background image

9

Vertical package air conditionners

Check the connection air tightness.

A

Condensates pan 

in depression

A

Siphon drain

Slight slope

5/1000

To drainage

Siphon principle scheme

  Carry out the assembly of the same one following the attached 

principle scheme:

Pan in overpressure:

•  It is installed to avoid the access through the drain tubing of bad 

smells.

Pan in depression:

•  Besides the previous application, the water must be sucked from 

the pan.

•  For the correct design of the siphon, the dimension “A” should be 

at least, the double of the depression to which is the condensates 

pan.

•  The drain tubing must be slightly sloped to ease circulation towards 

the drain.

•  To control the drain it is recommended to insert a funnel in the 

pipelines toward the drainage.

Note: The original diameter of the tube must be respected. No 

reduction can be made.

9. S

AFETY

 

ELEMENTS

High pressure pressostat

Connected to the compressor discharge, it will 

stop its operation when the pressure at that point 

reaches the setpoint. It disconnects at 29 bar 

and it is automatically reactivated.

Caution: Threaded and without schrader valve.

Automatic switch in the control circuit

Magnetothermal switch that protects the operation circuit against 

continuous surges as well as against high currents of short duration 

(short circuits).

Fans and compressors protection

Both the fans and the compressor have a thermal protection for the 

motor. Its mission is to protect the motor against an excessive heating 

caused by a surge.

Main door switch

By using a mechanical device, it impedes access to the electric panel 

when the unit is with voltage. Available in all units.

Low pressure pressostat

When connected to the intake compressor, it 

will stop operating when the pressure at this 

point drops below the tare value (caused by 

obstructions in the circuit, excessive dirt in the 

fi lters, fan stop or ice formation in the evaporator). It disconnects at 

0.5 bar and resets automatically

Magnetothermals for line protection

They are located at the beginning of the power lines of the compressor 

and motorfans to protect them. 

Safeties at the compressor

The type compressor that these units as standard have the following 

safeties:

-  Non-return valve built into the compressor.

-  Temperature probe for the discharge from the compressor to protect 

the unit with discharge temperatures greater than 135ºC.

Clogged fi lter detector (optional)

Differential pressostat for indication of maintenance to fi lters. Automatic 

reactivation. 

Summary of Contents for 50NF

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS 50NZ NF Nominal cooling capacity 17 9 69 6 kW Nominal heating capacity 18 4 73 0 kW 50 Hz Vertical package air conditionners Original document...

Page 2: ...ns 8 Checks at fans 8 Condensate drain connection 8 9 Safety elements 9 High pressure pressostat 9 Low pressure pressostat 9 Magnetothermals for line protection 9 Automatic switch in the control circu...

Page 3: ...e of its vertical construction 50NZ Series Air air packaged cooling units 50NF Series Air air packaged reversible heat pumps After their manufacture all units are charged with refrigerant and are test...

Page 4: ...14 7 13 14 Type Centrifugal Number 1 2 Motor output kW 1 1 1 5 2 2 3 0 1 5 2 2 3 0 Speed r p m 630 680 699 644 680 699 644 Indoor circuit fan Nominal air flow m3 h 4 000 4 600 6 000 7 000 9 200 12 00...

Page 5: ...location 5 TRANSPORT The unit must be lifted and fixed with care and without inclination maximum inclination 15 since it could harm its operation The unit can be handled with a forklift truck taking a...

Page 6: ...d and walls in order that the circuit makes the aspiration of the return air 7 LOCATION AND ASSEMBLING Anchorage for antivibrators A B Minimum free space for commissioning and maintenance operations E...

Page 7: ...th the control in the unit The electrical heaters requested for units already shipped will be sent in a kit and the installer will need to assemble the necessary elements for the operation of the unit...

Page 8: ...tection mesh in the discharge as per the current regulation Air ducts connections Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once ru...

Page 9: ...l circuit Magnetothermal switch that protects the operation circuit against continuous surges as well as against high currents of short duration short circuits Fans and compressors protection Both the...

Page 10: ...must be emptied Possible water freezing must be avoided glycolling water or by using anti frost thermostat that triggers the circulation pump In models 120 and 160 the hot water coil assembly is carr...

Page 11: ...e way to avoid breakdowns since the analysis of these data makes early detection of anomalies possible or the provision of the necessary means available to ensure that they do not take place Possible...

Page 12: ...l and taken from a can tightly closed until the moment of the charge Note Both the oil type as well as the volume needed for each model are stated in the Technical characteristic tables in chapter 3 R...

Page 13: ...charge fan of the internal circuit Access to the indoor of the frame through this lateral panel Condensates drain pans Access Firstly put the door switch in O position Later unscrew the screws that fi...

Page 14: ...element are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electr...

Page 15: ......

Page 16: ...Order No 10055 03 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: