to Off for all

7 days,

so the Contact closure will be in control.

When the thermostat is forced into Occupied 1 via
the dry contact closure, the icon

Occupied 1

will blink.

Advanced Setup (cont)

STEP NO.

DESCRIPTION

RANGE

FACTORY

DEFAULT

1

Time of day clock set

24 hour

12:00 Am

2

Day of the week

Su - Sa

Mo

3

Fan Mode

Auto /

Auto

4

Heat Pump On or Off

Off / On

Off

5

Deadband or Temperature swing

1 - 6

2

6

Forced minimum difference
heat/cool

0 - 6

2

7

Cycles per hour

d, d1, 2 - 6

6

8

Security Levels

0 - 3

0

9

Maximum allowable Heat set point

35 - 99 F

80 F

10

Minimum allowable Cool set point

35 - 99 F

65 F

11

Fahrenheit or Centigrade

F / C

F

12

Thermoglow™ Backlight

Off / On

On

13

Fan Purge timer

0:00 - 3:00

0:00

14

Soft Start

0 - 99

0

15

Remote Sensor

Yes / No

No

About Advanced Features and Operation

IMPORTANT: For control of multiple thermostats by
one source, refer to Potential Phasing Problems
(document part no. 88-173) prior to installing.

 

Setup

 

 

ON

Setup

Setup

Setup

 

  

 

 

  

 

Locked

  

 

 

Press

Setup

  

Outside

 

Setup

       

  

Locked

unoccupied 

ON

Setup

Cool

Heat

CK1

GND

Summary of Contents for 53DFS250-FS

Page 1: ... SYS TEM BEFORE REMOVING THE OLD THERMOSTAT AND INSTALLING THE NEW THERMOSTAT SERIOUS PERSONAL INJURY COULD RESULT STEP 1 PREPARATION A Proper installation of the thermostat will be ac complished by following these step by step in structions If you are unsure about any of these steps call a qualified technician for assistance B Assemble tools and recommended junction box For best operation install...

Page 2: ...Conductor 18 gage unshielded cable from the thermostat to the remote sensor CK1 GND RS RS 5 H2 G2 C G1 Y O R Adjust the maximum allowable heat set point when security is in effect Step 8 only appears if Step 9 is not 0 35 to 99 F Locked Setup HEAT Select the security level 0 no security in effect 1 set point range limited 2 1 program on all times 3 2 prohibits set point changes Locked Setup Select...

Page 3: ...tons Locked will appear on the display To unlock the buttons again press and hold the Mode button While holding the Mode button simul taneously press the Up and Down buttons Locked will disappear from the display DRY CONTACT SWITCH The terminals are normally open Closing or completing the circuit will cause the thermostat to enter Occupied 1 This fea ture allows an external device such as a centra...

Page 4: ...ead the tem perature from the remote sensor and ignore the tem perature sensor inside the thermostat The thermostat automatically recognizes when a remote sensor is con nected When reading the temperature from the re mote the degree icon above the room temperature blinks once a second The Override button on the remote sensor works slightly different than the Override button on the front panel Each...

Reviews: