4. Remove the thermostat and push button switch controls

and all remaining attached wires and discard. Remove
thermostat bulb and mounting bracket from front of coil
and discard with the thermostat control. See Fig. 7.

Install New Wall Thermostat Controls

1. Remove knockout on control box cover for thermostat

wiring interface. See Fig. 8.

2. Mount wall thermostat control panel to front control box

cover using 3 of the no. 10 hex head screws provided. See
Fig. 9-11.
NOTE: Be sure removable terminal block on control
board is lined up with hole in control box cover from
knockout in previous step.

3. Re-connect wiring to fan/cycle switch. See Fig. 6.

a. Black Hi Fan speed wire to top terminal on fan/

cycle switch.

b. Red Low Fan speed wire to bottom terminal on

fan/cycle switch.

c. Grey Fan wire (factory installed on printed circuit

board from Relay K3, see Fig. 20) to center termi-
nal on fan/cycle switch.

4. Re-connect the following wires to control board. See

Fig. 20.

a. Violet heater wire to Heat2 on relay K2A1. 

NOTE: The male piggy back terminal is not used. This
terminal may either be removed or pinched back to fit the
connector onto Heat2 relay terminal.

b. Pink L2 wire to L2 (brass post terminal) on relay

K2Al.

c. Power Cord wire (Ll) to L1 (brass post terminal)

on relay K2.

d. One of the 2 black reversing valve wires to RVS

(no polarity).

e. Remaining black reversing valve wire to L2 (brass

post terminal) on relay K2A1.

NOTE: Black reversing valve wires are molded together
in a 2-wire bundle.

5. Connect the following wires from the control board to the

Outdoor Frost Control (OFT):

a. Red wire from Heat1 on relay K2 to terminal 2 of

OFT.

b. Yellow wire from COMP of relay K1 (with piggy

back male terminal) to yellow wire already
attached to terminal 3 of OFT. Attach both wires
back on to terminal 3 of OFT.

6. Secure control board ground wire (green) to ground

screw on control box door with power cord and chassis
ground wires. See Fig. 13.

7. Remove coil filter. Install Indoor Coil Freeze Thermostat

(IFT) into coil.
a. Use a pen to make an opening in the fins 4-in. from

the right side of the coil between the second and third
tube from the top to install freeze sensor  (Fig. 14).

b. Push freeze sensor into opening made in Step 7a.
c. Bend clip on scored line and install in fins (the curved

notches will lock clip in place) next to sensor to hold
sensor in place in the coil. See Fig. 15.

8. Replace filter (indoor coil freeze thermostat will be locat-

ed in the coil behind the filter).

9. Dress wires using wire ties provided.

10. Close the control box door and secure by re-attaching

screws saved earlier. See Fig. 3.

11. Reinstall plastic control panel cover using the 2 screws

removed earlier. See Fig. 3.

Install Labels and Schematics

1. Remove old wiring schematic label and install new wir-

ing schematic label in same location. See Fig. 16.

2. Install conversion label to front of control box. See

Fig. 16.

3. Install Hi Speed/Low Speed label next to fan cycle switch

on side of control box. See Fig. 17.
NOTE: Fan cycle switch now becomes a speed selector
switch and selects whether the fan runs in high speed or
low speed. It is recommended to set the switch to low fan
speed for maximum sound comfort. 

Fig. 19 — Cut Blue Wire from Terminal 1

PINK (L2 ON K2A1)

VIOLET (HEAT2 ON K2A1)

PLAIN POWER CORD
(L1 ON K2)

RED WIRE
(HEAT1 ON K2)

YELLOW WIRE
(COMP ON K1)

GREY FAN WIRE

BLACK WIRE FROM
REVERSING VALVE
TO RVS
(NO POLARITY)

BLACK WIRE FROM REVERSING
VALVE TO L2 ON K2A1
(NO POLARITY)

K1

K2

K2A1

Fig. 20 — Typical Wall Thermostat Interface Board Terminal Connections (Heat Pump Control Board Shown)

Summary of Contents for 52S Wall Thermostat Interface Retrofit Kit

Page 1: ...ull firmly and discard See Fig 4 6 Open control box by removing the 2 control box cover screws shown in Fig 3 and swing the cover down to open Save the screws 7 Remove wire ties and discard making sure not to damage the wires 8 Remove Push Button Switch from control box door by removing 2 attachment screws and discard screws See Fig 5 9 Remove thermostat control from control box door by removing 2...

Page 2: ...hermostat Controls 1 Remove knockout on control box cover for thermostat wiring interface See Fig 8 2 Mount wall thermostat control panel to front control box cover using 3 of the no 10 hex head screws provided See Fig 9 11 NOTE Be sure removable terminal block on control board is lined up with hole in control box cover from knockout in previous step 3 Re connect wiring to fan cycle switch See Fig...

Page 3: ...RMOSTAT CONTROL PANEL MOUNTING SCREWS WALL THERMOSTAT CONTROL PANEL MOUNTING SCREW Fig 7 Thermostat Bulb and Mounting Bracket Fig 6 Fan Cycle Switch and Outdoor Frost Thermostat Fig 9 Wall Thermostat Control Panel Fig 8 Thermostat Wiring Knockout Fig 11 Secure Control Panel Front Fig 10 Secure Control Panel Top ...

Page 4: ...control box door and secure by re attaching screws saved earlier See Fig 3 10 Reinstall plastic control panel cover using the 2 screws removed earlier See Fig 3 Install Labels and Schematics 1 Remove old wiring schematic label and install new wiring schematic label in same location See Fig 16 2 Install conversion label to front of control box See Fig 16 3 Install Hi speed Low speed label next to f...

Page 5: ...e from L2 3 Remove the following wires from the Outdoor Frost Thermostat OFT See Fig 6 a Black Wire from Terminal 2 b Blue wire that is multi linked to the gray wire in Terminal 1 is no longer needed CUT Blue wire from Terminal 1 allowing about 3 inches of wire and attach included wire nut to end of Blue wire See Fig 19 Fig 15 Sensor Clip for Indoor Coil Freeze Thermostat IFT on Typical Unit WIRIN...

Page 6: ...ack male terminal to yellow wire already attached to terminal 3 of OFT Attach both wires back on to terminal 3 of OFT 6 Secure control board ground wire green to ground screw on control box door with power cord and chassis ground wires See Fig 13 7 Remove coil filter Install Indoor Coil Freeze Thermostat IFT into coil a Use a pen to make an opening in the fins 4 in from the right side of the coil ...

Page 7: ... the capacitor Connect the other end to L2 on relay K2A1 5 Re connect the following wires on control board See Fig 12 a Yellow compressor wire to COMP on relay Kl b Power Cord wire Ll to L1 brass post terminal on relay K2 6 Secure control board ground wire green to ground screw on control box door with power cord and chassis ground wires See Fig 13 7 Remove coil filter Install Indoor Coil Freeze T...

Page 8: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 132 Catalog No 535 20060 Printed in U S A Form 52S 67SI Pg 8 9 03 Replaces 52S 66SI Book 1 4 Tab 9a 11a Copyright 2003 Carrier Corporation ...

Reviews: