background image

Table 5—Wet Coil Air Delivery (Deduct 10 percent for 208v)*

Horizontal and Downflow Discharge

Unit 50SD024-060

230 VOLT

Unit

Motor

Speed

External Static Pressure (in. wg)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

Low

Watts

311

309

304

301

286

Cfm

935

885

820

757

686

Med

Watts

379

357

357

345

327

Cfm

957

868

769

647

365

High

Watts

447

435

421

Cfm

970

853

712

030

Low

Watts

311

309

304

301

Cfm

935

885

820

757

Med

Watts

411

405

398

390

379

357

357

Cfm

1195

1155

1100

1028

957

868

769

High

Watts

477

467

447

435

Cfm

1185

1088

970

853

036

Low

Watts

437

433

424

417

403

391

379

362

Cfm

1353

1318

1283

1235

1187

1123

1059

975

Med

Watts

531

516

496

478

459

435

Cfm

1489

1437

1362

1289

1208

1099

High

Watts

629

602

Cfm

1470

1357

042

Low

Watts

625

606

586

571

550

534

509

483

457

Cfm

1539

1496

1466

1437

1387

1330

1264

1183

1093

Med

Watts

741

715

694

669

645

610

573

544

Cfm

1738

1698

1653

1604

1538

1457

1362

1271

High

Watts

798

772

738

700

Cfm

1720

1648

1540

1414

048

Low

Watts

627

617

607

584

567

548

528

503

Cfm

1550

1530

1493

1461

1414

1361

1320

1250

Med

Watts

771

755

734

711

690

665

639

607

572

Cfm

1798

1771

1734

1687

1645

1595

1530

1449

1355

High

Watts

908

887

858

827

804

767

748

Cfm

2000

1994

1876

1811

1735

1647

1555

060

Low

Watts

786

769

754

736

722

705

684

658

Cfm

2027

1960

1901

1821

1759

1693

1616

1513

Med

Watts

873

849

833

815

798

782

763

748

Cfm

2095

2026

1962

1887

1817

1748

1679

1583

High

Watts

1012

993

981

963

948

927

904

886

Cfm

2184

2109

2036

1963

1886

1812

1729

1647

* Air delivery values are based on operating voltage of 230v wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static
pressure available for ducting.

NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below

this point.

2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.

16

Summary of Contents for 50SD

Page 1: ...RING 16 REFRIGERANT CIRCUIT 16 EVAPORATOR AIRFLOW 17 METERING DEVICE ACCURATER 17 TROUBLESHOOTING 17 START UP CHECKLIST 17 NOTE TO INSTALLER Before the installation READ THESE INSTRUCTIONS CAREFULLY A...

Page 2: ...esult in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 5A This is necessary for unit drain to function properly Refer to accessory roof curb installation instructio...

Page 3: ...TS UNIT TOP 48 00 1219 2 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 304 8 12 00 FROM WALL SYSTEM THEN SYSTEM PERFORMANCE MAYBE COMPROMISE REQU...

Page 4: ...230 1 60 460 209 46 98 1193 21 0 533 20 5 520 17 1 434 50SD048 208 230 1 60 480 218 46 98 1193 21 0 533 20 0 508 17 4 442 50SD060 208 230 1 60 492 223 46 98 1193 21 0 533 20 0 508 17 6 447 A05126 REQ...

Page 5: ...6 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 CPRFCURB009A00 14 356 16 3 16 411 17 3 8 441 40 5 16 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 NOTES 1 Dimensions in are in millimeters 2 Roof curb is...

Page 6: ...See Fig 7 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in tra...

Page 7: ...mmer Push louver down to break rear and left side tabs Fig 8 9 4 If unit ductwork is to be attached to vertical opening flanges on the unit composite base jackstand applications only do so at this tim...

Page 8: ...Contractors National Association SMACNA and Air Conditioning Contractors of America ACCA minimum installation standards for heating and air conditioning systems Secure all ducts to building structure...

Page 9: ...correction of improper voltage HIGH VOLTAGE CONNECTIONS The unit must have a separate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Re...

Page 10: ...0 28 5 28 5 28 5 31 2 50 3 57 2 72 8 83 3 95 4 109 3 37 6 42 6 35 35 35 35 60 60 40 45 80 90 100 110 060 208 230 1 60 187 253 25 0 148 0 1 5 6 2 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 5 4 7 2 18 1 20 8...

Page 11: ...ake the following inspections a Inspect for shipping and handling damages such as broken lines loose parts disconnected wires etc b Inspect for oil at all refrigerant tubing connections and on unit ba...

Page 12: ...Fig 12 Wiring Diagram 208 230 60 1 A05112 12...

Page 13: ...rvice fitting c Suction low side pressure psig 5 Using Cooling Charging Charts compare outdoor air tem perature F db with the suction line pressure psig to determine desired system operating suction l...

Page 14: ...son To troubleshoot heating or cooling of units refer to tables at the back of the book NOTE TO EQUIPMENT OWNER Consult your local dealer about the availability of a maintenance contract FIRE EXPLOSIO...

Page 15: ...crews that secure motor mount brackets to hous ing and slide motor and motor mount out of housing 2 Remove and clean blower wheel as follows a Ensure proper reassembly by marking wheel orientation b L...

Page 16: ...8 1457 1362 1271 High Watts 798 772 738 700 Cfm 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 Cfm 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 639 607...

Page 17: ...s publication as an aid in determining proper control operation REFRIGERANT CIRCUIT Inspect all refrigerant tubing connections and the unit base for oil accumulations annually Detecting oil generally...

Page 18: ...tion in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set to...

Page 19: ...lation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 C S __________ Compressor Amps L1 C __________ Indoor Evaporator Fan Amp...

Page 20: ...ianapolis IN 46231 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 6 Tab 6 8 PC 101 Printed in U...

Reviews: