background image

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
Errors made when reconnecting wires may cause improper
and dangerous operation. Label all wires prior to disconnec-
tion when servicing.

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, drain pan, and condensate drain at least

each cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness and check

lubrication each heating and cooling season. Clean when
necessary.

4. Check electrical connections for tightness and controls for

proper operation each heating and cooling season. Service
when necessary.

5. Ensure electric wires are not in contact with refrigerant tubing

or sharp metal edges.

AIR FILTER

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in unit component
damage.
Never operate the unit without a suitable air filter in the
return-air duct system. Always replace the filter with the same
dimensional size and type as originally installed. See Tables
1 and 2 for recommended filter sizes.

Inspect air filter(s) at least once each month and replace
(throwaway-type) or clean (cleanable-type) at least twice during
each heating and cooling season or whenever the filter(s) becomes
clogged with dust and lint.

EVAPORATOR BLOWER AND MOTOR

NOTE:

All motors are prelubricated. Do not attempt to lubricate

these motors.

For longer life, operating economy, and continuing efficiency,
clean accumulated dirt and grease from the blower wheel and
motor annually.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Disconnect and tag electrical power to the unit before
cleaning the blower motor and wheel.

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows:

a. Remove unit access panel.

b. Disconnect motor lead from time delay relay (TDR).

Disconnect yellow lead from terminal L2 of the contactor.

c. On all units remove blower assembly from unit. Remove

screws securing blower to blower partition and slide
assembly out. Be careful not to tear insulation in blower
compartment.

d. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft,

remove screws that secure motor mount brackets to hous-
ing, and slide motor and motor mount out of housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights (clips)
on blower wheel vanes.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush attach-
ment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are

tightened on motor shaft flats and not on round part of
shaft.

f. Reinstall unit access panel.

3. Restore electrical power to unit. Start unit and check for

proper blower rotation and motor speeds during heating and
cooling cycles.

CONDENSER COIL, EVAPORATOR COIL, AND CONDEN-
SATE DRAIN PAN

Inspect the condenser coil, evaporator coil, and condensate drain
pan at least once each year.

The coils are easily cleaned when dry; therefore, inspect and clean
the coils either before or after each cooling season. Remove all
obstructions, including weeds and shrubs, that interfere with the
airflow through the condenser coil.

Straighten bent fins with a fin comb. If coated with dirt or lint,
clean the coils with a vacuum cleaner, using the soft brush
attachment. Be careful not to bend the fins. If coated with oil or
grease, clean the coils with a mild detergent-and-water solution.
Rinse coils with clear water, using a garden hose. Be careful not to
splash water on motors, insulation, wiring, or air filter(s). For best
results, spray condenser coil fins from inside to outside the unit.
On units with an outer and inner condenser coil, be sure to clean
between the coils. Be sure to flush all dirt and debris from the unit
base.

Inspect the drain pan and condensate drain line when inspecting
the coils. Clean the drain pan and condensate drain by removing all
foreign matter from the pan. Flush the pan and drain tube with
clear water. Do not splash water on the insulation, motor, wiring,
or air filter(s). If the drain tube is restricted, clear it with a
“plumbers snake” or similar probe device. Ensure that the auxiliary
drain port above the drain tube is also clear

CONDENSER FAN

UNIT OPERATIONAL HAZARD
Failure to follow this caution may result in damage to unit
components.
Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the
unit.

1. Remove 6 screws holding condenser grille and motor to top

cover.

15

Summary of Contents for 50SD

Page 1: ...RING 16 REFRIGERANT CIRCUIT 16 EVAPORATOR AIRFLOW 17 METERING DEVICE ACCURATER 17 TROUBLESHOOTING 17 START UP CHECKLIST 17 NOTE TO INSTALLER Before the installation READ THESE INSTRUCTIONS CAREFULLY A...

Page 2: ...esult in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 5A This is necessary for unit drain to function properly Refer to accessory roof curb installation instructio...

Page 3: ...TS UNIT TOP 48 00 1219 2 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 304 8 12 00 FROM WALL SYSTEM THEN SYSTEM PERFORMANCE MAYBE COMPROMISE REQU...

Page 4: ...230 1 60 460 209 46 98 1193 21 0 533 20 5 520 17 1 434 50SD048 208 230 1 60 480 218 46 98 1193 21 0 533 20 0 508 17 4 442 50SD060 208 230 1 60 492 223 46 98 1193 21 0 533 20 0 508 17 6 447 A05126 REQ...

Page 5: ...6 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 CPRFCURB009A00 14 356 16 3 16 411 17 3 8 441 40 5 16 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 NOTES 1 Dimensions in are in millimeters 2 Roof curb is...

Page 6: ...See Fig 7 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in tra...

Page 7: ...mmer Push louver down to break rear and left side tabs Fig 8 9 4 If unit ductwork is to be attached to vertical opening flanges on the unit composite base jackstand applications only do so at this tim...

Page 8: ...Contractors National Association SMACNA and Air Conditioning Contractors of America ACCA minimum installation standards for heating and air conditioning systems Secure all ducts to building structure...

Page 9: ...correction of improper voltage HIGH VOLTAGE CONNECTIONS The unit must have a separate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Re...

Page 10: ...0 28 5 28 5 28 5 31 2 50 3 57 2 72 8 83 3 95 4 109 3 37 6 42 6 35 35 35 35 60 60 40 45 80 90 100 110 060 208 230 1 60 187 253 25 0 148 0 1 5 6 2 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 5 4 7 2 18 1 20 8...

Page 11: ...ake the following inspections a Inspect for shipping and handling damages such as broken lines loose parts disconnected wires etc b Inspect for oil at all refrigerant tubing connections and on unit ba...

Page 12: ...Fig 12 Wiring Diagram 208 230 60 1 A05112 12...

Page 13: ...rvice fitting c Suction low side pressure psig 5 Using Cooling Charging Charts compare outdoor air tem perature F db with the suction line pressure psig to determine desired system operating suction l...

Page 14: ...son To troubleshoot heating or cooling of units refer to tables at the back of the book NOTE TO EQUIPMENT OWNER Consult your local dealer about the availability of a maintenance contract FIRE EXPLOSIO...

Page 15: ...crews that secure motor mount brackets to hous ing and slide motor and motor mount out of housing 2 Remove and clean blower wheel as follows a Ensure proper reassembly by marking wheel orientation b L...

Page 16: ...8 1457 1362 1271 High Watts 798 772 738 700 Cfm 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 Cfm 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 639 607...

Page 17: ...s publication as an aid in determining proper control operation REFRIGERANT CIRCUIT Inspect all refrigerant tubing connections and the unit base for oil accumulations annually Detecting oil generally...

Page 18: ...tion in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set to...

Page 19: ...lation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 C S __________ Compressor Amps L1 C __________ Indoor Evaporator Fan Amp...

Page 20: ...ianapolis IN 46231 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 6 Tab 6 8 PC 101 Printed in U...

Reviews: