background image

35

When the second stage of cooling is satisfied, the compres-

sor and condenser-fan motors will be deenergized. The damper
position will be determined by the supply-air temperature.

When the first stage of cooling is satisfied and the indoor

(evaporator) fan motor is deenergized, the damper will move to
fully closed position.
COOLING, UNIT WITH ECONOMI$ER — When the
outdoor-air temperature (OAT) is above the ECON SP set point
and the room thermostat calls for Stage 1 cooling (R to G +
Y1), the indoor-fan motor (IFM) is energized and the
EconoMi$er damper modulates to minimum position. The
compressor contactor and OFC are energized starting the com-
pressor and outdoor-fan motors (OFM). After the thermostat is
satisfied, the damper modulates to the fully closed position
when the IFM is deenergized.

When the OAT is below the ECON SP setting and the room

thermostat calls for Stage 1 cooling (R to G + Y1), the
EconoMi$er modulates to the minimum position when the
IFM is energized. The EconoMi$er provides Stage 1 of cooling
by modulating the return and outdoor air dampers to maintain a
55 F supply air set point. If the supply-air temperature (SAT) is
greater than 57 F, the EconoMi$er modulates open, allowing a
greater amount of outdoor air to enter the unit. If the SAT drops
below 53 F, the outdoor-air damper modulates closed to reduce
the amount of outdoor air. When the SAT is between 53 and
57 F, the EconoMi$er maintains its position.

If outdoor air alone cannot satisfy the cooling requirements

of the conditioned space, and the OAT is above the MECH
CLG LOCKOUT set point, the EconoMi$er integrates free
cooling with mechanical cooling. This is accomplished by the
strategies below.
NOTE: Compressors have a two-minute Minimum On, Mini-
mum Off, and Interstage delay timer.

1. If Y1 is energized, and the room thermostat calls for

Y2 (2-stage thermostat), the compressor number 1 and
OFM are energized. The position of the EconoMi$er
damper is maintained at its current value.

2. If Y1 is energized for more then 20 minutes, and Y2 is

not energized (whether or not a 2-stage thermostat is
used), compressor no. 1 and OFM are energized. The
position of the EconoMi$er damper is maintained at its
current value.

3. If Y1 is energized, and compressor no. 1 is already

energized and the room thermostat calls for Y2,
compressor no. 1 continues to operate. If Y2 remains
energized for more than 20 minutes, compressor no. 2
is energized.

NOTE: Compressor no. 2 cannot be energized unless there is a
signal for Y2 from the space thermostat.

4. If compressor no. 2 is energized, and the Y2 signal

from the thermostat is satisfied, compressor no. 1 and
2 are deenergized. If the thermostat reenergizes Y2
will start compressor no. 1 and (after a 20-minute
interstage delay) compressor no. 2.

5. If compressor no. 1 is energized and the thermostat is

satisfied, compressor no. 1, the OFM, and IFM are
deenergized and the EconoMi$er modulates closed.

When the OAT is below the MECH CLG LOCKOUT set

point, the compressors remain off.
HEATING, UNITS WITH DURABLADE ECONOMIZER
OR ECONOMI$ER — When the room thermostat calls for
heat, the heating controls are energized as described in the roof-
top unit Installation, Start-Up and Service Instructions.The IFM
is energized and the Durablade economizer or EconoMi$er
damper modulates to the minimum position. When the thermo-
stat is satisfied, the damper modulates closed.

SERVICE

Cleaning — 

Inspect unit interior and exterior at the begin-

ning of each heating and cooling season or more frequently as
operating conditions require.
EVAPORATOR COIL

1. Turn unit power off, tag disconnect. Remove evaporator

coil access panel.

2. If economizer is installed, remove economizer by discon-

necting Molex plug and removing economizer mounting
screws. Refer to Accessory Economizer Installation In-
structions or Optional Economizer sections, on pages 12
and 15 for more details.

3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher

detergent in a pressurized spray canister. Wash both
sides of coil and flush with clean water. For best results,
backflush toward return-air section to remove foreign
material.

5. Flush condensate pan after completion.
6. Reinstall economizer and filters.
7. Reconnect economizer wiring.
8. Replace access panels.

CONDENSER COIL — Inspect  coil  monthly.  Clean  con-
denser coil annually, or as required by location and outdoor-air
conditions.
One-Row Coil — Wash coil with commercial coil cleaner.
Clean the outer surfaces with a stiff brush in the normal man-
ner. It is not necessary to remove top panel.
Two-Row Coils — Clean coils as follows:

1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. See Fig. 46. To hold

top panel open, place coil corner post between top panel
and center post. See Fig. 47.

4. Remove screws securing coil to center post.
5. Remove fastener holding coil sections together at return

end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. See Fig. 48.

6. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and de-
bris. Clean the outer surfaces with a stiff brush in the nor-
mal manner.

7. Secure inner and outer coil rows together with fastener re-

moved in Step 5.

8. Reposition the outer coil section and remove the coil cor-

ner post between the top panel and center post. Reinstall
the coil corner post and replace all screws.

CONDENSATE DRAIN — Check  and  clean  each  year  at
start of cooling season. In winter, keep drain dry or protect
against freeze-up.
FILTERS — Clean or replace at start of each heating and cool-
ing season, or more often if operating conditions require it. Re-
placement filters must be same dimensions as original filters.

When servicing unit, shut off all electrical power to unit to
avoid shock hazard or injury from rotating parts.

Summary of Contents for 50TFF008-014

Page 1: ...Fig 2 In stall insulation cant strips roofing felt and counter flashing as shown Ductwork must be attached to curb not to unit If elec tric control power is to be routed through the basepan attach the...

Page 2: ...alled downstream from the external trap pitch the line away from the unit at 1 in per 10 ft of run Do not use a pipe size smaller than the unit connection Step 4 Rig and Place Unit Inspect unit for tr...

Page 3: ...ections B C D ALT DRAIN HOLE E GAS F POWER G CONTROL CONNECTOR PACKAGE ACCESSORY 2 87 16 827 1 1015 16 583 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 NPT CRBTMPWR001A00 11 4 31 7 NPT CRBTMPWR002A00 1 2...

Page 4: ...les in base rail as shown in detail A Holes in base rails are centered around the unit cen ter of gravity Use wooden top skid when rigging to prevent rig ging straps from damaging unit 3 Unit weights...

Page 5: ...head 60 in to assure proper condenser fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box side 36 in per NEC f Betw...

Page 6: ...0 2 90 5 25 High Static 3 70 3 70 5 25 Motor Frame Size Std 56 56 56 56 Alt 56 56 56 High Static 56 56 56 Nominal Rpm High Low Std Alt High Static 1725 1725 1725 1725 Fan Rpm Range Std 590 840 685 935...

Page 7: ...tructions Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low voltage connections on unit shown in Fig 11 as described in Steps 1 5 below NOTE For wire runs...

Page 8: ...24 0 32 0 66 7 77 0 90 6 103 5 100 110 83 95 31 9 42 4 88 4 102 0 117 7 134 8 125 150 108 124 High 10 6 49 4 49 4 60 60 52 52 365 365 7 8 10 4 21 7 25 0 49 4 49 4 60 60 52 52 12 0 16 0 33 4 38 5 54 9...

Page 9: ...4 0 36 0 50 1 60 46 51 0 51 2 58 6 70 66 014 208 230 3 60 Std 187 254 23 0 146 0 2 1 4 1 4 10 6 65 2 65 2 80 80 68 68 383 383 7 8 10 4 21 7 25 0 65 2 65 2 80 80 68 68 12 0 16 0 33 4 38 5 65 2 65 2 70...

Page 10: ...ce Example Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 457 Determine maximum deviation from average voltage AB 457 452 5 v BC 464 457 7 v AC 457 455 2 v Maximum deviation is 7 v Determine pe...

Page 11: ...attached to the basepan at the bottom of the unit for shipping MAIN CONTROL BOX BOX SINGLE POINT BOX MOUNTING SCREW DISCONNECT MOUNTING LOCATION EMT OR RIGID CONDUIT FIELD SUPPLIED BRACKET AND CONDUI...

Page 12: ...d record quantity of ventilation air needed for use in Step 8 2 Remove filter access panel by raising panel and swinging panel outward Panel is now disengaged from track and can be removed No tools ar...

Page 13: ...thermostat set ting If accessory enthalpy control EC is used in place of OAT see instructions shipped with EC for installation and adjustment See Fig 26 13 Connect OAT per Fig 27 14 Slide outdoor air...

Page 14: ...blade Economizer Installed in Unit Fig 22 Horizontal Durablade Economizer Installation 90 Degree Rotation Fig 23 Horizontal Discharge Block Off Plate EXAMPLE Given Negative Pressure 0 1 in wg Outdoor...

Page 15: ...ed on back sloped side of EconoMi er assembly These brackets are used to retain hood assembly during shipping only MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I...

Page 16: ...er exhaust is being installed complete installation of power exhaust at this time See Fig 38 for wiring 10 Install the complete hood assembly on the unit and secure using the screws provided 11 Remove...

Page 17: ...E UNIT BASE UNIT FILTER RACK ECONOMIZER CLIP HVAC UNIT Fig 35 Rear EconoMi er Flange Installation WIRING HARNESS OUTDOOR AIR BLOCK OFF PLATE Fig 36 EconoMi er Installed in Unit LEGEND OAT Outdoor Air...

Page 18: ...OWN ORANGE 3 PIN CONNECTOR PLUG YELLOW RED YEL H1 BLU GRAY H4 SECONDARY 230VAC X4 X1 HT01AH850 460 VAC RED H1 GRAY H2 SECONDARY 230VAC X4 X1 HT01AH859 575 VAC 23 13 11 21 230VAC OR BLACK L1 BLUE L2 CO...

Page 19: ...tiome ter Turn the potentiometer full CCW to fully close the outdoor air dampers Turn the potentiometer gradually clockwise CW to the desired position See Fig 40 3 Replace the filter access panel See...

Page 20: ...earest flat of pulley hub and tight en setscrew see Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along f...

Page 21: ...35 615 590 008 935 910 885 860 835 810 785 760 735 710 685 008 1080 1025 1007 988 970 952 933 915 897 878 860 009 935 910 885 860 835 810 785 760 735 710 685 009 1080 1025 1007 988 970 952 933 915 897...

Page 22: ...1173 773 1 55 1378 827 1 83 1621 878 2 12 1875 2800 597 0 89 827 665 1 12 1014 733 1 40 1250 786 1 66 1473 839 1 93 1709 889 2 23 1971 2900 613 0 97 891 679 1 20 1081 745 1 50 1335 799 1 76 1560 850 2...

Page 23: ...3 1147 815 1 92 1700 866 2 23 1971 3100 646 1 16 1047 714 1 45 1292 773 1 74 1543 828 2 04 1805 878 2 35 2076 3200 662 1 28 1131 729 1 55 1378 787 1 86 1648 841 2 16 1910 891 2 48 2188 3300 679 1 36 1...

Page 24: ...2 15 1901 911 2 46 2171 3100 646 1 15 1039 709 1 39 1241 772 1 70 1508 825 1 99 1761 875 2 28 2015 923 2 58 2275 3200 662 1 25 1123 724 1 50 1335 785 1 80 1595 840 2 11 1866 887 2 41 2128 934 2 71 238...

Page 25: ...8 816 2 10 1958 867 2 42 2136 917 2 75 2420 3500 712 1 59 1413 774 1 90 1683 830 2 23 1971 881 2 56 2257 930 2 90 2546 3600 729 1 71 1517 790 2 03 1796 845 2 37 2093 895 2 71 2386 943 3 05 2670 3700 7...

Page 26: ...878 2 22 1962 922 2 44 2203 4100 675 1 42 1267 734 1 67 1482 790 1 89 1674 839 2 12 1875 888 2 33 2058 933 2 56 2309 4200 689 1 52 1353 746 1 77 1569 801 1 99 1761 851 2 23 1971 898 2 45 2212 943 2 6...

Page 27: ...2602 967 3 17 2828 1006 3 43 3065 1043 3 65 3267 5000 843 2 52 2246 892 2 81 2503 937 3 08 2746 980 3 32 2964 1019 3 60 3221 1055 3 82 3424 5100 858 2 67 2378 906 2 95 2629 950 3 24 2891 993 3 48 311...

Page 28: ...932 693 1 27 1140 756 1 57 1396 813 1 84 1630 3000 559 0 83 779 637 1 09 989 704 1 35 1207 765 1 66 1473 823 1 94 1718 3100 572 0 90 835 648 1 17 1056 715 1 43 1275 775 1 74 1543 832 2 05 1814 3200 58...

Page 29: ...100 636 1 11 1006 704 1 39 1241 764 1 69 1499 818 1 97 1744 870 2 29 2023 3200 652 1 21 1089 718 1 49 1327 778 1 90 1595 831 2 09 1849 882 2 40 2119 3300 668 1 31 1173 732 1 59 1413 793 1 92 1700 844...

Page 30: ...1 03 940 671 1 32 1182 739 1 62 1439 795 1 91 1691 851 2 26 1997 3400 610 1 10 998 682 1 41 1258 750 1 72 1526 806 2 01 1779 860 2 36 2084 3500 623 1 17 1056 694 1 50 1335 761 1 82 1613 817 2 11 1866...

Page 31: ...2343 3500 701 1 53 1361 762 1 82 1613 821 2 16 1910 871 2 48 2188 919 2 80 2462 3600 717 1 65 1465 777 1 94 1718 835 2 29 2023 885 2 63 2317 932 2 95 2587 3700 733 1 77 1569 792 2 07 1831 849 2 42 21...

Page 32: ...3 789 1 95 1726 841 2 18 1927 4300 628 1 56 1387 690 1 63 1447 747 1 83 1621 798 2 05 1814 849 2 30 2032 4400 639 1 67 1482 701 1 73 1534 757 1 92 1700 807 2 16 1910 858 2 41 2177 4500 651 1 78 1578 7...

Page 33: ...09 3 09 2755 955 3 42 3056 998 3 69 3304 5400 869 2 92 2602 882 3 01 2683 920 3 24 2891 967 3 57 3193 1009 3 86 3461 5500 885 3 09 2755 897 3 17 2828 932 3 38 3019 978 3 72 3331 1029 4 03 3618 5600 90...

Page 34: ...ter is Installed To start unit turn on main power supply Set thermostat at HEAT position and a setting above room temperature and set fan at AUTO position First stage of thermostat energizes the first...

Page 35: ...1 the OFM and IFM are deenergized and the EconoMi er modulates closed When the OAT is below the MECH CLG LOCKOUT set point the compressors remain off HEATING UNITS WITH DURABLADE ECONOMIZER OR ECONOMI...

Page 36: ...AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with R 22 refrigerant tested and factory sealed Unit must operate in Cooling mode a minimum of 10 minutes before checking charg...

Page 37: ...ssure gage Refer to ap propriate chart to determine what suction temperature should be If suction temperature is high add refrigerant If suction temperature is low carefully recover some of the charge...

Page 38: ...38 CIRCUIT NO 2 CIRCUIT NO 1 Fig 52 Cooling Charging Chart 50TFF012 Fig 53 Cooling Charging Chart 50TFF014...

Page 39: ...ontinuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge...

Page 40: ...OAT and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired...

Page 41: ...ical panel The fault condition is caused by Y2 being energized before Y1 Actuator fault Check the wiring between the EconoMi er controller and the actuator Hold CONFIG button between three and ten sec...

Page 42: ...tinue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00010 Printed in U S A Form 50TFF 2SI Pg 42 8 00 Replaces New Book 1 4 Tab...

Page 43: ......

Page 44: ...AS SHOWN IN THE INSTALLATION INSTRUCTIONS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL WITH...

Reviews: