Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1-33

Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . . . . 1

• ROOF  CURB
• SLAB MOUNT

Step 2 — Field Fabricate Ductwork

. . . . . . . . . . . . . . . 1

Step 3 — Install External Trap for

Condensate Drain

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Step 4 — Rig and Place Unit

 . . . . . . . . . . . . . . . . . . . . . 2

• POSITIONING

Step 5 — Make Electrical Connections

 . . . . . . . . . . . 7

• FIELD POWER SUPPLY
• FIELD CONTROL WIRING

Step 6 — Adjust Factory-Installed

Options

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

• APOLLO CONTROL
• MANUAL OUTDOOR-AIR DAMPER
• OPTIONAL DURABLADE ECONOMIZER
• OPTIONAL ECONOMI$ER

Step 7 — Adjust Evaporator-Fan Speed

 . . . . . . . . . 20

START-UP

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34,35

SERVICE

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  35-38

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . .  39-41

START-UP CHECKLIST

. . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing air-conditioning equipment can be

hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, re-
pair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func-

tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.    

INSTALLATION

Unit is shipped in the vertical discharge configuration. To

convert to horizontal configuration, remove screws from hori-
zontal duct opening covers and remove covers. Using the same
screws, install covers on duct openings in basepan of unit with
the insulation-side down. Seals around duct openings must be
tight. See Fig. 1.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb in
accordance with instructions shipped with curb. See Fig. 2. In-
stall insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to curb, not to unit. If elec-
tric control power is to be routed through the basepan, attach
the accessory thru-the-bottom service connections to the roof
curb in accordance with the accessory installation instructions.
Connection must be installed before unit is set on roof curb.

Curb should be level. This is necessary for unit drain to

function properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for ad-
ditional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide  a  level
concrete slab that extends a minimum of 6 in. beyond unit cab-
inet. Install a 6-in. gravel apron in front of outdoor-coil air inlet
to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.

Step 2 — Field Fabricate Ductwork — 

On verti-

cal discharge units, secure all ducts to roof curb and building
structure. Do not connect ductwork to unit. For horizontal ap-
plications, field-supplied isolation flanges should be attached
to horizontal discharge openings and all ductwork attached to
the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.

Ducts passing through an unconditioned space must be in-

sulated and covered with a vapor barrier.

If plenum return is used on a vertical unit, the return should

be ducted through the roof deck to comply with applicable fire
codes.

If electrical connections are to be routed through the

bottom of the unit, attach accessory thru-the-bottom service
connections to the basepan in accordance with installation
instructions.

Before performing service or maintenance operations on
unit, turn off main power switch to unit and tag. Electrical
shock could cause personal injury.

Ensure voltage listed on unit data plate agrees with electri-
cal supply provided for the unit.

IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.

50TFF008-014

Single-Package Rooftop Cooling Units

Summary of Contents for 50TFF008-014

Page 1: ...Fig 2 In stall insulation cant strips roofing felt and counter flashing as shown Ductwork must be attached to curb not to unit If elec tric control power is to be routed through the basepan attach the...

Page 2: ...alled downstream from the external trap pitch the line away from the unit at 1 in per 10 ft of run Do not use a pipe size smaller than the unit connection Step 4 Rig and Place Unit Inspect unit for tr...

Page 3: ...ections B C D ALT DRAIN HOLE E GAS F POWER G CONTROL CONNECTOR PACKAGE ACCESSORY 2 87 16 827 1 1015 16 583 13 4 44 5 3 4 19 NPT 3 4 19 NPT 1 2 12 7 NPT CRBTMPWR001A00 11 4 31 7 NPT CRBTMPWR002A00 1 2...

Page 4: ...les in base rail as shown in detail A Holes in base rails are centered around the unit cen ter of gravity Use wooden top skid when rigging to prevent rig ging straps from damaging unit 3 Unit weights...

Page 5: ...head 60 in to assure proper condenser fan operation d Between units control box side 42 in per NEC National Electrical Code e Between unit and ungrounded surfaces control box side 36 in per NEC f Betw...

Page 6: ...0 2 90 5 25 High Static 3 70 3 70 5 25 Motor Frame Size Std 56 56 56 56 Alt 56 56 56 High Static 56 56 56 Nominal Rpm High Low Std Alt High Static 1725 1725 1725 1725 Fan Rpm Range Std 590 840 685 935...

Page 7: ...tructions Route thermostat cable or equivalent single leads of colored wire from subbase terminals to low voltage connections on unit shown in Fig 11 as described in Steps 1 5 below NOTE For wire runs...

Page 8: ...24 0 32 0 66 7 77 0 90 6 103 5 100 110 83 95 31 9 42 4 88 4 102 0 117 7 134 8 125 150 108 124 High 10 6 49 4 49 4 60 60 52 52 365 365 7 8 10 4 21 7 25 0 49 4 49 4 60 60 52 52 12 0 16 0 33 4 38 5 54 9...

Page 9: ...4 0 36 0 50 1 60 46 51 0 51 2 58 6 70 66 014 208 230 3 60 Std 187 254 23 0 146 0 2 1 4 1 4 10 6 65 2 65 2 80 80 68 68 383 383 7 8 10 4 21 7 25 0 65 2 65 2 80 80 68 68 12 0 16 0 33 4 38 5 65 2 65 2 70...

Page 10: ...ce Example Supply voltage is 460 3 60 AB 452 v BC 464 v AC 455 v 457 Determine maximum deviation from average voltage AB 457 452 5 v BC 464 457 7 v AC 457 455 2 v Maximum deviation is 7 v Determine pe...

Page 11: ...attached to the basepan at the bottom of the unit for shipping MAIN CONTROL BOX BOX SINGLE POINT BOX MOUNTING SCREW DISCONNECT MOUNTING LOCATION EMT OR RIGID CONDUIT FIELD SUPPLIED BRACKET AND CONDUI...

Page 12: ...d record quantity of ventilation air needed for use in Step 8 2 Remove filter access panel by raising panel and swinging panel outward Panel is now disengaged from track and can be removed No tools ar...

Page 13: ...thermostat set ting If accessory enthalpy control EC is used in place of OAT see instructions shipped with EC for installation and adjustment See Fig 26 13 Connect OAT per Fig 27 14 Slide outdoor air...

Page 14: ...blade Economizer Installed in Unit Fig 22 Horizontal Durablade Economizer Installation 90 Degree Rotation Fig 23 Horizontal Discharge Block Off Plate EXAMPLE Given Negative Pressure 0 1 in wg Outdoor...

Page 15: ...ed on back sloped side of EconoMi er assembly These brackets are used to retain hood assembly during shipping only MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I...

Page 16: ...er exhaust is being installed complete installation of power exhaust at this time See Fig 38 for wiring 10 Install the complete hood assembly on the unit and secure using the screws provided 11 Remove...

Page 17: ...E UNIT BASE UNIT FILTER RACK ECONOMIZER CLIP HVAC UNIT Fig 35 Rear EconoMi er Flange Installation WIRING HARNESS OUTDOOR AIR BLOCK OFF PLATE Fig 36 EconoMi er Installed in Unit LEGEND OAT Outdoor Air...

Page 18: ...OWN ORANGE 3 PIN CONNECTOR PLUG YELLOW RED YEL H1 BLU GRAY H4 SECONDARY 230VAC X4 X1 HT01AH850 460 VAC RED H1 GRAY H2 SECONDARY 230VAC X4 X1 HT01AH859 575 VAC 23 13 11 21 230VAC OR BLACK L1 BLUE L2 CO...

Page 19: ...tiome ter Turn the potentiometer full CCW to fully close the outdoor air dampers Turn the potentiometer gradually clockwise CW to the desired position See Fig 40 3 Replace the filter access panel See...

Page 20: ...earest flat of pulley hub and tight en setscrew see Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along f...

Page 21: ...35 615 590 008 935 910 885 860 835 810 785 760 735 710 685 008 1080 1025 1007 988 970 952 933 915 897 878 860 009 935 910 885 860 835 810 785 760 735 710 685 009 1080 1025 1007 988 970 952 933 915 897...

Page 22: ...1173 773 1 55 1378 827 1 83 1621 878 2 12 1875 2800 597 0 89 827 665 1 12 1014 733 1 40 1250 786 1 66 1473 839 1 93 1709 889 2 23 1971 2900 613 0 97 891 679 1 20 1081 745 1 50 1335 799 1 76 1560 850 2...

Page 23: ...3 1147 815 1 92 1700 866 2 23 1971 3100 646 1 16 1047 714 1 45 1292 773 1 74 1543 828 2 04 1805 878 2 35 2076 3200 662 1 28 1131 729 1 55 1378 787 1 86 1648 841 2 16 1910 891 2 48 2188 3300 679 1 36 1...

Page 24: ...2 15 1901 911 2 46 2171 3100 646 1 15 1039 709 1 39 1241 772 1 70 1508 825 1 99 1761 875 2 28 2015 923 2 58 2275 3200 662 1 25 1123 724 1 50 1335 785 1 80 1595 840 2 11 1866 887 2 41 2128 934 2 71 238...

Page 25: ...8 816 2 10 1958 867 2 42 2136 917 2 75 2420 3500 712 1 59 1413 774 1 90 1683 830 2 23 1971 881 2 56 2257 930 2 90 2546 3600 729 1 71 1517 790 2 03 1796 845 2 37 2093 895 2 71 2386 943 3 05 2670 3700 7...

Page 26: ...878 2 22 1962 922 2 44 2203 4100 675 1 42 1267 734 1 67 1482 790 1 89 1674 839 2 12 1875 888 2 33 2058 933 2 56 2309 4200 689 1 52 1353 746 1 77 1569 801 1 99 1761 851 2 23 1971 898 2 45 2212 943 2 6...

Page 27: ...2602 967 3 17 2828 1006 3 43 3065 1043 3 65 3267 5000 843 2 52 2246 892 2 81 2503 937 3 08 2746 980 3 32 2964 1019 3 60 3221 1055 3 82 3424 5100 858 2 67 2378 906 2 95 2629 950 3 24 2891 993 3 48 311...

Page 28: ...932 693 1 27 1140 756 1 57 1396 813 1 84 1630 3000 559 0 83 779 637 1 09 989 704 1 35 1207 765 1 66 1473 823 1 94 1718 3100 572 0 90 835 648 1 17 1056 715 1 43 1275 775 1 74 1543 832 2 05 1814 3200 58...

Page 29: ...100 636 1 11 1006 704 1 39 1241 764 1 69 1499 818 1 97 1744 870 2 29 2023 3200 652 1 21 1089 718 1 49 1327 778 1 90 1595 831 2 09 1849 882 2 40 2119 3300 668 1 31 1173 732 1 59 1413 793 1 92 1700 844...

Page 30: ...1 03 940 671 1 32 1182 739 1 62 1439 795 1 91 1691 851 2 26 1997 3400 610 1 10 998 682 1 41 1258 750 1 72 1526 806 2 01 1779 860 2 36 2084 3500 623 1 17 1056 694 1 50 1335 761 1 82 1613 817 2 11 1866...

Page 31: ...2343 3500 701 1 53 1361 762 1 82 1613 821 2 16 1910 871 2 48 2188 919 2 80 2462 3600 717 1 65 1465 777 1 94 1718 835 2 29 2023 885 2 63 2317 932 2 95 2587 3700 733 1 77 1569 792 2 07 1831 849 2 42 21...

Page 32: ...3 789 1 95 1726 841 2 18 1927 4300 628 1 56 1387 690 1 63 1447 747 1 83 1621 798 2 05 1814 849 2 30 2032 4400 639 1 67 1482 701 1 73 1534 757 1 92 1700 807 2 16 1910 858 2 41 2177 4500 651 1 78 1578 7...

Page 33: ...09 3 09 2755 955 3 42 3056 998 3 69 3304 5400 869 2 92 2602 882 3 01 2683 920 3 24 2891 967 3 57 3193 1009 3 86 3461 5500 885 3 09 2755 897 3 17 2828 932 3 38 3019 978 3 72 3331 1029 4 03 3618 5600 90...

Page 34: ...ter is Installed To start unit turn on main power supply Set thermostat at HEAT position and a setting above room temperature and set fan at AUTO position First stage of thermostat energizes the first...

Page 35: ...1 the OFM and IFM are deenergized and the EconoMi er modulates closed When the OAT is below the MECH CLG LOCKOUT set point the compressors remain off HEATING UNITS WITH DURABLADE ECONOMIZER OR ECONOMI...

Page 36: ...AND ADJUSTING REFRIGERANT CHARGE The refrigerant system is fully charged with R 22 refrigerant tested and factory sealed Unit must operate in Cooling mode a minimum of 10 minutes before checking charg...

Page 37: ...ssure gage Refer to ap propriate chart to determine what suction temperature should be If suction temperature is high add refrigerant If suction temperature is low carefully recover some of the charge...

Page 38: ...38 CIRCUIT NO 2 CIRCUIT NO 1 Fig 52 Cooling Charging Chart 50TFF012 Fig 53 Cooling Charging Chart 50TFF014...

Page 39: ...ontinuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge...

Page 40: ...OAT and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired...

Page 41: ...ical panel The fault condition is caused by Y2 being energized before Y1 Actuator fault Check the wiring between the EconoMi er controller and the actuator Hold CONFIG button between three and ten sec...

Page 42: ...tinue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00010 Printed in U S A Form 50TFF 2SI Pg 42 8 00 Replaces New Book 1 4 Tab...

Page 43: ......

Page 44: ...AS SHOWN IN THE INSTALLATION INSTRUCTIONS CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK THAT INDOOR AIR FILTERS ARE CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL WITH...

Reviews: