29

Table 16 — Fan Performance, 50TFF008 High-Static Motor — Horizontal Discharge Units

LEGEND

*Motor drive range: 860 to 1080 rpm. All other rpms require field-

supplied drive.

NOTES:

1. Boldface indicates field-supplied drive is required.

2.

 indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casing, and wet coils. See

Table 7 for accessory/FIOP static pressure information.

4. Maximum continuous bhp is 3.7 and the maximum continuous

watts are 3313. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings
shown will not result in nuisance tripping or premature motor fail-
ure. Unit warranty will not be affected. See Table 8 for additional
information.

5. Use of a field-supplied motor may affect wire sizing. Contact

your Carrier representative for details.

6. Interpolation is permissible. Do not extrapolate.

50TFF008 (7

1

/

TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2250

507

0.53

547

586

0.73

700

658

0.97

891

722

1.22

1097

783

1.46

1301

2300

513

0.55

562

592

0.76

723

663

1.00

916

727

1.26

1131

786

1.49

1327

2400

528

0.60

600

606

0.83

779

674

1.06

965

738

1.34

1199

795

1.58

1404

2500

542

0.68

648

619

0.90

835

686

1.13

1022

748

1.41

1258

806

1.68

1491

2550

550

0.69

669

627

0.94

867

692

1.17

1056

754

1.45

1292

812

1.74

1543

2660

557

0.72

692

634

0.97

891

698

1.21

1089

759

1.49

1327

816

1.79

1587

2700

573

0.79

747

648

1.05

956

711

1.29

1156

770

1.58

1404

827

1.88

1665

2800

588

0.86

803

662

1.13

1022

723

1.38

1233

782

1.66

1473

837

1.98

1763

2900

604

0.94

867

676

1.21

1089

737

1.48

1318

794

1.76

1560

849

2.08

1840

3000

620

1.02

932

690

1.30

1165

750

1.58

1404

806

1.86

1648

849

2.18

1927

3100

636

1.11

1006

704

1.39

1241

764

1.69

1499

818

1.97

1744

870

2.29

2023

3200

652

1.21

1089

718

1.49

1327

778

1.90

1595

831

2.09

1849

882

2.40

2119

3300

668

1.31

1173

732

1.59

1413

793

1.92

1700

844

2.21

1954

894

2.53

2232

3400

684

1.41

1258

747

1.70

1508

807

2.04

1805

857

2.35

2076

907

2.66

2343

3500

701

1.53

1361

762

1.82

1613

821

2.16

1010

871

2.48

2188

919

2.80

2462

3600

717

1.65

1465

777

1.94

1718

835

2.29

2023

885

2.63

2317

932

2.95

2587

3700

733

1.77

1569

792

2.07

1831

849

2.42

2136

899

2.78

2445

945

3.11

2718

3750

742

1.84

1630

800

2.14

1892

856

2.49

2197

907

2.86

2512

952

3.20

2719

50TFF008 (7

1

/

2

 TONS — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

2250

843

1.81

1604

908

2.25

1989

955

2.59

2283

991

2.89

2543

1023

3.19

2805

2300

846

1.84

1630

910

2.25

2015

959

2.61

2300

995

2.91

2563

1028

3.21

2827

2400

853

1.88

1665

912

2.31

2041

967

2.68

2360

1003

2.99

2631

1036

3.30

2902

2500

859

1.94

1718

919

2.37

2093

971

2.73

2403

1007

3.05

2681

1041

3.36

2956

2550

864

1.99

1761

920

2.39

2110

974

2.76

2428

1010

3.08

2710

1044

3.40

2989

2660

868

2.04

1805

921

2.41

2136

976

2.78

2445

1012

3.10

2730

1046

3.42

3011

2700

878

2.16

1910

928

2.45

2162

983

2.88

2529

1020

3.21

2828

1053

3.54

3119

2800

889

2.29

2023

937

2.57

2266

986

2.91

2554

1023

3.25

2857

1057

3.58

3181

2900

900

2.41

2128

947

2.70

2377

993

3.01

2637

1030

3.36

2955

1064

3.70

3260

3000

910

2.52

2223

958

2.85

2504

1002

3.15

2751

1039

3.51

3093

1074

3.88

3411

3100

920

2.64

2326

968

2.99

2620

1012

3.30

2870

1050

3.68

3240

1084

4.06

3574

3200

931

2.76

2428

979

3.13

2735

1023

3.47

3002

1061

3.87

3407

3300

942

2.89

2537

989

3.26

2839

1034

3.63

3121

1072

4.05

3564

3400

954

3.02

2645

1000

3.40

2948

1044

3.79

3237

3500

966

3.15

2751

1011

3.55

3062

1054

3.94

3340

3600

978

3.30

2870

1022

3.69

3165

1065

4.10

3445

3700

990

3.45

2987

1034

3.84

3272

3750

997

3.54

3055

1040

3.93

3333

Bhp

— Brake Horsepower Input to Fan

FIOP — Factory-Installed Option
Watts — Input Watts to Motor

Summary of Contents for 50TFF008-014

Page 1: ...Fig 2 In stall insulation cant strips roofing felt and counter flashing as shown Ductwork must be attached to curb not to unit If elec tric control power is to be routed through the basepan attach the...

Page 2: ...alled downstream from the external trap pitch the line away from the unit at 1 in per 10 ft of run Do not use a pipe size smaller than the unit connection Step 4 Rig and Place Unit Inspect unit for tr...

Page 3: ...ections B C D ALT DRAIN HOLE E GAS F POWER G CONTROL CONNECTOR PACKAGE ACCESSORY 2 87 16 827 1 1015 16 583 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 NPT CRBTMPWR001A00 11 4 31 7 NPT CRBTMPWR002A00 1 2...

Page 4: ...les in base rail as shown in detail A Holes in base rails are centered around the unit cen ter of gravity Use wooden top skid when rigging to prevent rig ging straps from damaging unit 3 Unit weights...

Page 5: ...head 60 in to assure proper condenser fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box side 36 in per NEC f Betw...

Page 6: ...0 2 90 5 25 High Static 3 70 3 70 5 25 Motor Frame Size Std 56 56 56 56 Alt 56 56 56 High Static 56 56 56 Nominal Rpm High Low Std Alt High Static 1725 1725 1725 1725 Fan Rpm Range Std 590 840 685 935...

Page 7: ...tructions Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low voltage connections on unit shown in Fig 11 as described in Steps 1 5 below NOTE For wire runs...

Page 8: ...24 0 32 0 66 7 77 0 90 6 103 5 100 110 83 95 31 9 42 4 88 4 102 0 117 7 134 8 125 150 108 124 High 10 6 49 4 49 4 60 60 52 52 365 365 7 8 10 4 21 7 25 0 49 4 49 4 60 60 52 52 12 0 16 0 33 4 38 5 54 9...

Page 9: ...4 0 36 0 50 1 60 46 51 0 51 2 58 6 70 66 014 208 230 3 60 Std 187 254 23 0 146 0 2 1 4 1 4 10 6 65 2 65 2 80 80 68 68 383 383 7 8 10 4 21 7 25 0 65 2 65 2 80 80 68 68 12 0 16 0 33 4 38 5 65 2 65 2 70...

Page 10: ...ce Example Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 457 Determine maximum deviation from average voltage AB 457 452 5 v BC 464 457 7 v AC 457 455 2 v Maximum deviation is 7 v Determine pe...

Page 11: ...attached to the basepan at the bottom of the unit for shipping MAIN CONTROL BOX BOX SINGLE POINT BOX MOUNTING SCREW DISCONNECT MOUNTING LOCATION EMT OR RIGID CONDUIT FIELD SUPPLIED BRACKET AND CONDUI...

Page 12: ...d record quantity of ventilation air needed for use in Step 8 2 Remove filter access panel by raising panel and swinging panel outward Panel is now disengaged from track and can be removed No tools ar...

Page 13: ...thermostat set ting If accessory enthalpy control EC is used in place of OAT see instructions shipped with EC for installation and adjustment See Fig 26 13 Connect OAT per Fig 27 14 Slide outdoor air...

Page 14: ...blade Economizer Installed in Unit Fig 22 Horizontal Durablade Economizer Installation 90 Degree Rotation Fig 23 Horizontal Discharge Block Off Plate EXAMPLE Given Negative Pressure 0 1 in wg Outdoor...

Page 15: ...ed on back sloped side of EconoMi er assembly These brackets are used to retain hood assembly during shipping only MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I...

Page 16: ...er exhaust is being installed complete installation of power exhaust at this time See Fig 38 for wiring 10 Install the complete hood assembly on the unit and secure using the screws provided 11 Remove...

Page 17: ...E UNIT BASE UNIT FILTER RACK ECONOMIZER CLIP HVAC UNIT Fig 35 Rear EconoMi er Flange Installation WIRING HARNESS OUTDOOR AIR BLOCK OFF PLATE Fig 36 EconoMi er Installed in Unit LEGEND OAT Outdoor Air...

Page 18: ...OWN ORANGE 3 PIN CONNECTOR PLUG YELLOW RED YEL H1 BLU GRAY H4 SECONDARY 230VAC X4 X1 HT01AH850 460 VAC RED H1 GRAY H2 SECONDARY 230VAC X4 X1 HT01AH859 575 VAC 23 13 11 21 230VAC OR BLACK L1 BLUE L2 CO...

Page 19: ...tiome ter Turn the potentiometer full CCW to fully close the outdoor air dampers Turn the potentiometer gradually clockwise CW to the desired position See Fig 40 3 Replace the filter access panel See...

Page 20: ...earest flat of pulley hub and tight en setscrew see Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along f...

Page 21: ...35 615 590 008 935 910 885 860 835 810 785 760 735 710 685 008 1080 1025 1007 988 970 952 933 915 897 878 860 009 935 910 885 860 835 810 785 760 735 710 685 009 1080 1025 1007 988 970 952 933 915 897...

Page 22: ...1173 773 1 55 1378 827 1 83 1621 878 2 12 1875 2800 597 0 89 827 665 1 12 1014 733 1 40 1250 786 1 66 1473 839 1 93 1709 889 2 23 1971 2900 613 0 97 891 679 1 20 1081 745 1 50 1335 799 1 76 1560 850 2...

Page 23: ...3 1147 815 1 92 1700 866 2 23 1971 3100 646 1 16 1047 714 1 45 1292 773 1 74 1543 828 2 04 1805 878 2 35 2076 3200 662 1 28 1131 729 1 55 1378 787 1 86 1648 841 2 16 1910 891 2 48 2188 3300 679 1 36 1...

Page 24: ...2 15 1901 911 2 46 2171 3100 646 1 15 1039 709 1 39 1241 772 1 70 1508 825 1 99 1761 875 2 28 2015 923 2 58 2275 3200 662 1 25 1123 724 1 50 1335 785 1 80 1595 840 2 11 1866 887 2 41 2128 934 2 71 238...

Page 25: ...8 816 2 10 1958 867 2 42 2136 917 2 75 2420 3500 712 1 59 1413 774 1 90 1683 830 2 23 1971 881 2 56 2257 930 2 90 2546 3600 729 1 71 1517 790 2 03 1796 845 2 37 2093 895 2 71 2386 943 3 05 2670 3700 7...

Page 26: ...878 2 22 1962 922 2 44 2203 4100 675 1 42 1267 734 1 67 1482 790 1 89 1674 839 2 12 1875 888 2 33 2058 933 2 56 2309 4200 689 1 52 1353 746 1 77 1569 801 1 99 1761 851 2 23 1971 898 2 45 2212 943 2 6...

Page 27: ...2602 967 3 17 2828 1006 3 43 3065 1043 3 65 3267 5000 843 2 52 2246 892 2 81 2503 937 3 08 2746 980 3 32 2964 1019 3 60 3221 1055 3 82 3424 5100 858 2 67 2378 906 2 95 2629 950 3 24 2891 993 3 48 311...

Page 28: ...932 693 1 27 1140 756 1 57 1396 813 1 84 1630 3000 559 0 83 779 637 1 09 989 704 1 35 1207 765 1 66 1473 823 1 94 1718 3100 572 0 90 835 648 1 17 1056 715 1 43 1275 775 1 74 1543 832 2 05 1814 3200 58...

Page 29: ...100 636 1 11 1006 704 1 39 1241 764 1 69 1499 818 1 97 1744 870 2 29 2023 3200 652 1 21 1089 718 1 49 1327 778 1 90 1595 831 2 09 1849 882 2 40 2119 3300 668 1 31 1173 732 1 59 1413 793 1 92 1700 844...

Page 30: ...1 03 940 671 1 32 1182 739 1 62 1439 795 1 91 1691 851 2 26 1997 3400 610 1 10 998 682 1 41 1258 750 1 72 1526 806 2 01 1779 860 2 36 2084 3500 623 1 17 1056 694 1 50 1335 761 1 82 1613 817 2 11 1866...

Page 31: ...2343 3500 701 1 53 1361 762 1 82 1613 821 2 16 1910 871 2 48 2188 919 2 80 2462 3600 717 1 65 1465 777 1 94 1718 835 2 29 2023 885 2 63 2317 932 2 95 2587 3700 733 1 77 1569 792 2 07 1831 849 2 42 21...

Page 32: ...3 789 1 95 1726 841 2 18 1927 4300 628 1 56 1387 690 1 63 1447 747 1 83 1621 798 2 05 1814 849 2 30 2032 4400 639 1 67 1482 701 1 73 1534 757 1 92 1700 807 2 16 1910 858 2 41 2177 4500 651 1 78 1578 7...

Page 33: ...09 3 09 2755 955 3 42 3056 998 3 69 3304 5400 869 2 92 2602 882 3 01 2683 920 3 24 2891 967 3 57 3193 1009 3 86 3461 5500 885 3 09 2755 897 3 17 2828 932 3 38 3019 978 3 72 3331 1029 4 03 3618 5600 90...

Page 34: ...ter is Installed To start unit turn on main power supply Set thermostat at HEAT position and a setting above room temperature and set fan at AUTO position First stage of thermostat energizes the first...

Page 35: ...1 the OFM and IFM are deenergized and the EconoMi er modulates closed When the OAT is below the MECH CLG LOCKOUT set point the compressors remain off HEATING UNITS WITH DURABLADE ECONOMIZER OR ECONOMI...

Page 36: ...AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with R 22 refrigerant tested and factory sealed Unit must operate in Cooling mode a minimum of 10 minutes before checking charg...

Page 37: ...ssure gage Refer to ap propriate chart to determine what suction temperature should be If suction temperature is high add refrigerant If suction temperature is low carefully recover some of the charge...

Page 38: ...38 CIRCUIT NO 2 CIRCUIT NO 1 Fig 52 Cooling Charging Chart 50TFF012 Fig 53 Cooling Charging Chart 50TFF014...

Page 39: ...ontinuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge...

Page 40: ...OAT and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired...

Page 41: ...ical panel The fault condition is caused by Y2 being energized before Y1 Actuator fault Check the wiring between the EconoMi er controller and the actuator Hold CONFIG button between three and ten sec...

Page 42: ...tinue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00010 Printed in U S A Form 50TFF 2SI Pg 42 8 00 Replaces New Book 1 4 Tab...

Page 43: ......

Page 44: ...AS SHOWN IN THE INSTALLATION INSTRUCTIONS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL WITH...

Reviews: