Vertical package air conditionners

13. C

ONTROL

 

AND

 

ANALYSIS

 

OF

 

BREAKDOWNS

Symptom

Cause

Solution

Evaporation pressure very high in relation with 
the air inlet

a) Charge excess
b) High air temperature
c) Compressor suction not air tight
d) Cycle reversing valve in middle position

a) Collect refrigerant
b) Verify overheating
c) Verify compressor state and replace
d) Check that the valve is not clogged. Replace if 

necessary

Very low condensation pressure

a) Gas lack
b) Compressor suction not air tight
c) Cycle inversion valve in middle position

d) Liquid circuit plugging

a) Search for leaks, complete charge
b) Verify compressor state and replace
c) Check that the valve is not clogged. Replace if 

necessary

d) Verify the dehydrating fi lter and expansion valve

Condensation pressure very high in relation to 
the air outlet, high pressostat cutoff

a) Insuffi cient air fl ow
b) Air inlet temperature very high
c) Dirty condenser (does not exchange)
d) Much refrigerant load (fl ooded condenser)
e) The condenser fan is broken down
f)  Air in the cooling circuit

a) Verify the air circuits (fl ow, fi lter cleanliness...)
b) Verify the control thermostat readjustment
c) Clean it
d) Collect refrigerant
e) Repair
f)  Make vacuum and load

Evaporation pressure too low (low pressostat 
cut-off)

a) Low fl ow in evaporator. Air recirculation
b) Frozen evaporator
c) Liquid line as different temperatures at fi lter inlet 

and outlet

d) Gas lack
e) Very low condensation pressure

f)  Evaporator fan broken down

a) Verify the air circuits (fl ow, fi lter cleanliness...)
b) Verify defrost
c) Replace fi lter

d) Search for leaks, complete charge
e) Temperature of air or water in condenser very 

low (air or water fl ow very high), adjust fl ow

f) Repair

Compressor does not start, does not make 
noise (humming)

a) No power
b) The contacts of a control element are open
c) Timing of anti cycle short does not allow the 

starting

d) Open contact
e) Contactor coil burnt
f)  Indoor klixon open

a) Check differential, fuses
b) Verify the safety chain of the electronic control
c) Verify electronic control

d) Replace
e) Replace
f)  Wait for reactivation, verify current absorbed

Compressor does not start, motor sounds 
intermittently

a) Electrical power supply very low
b) Power cable disconnected

a) Control line voltage and locate voltage drop 
b) Verify connections

Repeated compressor starts and stops

a) Because of high pressure
b) Control differential too short (short cycle)
c) Insuffi cient gas, cut-off because of low pressure
d) Dirty or frosted evaporator
e) The evaporator fan does not work, cuts off the 

low pressostat

f)  Expansion valve damaged or clogged by 

impurities (cuts off low pressostat)

g) Dehydrating fi lter clogged (cuts off low safety)

a) Verify charge
b) Increase differential
c) Search for leak, reload unit
d) Clean, verify evaporator air circuit
e) Replace or repair

f)  Replace, as well as fi lter

g) Replace

The compressor makes a noise

a) Loose attachment
b) Oil lack
c) Compressor noise

a) Fix
b) Add oil to recommended level
c) Replace

Noisy operation

a) Unit installed without antivibration protection

a) Place base over shock absorbers

Cycle reversing is not carried out:
- No 

defrosting

-  Does not change winter - summer cycles

a) Electrical fault
b) Inversion valve coil defective
c) Defrost method not working
d) Cycle inversion valve in middle position

e) Control fault

a) Locate and repair
b) Replace
c) Verify parameters
d) Tap with running compressor. Replace if 

necessary

e) Locate and repair

Alarm or reading error in the humidity probe 
(with CARRIERrtc enthalpic electronic control)

a) Dirt in the humidity sensor

a) Disassembly the probe encapsule
b) Proceed to clean the sensor with some soft 

cotton element and non-abrasive fl uid, without 
pressing it 

c) Reassemble the casing, checking that the 

cable is in contact externally with the metallic 
mesh 

Summary of Contents for 50NF

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS 50NZ NF Nominal cooling capacity 17 9 69 6 kW Nominal heating capacity 18 4 73 0 kW 50 Hz Vertical package air conditionners Original document...

Page 2: ...ns 8 Checks at fans 8 Condensate drain connection 8 9 Safety elements 9 High pressure pressostat 9 Low pressure pressostat 9 Magnetothermals for line protection 9 Automatic switch in the control circu...

Page 3: ...e of its vertical construction 50NZ Series Air air packaged cooling units 50NF Series Air air packaged reversible heat pumps After their manufacture all units are charged with refrigerant and are test...

Page 4: ...14 7 13 14 Type Centrifugal Number 1 2 Motor output kW 1 1 1 5 2 2 3 0 1 5 2 2 3 0 Speed r p m 630 680 699 644 680 699 644 Indoor circuit fan Nominal air flow m3 h 4 000 4 600 6 000 7 000 9 200 12 00...

Page 5: ...location 5 TRANSPORT The unit must be lifted and fixed with care and without inclination maximum inclination 15 since it could harm its operation The unit can be handled with a forklift truck taking a...

Page 6: ...d and walls in order that the circuit makes the aspiration of the return air 7 LOCATION AND ASSEMBLING Anchorage for antivibrators A B Minimum free space for commissioning and maintenance operations E...

Page 7: ...th the control in the unit The electrical heaters requested for units already shipped will be sent in a kit and the installer will need to assemble the necessary elements for the operation of the unit...

Page 8: ...tection mesh in the discharge as per the current regulation Air ducts connections Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once ru...

Page 9: ...l circuit Magnetothermal switch that protects the operation circuit against continuous surges as well as against high currents of short duration short circuits Fans and compressors protection Both the...

Page 10: ...must be emptied Possible water freezing must be avoided glycolling water or by using anti frost thermostat that triggers the circulation pump In models 120 and 160 the hot water coil assembly is carr...

Page 11: ...e way to avoid breakdowns since the analysis of these data makes early detection of anomalies possible or the provision of the necessary means available to ensure that they do not take place Possible...

Page 12: ...l and taken from a can tightly closed until the moment of the charge Note Both the oil type as well as the volume needed for each model are stated in the Technical characteristic tables in chapter 3 R...

Page 13: ...charge fan of the internal circuit Access to the indoor of the frame through this lateral panel Condensates drain pans Access Firstly put the door switch in O position Later unscrew the screws that fi...

Page 14: ...element are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electr...

Page 15: ......

Page 16: ...Order No 10055 03 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: