background image

50SD

Single Packaged Electric Cooling Units

Installation, Start-Up, and Operating Instructions

Sizes 024-060

NOTE:

Read the entire instruction manual before starting the

installation.

This symbol

indicates a change since the last issue.

TABLE OF CONTENTS

SAFETY CONSIDERATIONS .....................................................1

RULES FOR SAFE INSTALLATION AND OPERATION .......2

INTRODUCTION ..........................................................................2

RECEIVING AND INSTALLATION ..........................................2

Check Equipment......................................................................2

IDENTIFY UNIT ................................................................2
INSPECT SHIPMENT ........................................................2

Provide Unit Support ................................................................2

ROOF CURB.......................................................................2
SLAB MOUNT ...................................................................2
GROUND MOUNT ............................................................2

Provide Clearances....................................................................2
Field Fabricate Ductwork .........................................................2
Rig and Place Unit....................................................................2

INSPECTION ......................................................................4
INSTALLATION ................................................................4

Connect Condensate Drain .......................................................7
Install Duct Connections ..........................................................7

CONFIGURING UNITS FOR DOWNFLOW (VERTI-
CAL) DISCHARGE ............................................................7

Install Electrical Connection ....................................................9

HIGH-VOLTAGE CONNECTIONS..................................9
SPECIAL PROCEDURES FOR 208-V OPERATION .....9
CONTROL VOLTAGE CONNECTIONS.........................9
STANDARD CONNECTION ..........................................10
TRANSFORMER PROTECTION....................................12

PRE-START-UP ..........................................................................12

START-UP ...................................................................................12

CHECK FOR REFRIGERANT LEAKS..........................12
START UP COOLING SECTION AND MAKE ADJUST-
MENTS ..............................................................................12
CHECKING COOLING CONTROL OPERATION .......12
CHECKING

AND

ADJUSTING

REFRIGERANT

CHARGE ...........................................................................12
INDOOR

AIRFLOW

AND

AIRFLOW

ADJUST-

MENTS ..............................................................................14
For 208/230V.....................................................................14
COOLING SEQUENCE OF OPERATION.....................14

MAINTENANCE.........................................................................14

AIR FILTER......................................................................15
EVAPORATOR BLOWER AND MOTOR.....................15
CONDENSER COIL, EVAPORATOR COIL, AND CON-
DENSATE DRAIN PAN ..................................................16
CONDENSER FAN ..........................................................16
ELECTRICAL CONTROLS AND WIRING ..................16
REFRIGERANT CIRCUIT...............................................16
EVAPORATOR AIRFLOW .............................................17
METERING DEVICE — ACCURATER ........................17

TROUBLESHOOTING ...............................................................17

START-UP CHECKLIST............................................................17

NOTE TO INSTALLER — Before the installation, READ THESE
INSTRUCTIONS CAREFULLY AND COMPLETELY. Also,
make sure the User’s Manual and Replacement Guide are left with
the unit after installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified personnel should install, repair, or service
air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of
cleaning coils and filters. All other operations should be performed
by trained service personnel. When working on air-conditioning
equipment, observe precautions in the literature, tags, and labels
attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguisher
available for all brazing operations. Consult a qualified installer or
service agency for information or assistance. The qualified in-
staller or agency must use only factory-authorized kits or acces-
sories when modifying this product.

Fig. 1—Model 50SD

C99001

Visit www.carrier.com

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

6

Tab

6 8

PC 101

Printed in U.S.A.

Catalog No. 50SD-1SI

Pg 1

8-05

Replaces: New

Summary of Contents for 50SD

Page 1: ...RING 16 REFRIGERANT CIRCUIT 16 EVAPORATOR AIRFLOW 17 METERING DEVICE ACCURATER 17 TROUBLESHOOTING 17 START UP CHECKLIST 17 NOTE TO INSTALLER Before the installation READ THESE INSTRUCTIONS CAREFULLY A...

Page 2: ...esult in air leaks and poor unit performance Curb should be level to within 1 4 in See Fig 5A This is necessary for unit drain to function properly Refer to accessory roof curb installation instructio...

Page 3: ...TS UNIT TOP 48 00 1219 2 SIDE OPPOSITE DUCTS 36 00 914 0 DUCT PANEL 12 00 304 8 MINIMUM DISTANCES IF UNIT IS PLACED LESS THAN 304 8 12 00 FROM WALL SYSTEM THEN SYSTEM PERFORMANCE MAYBE COMPROMISE REQU...

Page 4: ...230 1 60 460 209 46 98 1193 21 0 533 20 5 520 17 1 434 50SD048 208 230 1 60 480 218 46 98 1193 21 0 533 20 0 508 17 4 442 50SD060 208 230 1 60 492 223 46 98 1193 21 0 533 20 0 508 17 6 447 A05126 REQ...

Page 5: ...6 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 CPRFCURB009A00 14 356 16 3 16 411 17 3 8 441 40 5 16 1022 41 15 16 1065 44 7 16 1129 46 1 16 1169 NOTES 1 Dimensions in are in millimeters 2 Roof curb is...

Page 6: ...See Fig 7 When using a gravel apron make sure it slopes away from the unit Connect a drain tube using a minimum of 3 4 in PVC or 3 4 in copper pipe all field supplied at the outlet end of the 2 in tra...

Page 7: ...mmer Push louver down to break rear and left side tabs Fig 8 9 4 If unit ductwork is to be attached to vertical opening flanges on the unit composite base jackstand applications only do so at this tim...

Page 8: ...Contractors National Association SMACNA and Air Conditioning Contractors of America ACCA minimum installation standards for heating and air conditioning systems Secure all ducts to building structure...

Page 9: ...correction of improper voltage HIGH VOLTAGE CONNECTIONS The unit must have a separate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Re...

Page 10: ...0 28 5 28 5 28 5 31 2 50 3 57 2 72 8 83 3 95 4 109 3 37 6 42 6 35 35 35 35 60 60 40 45 80 90 100 110 060 208 230 1 60 187 253 25 0 148 0 1 5 6 2 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 5 4 7 2 18 1 20 8...

Page 11: ...ake the following inspections a Inspect for shipping and handling damages such as broken lines loose parts disconnected wires etc b Inspect for oil at all refrigerant tubing connections and on unit ba...

Page 12: ...Fig 12 Wiring Diagram 208 230 60 1 A05112 12...

Page 13: ...rvice fitting c Suction low side pressure psig 5 Using Cooling Charging Charts compare outdoor air tem perature F db with the suction line pressure psig to determine desired system operating suction l...

Page 14: ...son To troubleshoot heating or cooling of units refer to tables at the back of the book NOTE TO EQUIPMENT OWNER Consult your local dealer about the availability of a maintenance contract FIRE EXPLOSIO...

Page 15: ...crews that secure motor mount brackets to hous ing and slide motor and motor mount out of housing 2 Remove and clean blower wheel as follows a Ensure proper reassembly by marking wheel orientation b L...

Page 16: ...8 1457 1362 1271 High Watts 798 772 738 700 Cfm 1720 1648 1540 1414 048 Low Watts 627 617 607 584 567 548 528 503 Cfm 1550 1530 1493 1461 1414 1361 1320 1250 Med Watts 771 755 734 711 690 665 639 607...

Page 17: ...s publication as an aid in determining proper control operation REFRIGERANT CIRCUIT Inspect all refrigerant tubing connections and the unit base for oil accumulations annually Detecting oil generally...

Page 18: ...tion in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set to...

Page 19: ...lation is level ____ Check fan wheel propeller for location in housing and setscrew tightness III START UP Supply Voltage L1 L2 C S __________ Compressor Amps L1 C __________ Indoor Evaporator Fan Amp...

Page 20: ...ianapolis IN 46231 Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 6 Tab 6 8 PC 101 Printed in U...

Reviews: