NOTE: Wiring schematic for the unit is located in plastic bag
on front of control box door.

SELECT UNIT

For Cooling with Electric Heat units see below. For Heat

Pump units see page 5. For Cooling Only units see page 7.

COOLING WITH ELECTRIC HEAT UNITS

Remove Existing Controls

1. Remove ALL 3 wires (yellow, white and orange) from

the fan cycle switch. See Fig. 6.

2. Remove the following wires from the push button switch:

a. Power cord wire from L1.
b. Yellow compressor wire from COMP.
c. Violet heater wire from HTR.
d. Grey heater wire from LS.
e. Black fan motor wire from HI.
f. Red fan motor wire from LO.
g. Pink L2 wire from L2.

3. Remove the thermostat and push button switch controls

and all remaining attached wires and discard. Remove
thermostat bulb and mounting bracket from front of coil
and discard with the thermostat control. See Fig. 7.

Install New Wall Thermostat Controls

1. Remove knockout on control box cover for thermostat

wiring interface. See Fig. 8.

2. Mount wall thermostat control panel to front control box

cover using 3 of the no. 10 hex head screws provided. See
Fig. 9-11.
NOTE: Be sure removable terminal block on control
board is lined up with hole in control box cover from
knockout in previous step.

3. Re-connect wiring to fan/cycle switch. See Fig. 6.

a. Black Hi Fan speed wire to top terminal on fan/

cycle switch.

b. Red Low Fan speed wire to bottom terminal on

fan/cycle switch.

c. Grey Fan wire (factory installed on printed circuit

board from Relay K3, see Fig. 12) to center termi-
nal on fan/cycle switch.

WIRING   SCHEMATIC

STANDARD PTAC MODELS

CONTROL PANEL
COVER PLATE

PUSH BUTTON
SWITCH

THERMOSTAT
KNOB

CONTROL BOX
COVER SCREWS

CONTROL PANEL COVER
PLATE ATTACHMENT SCREWS

TEMPERATURE
LIMITER

PUSH BUTTON SWITCH
ATTACHMENT SCREWS

THERMOSTAT CONTROL
ATTACHMENT SCREWS

Fig. 2 — Removing Front Panel

Fig. 5 — Thermostat Control and 

Push Button Switch

Fig. 3 — Control Panel Cover Plate

Fig. 4 — Temperature Limiter

Summary of Contents for 52S Wall Thermostat Interface Retrofit Kit

Page 1: ...ull firmly and discard See Fig 4 6 Open control box by removing the 2 control box cover screws shown in Fig 3 and swing the cover down to open Save the screws 7 Remove wire ties and discard making sure not to damage the wires 8 Remove Push Button Switch from control box door by removing 2 attachment screws and discard screws See Fig 5 9 Remove thermostat control from control box door by removing 2...

Page 2: ...hermostat Controls 1 Remove knockout on control box cover for thermostat wiring interface See Fig 8 2 Mount wall thermostat control panel to front control box cover using 3 of the no 10 hex head screws provided See Fig 9 11 NOTE Be sure removable terminal block on control board is lined up with hole in control box cover from knockout in previous step 3 Re connect wiring to fan cycle switch See Fig...

Page 3: ...RMOSTAT CONTROL PANEL MOUNTING SCREWS WALL THERMOSTAT CONTROL PANEL MOUNTING SCREW Fig 7 Thermostat Bulb and Mounting Bracket Fig 6 Fan Cycle Switch and Outdoor Frost Thermostat Fig 9 Wall Thermostat Control Panel Fig 8 Thermostat Wiring Knockout Fig 11 Secure Control Panel Front Fig 10 Secure Control Panel Top ...

Page 4: ...control box door and secure by re attaching screws saved earlier See Fig 3 10 Reinstall plastic control panel cover using the 2 screws removed earlier See Fig 3 Install Labels and Schematics 1 Remove old wiring schematic label and install new wiring schematic label in same location See Fig 16 2 Install conversion label to front of control box See Fig 16 3 Install Hi speed Low speed label next to f...

Page 5: ...e from L2 3 Remove the following wires from the Outdoor Frost Thermostat OFT See Fig 6 a Black Wire from Terminal 2 b Blue wire that is multi linked to the gray wire in Terminal 1 is no longer needed CUT Blue wire from Terminal 1 allowing about 3 inches of wire and attach included wire nut to end of Blue wire See Fig 19 Fig 15 Sensor Clip for Indoor Coil Freeze Thermostat IFT on Typical Unit WIRIN...

Page 6: ...ack male terminal to yellow wire already attached to terminal 3 of OFT Attach both wires back on to terminal 3 of OFT 6 Secure control board ground wire green to ground screw on control box door with power cord and chassis ground wires See Fig 13 7 Remove coil filter Install Indoor Coil Freeze Thermostat IFT into coil a Use a pen to make an opening in the fins 4 in from the right side of the coil ...

Page 7: ... the capacitor Connect the other end to L2 on relay K2A1 5 Re connect the following wires on control board See Fig 12 a Yellow compressor wire to COMP on relay Kl b Power Cord wire Ll to L1 brass post terminal on relay K2 6 Secure control board ground wire green to ground screw on control box door with power cord and chassis ground wires See Fig 13 7 Remove coil filter Install Indoor Coil Freeze T...

Page 8: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 132 Catalog No 535 20060 Printed in U S A Form 52S 67SI Pg 8 9 03 Replaces 52S 66SI Book 1 4 Tab 9a 11a Copyright 2003 Carrier Corporation ...

Reviews: