background image

12

Vertical package air conditionners

12. M

AINTENANCE

Recommendations:

Next, some recommendations are stated to perform the cleaning of 

the unit’s components:

Air coil

-  Check that the coil is free from dust and grease. 

-  Cleaning the accumulated dust on the coil can be performed with 

a vacuum cleaner perpendicular to the fi ns or with a low-pressure 

water cleaner. Grease can be removed with water with degreaser. 

Do not put stress on the fi ns as they could deform.

Air fi lters

Maintenance:

-  Clean usually. Depending on the installation conditions, the fi lter 

aspect must be examined to defi ne the cleaning periodicity. 

- Gravimetric fi lters. Cleaning the fi ltering mesh can be done with a 

household vacuum cleaner, or else by submerging it in water.

- Creased 

opacimetric 

fi lters It is necessary to replace them. Foresee 

replacement.

Filters extraction: 

- In fi rst place, put the door switch in 0 position.

-  In these units, for maintenance operation the extraction of the fi lter 

is lateral. Simply, it is carried out the unblocking of the stop-pieces 

that fi t the fi lter and it is removed. 

Dehydrant fi lter

- The 

fi lter function is the preserve the cooling circuit clean and without 

humidity, neutralizing the acids that can be found in the cooling circuit. 

Verify dirt measuring the difference in temperature at the tubing level, 

at the inlet and at the outlet of the dehydrant. 

-  If necessary, replace.

Oil

-  Check the oil level and aspect. In case of a colour change, check 

the oil quality using a contamination test. 

-  In the case of the presence of acid, water or metallic particles, replace 

the affected circuit oil, as well as the dehydrant fi lter. 

-  In the event of an oil charge change, only new oil will be used, which 

will be identical to the original oil and taken from a can tightly closed 

until the moment of the charge.

Note:

 Both the oil type as well as the volume needed for each model are 

stated in the Technical characteristic tables in chapter 3.

Refrigerant

Qualifi ed personnel must perform a periodic control to air tightness 

depending on the refrigerant charge, in accordance with the regulation 

(EC) No. 842/2006.

It is important not to ever forget that the cooling systems contain liquids 

and vapours under pressure.

-  All necessary precautions must be taken during the partial opening 

of the cooling circuit. This opening entails the discharge of a certain 

amount of refrigerant to the atmosphere. It is essential to limit to its 

minimum this amount of lost refrigerant by pumping and isolating the 

charge in some other part of the circuit.

-  The liquid refrigerant at low temperature can cause infl ammatory 

injuries similar to burns when contacting the skin or eyes. Always 

use protection glasses, gloves, etc. when opening ducts that may 

contain liquids. 

-  The refrigerant in excess must be stored in appropriate containers 

and the amount of refrigerant stored at the technical rooms must be 

limited. 

-  Refrigerant barrels and deposits must be handled with precaution 

and visible warning signs must be placed to attract attention over 

the risks of intoxication, fi re and explosion linked to the refrigerant. 

-  At the end of its useful life, the refrigerant must be retrieved and 

recycled as per the current regulations.

If the return is not ducted, all the set can be removed from the unit 

unscrewing the two screws that fi x the panel to the unit and taking it out.

Unit access from all its gates.

V-220004

Caution: Before intervening in the unit, cut off main 

power.

The minimal maintenance operations and their periodicity will be made 

according to the national regulations. 

Any intervention on the electric cooling components must be made by 

a qualifi ed and authorized technician. 

Summary of Contents for 50NF

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS 50NZ NF Nominal cooling capacity 17 9 69 6 kW Nominal heating capacity 18 4 73 0 kW 50 Hz Vertical package air conditionners Original document...

Page 2: ...ns 8 Checks at fans 8 Condensate drain connection 8 9 Safety elements 9 High pressure pressostat 9 Low pressure pressostat 9 Magnetothermals for line protection 9 Automatic switch in the control circu...

Page 3: ...e of its vertical construction 50NZ Series Air air packaged cooling units 50NF Series Air air packaged reversible heat pumps After their manufacture all units are charged with refrigerant and are test...

Page 4: ...14 7 13 14 Type Centrifugal Number 1 2 Motor output kW 1 1 1 5 2 2 3 0 1 5 2 2 3 0 Speed r p m 630 680 699 644 680 699 644 Indoor circuit fan Nominal air flow m3 h 4 000 4 600 6 000 7 000 9 200 12 00...

Page 5: ...location 5 TRANSPORT The unit must be lifted and fixed with care and without inclination maximum inclination 15 since it could harm its operation The unit can be handled with a forklift truck taking a...

Page 6: ...d and walls in order that the circuit makes the aspiration of the return air 7 LOCATION AND ASSEMBLING Anchorage for antivibrators A B Minimum free space for commissioning and maintenance operations E...

Page 7: ...th the control in the unit The electrical heaters requested for units already shipped will be sent in a kit and the installer will need to assemble the necessary elements for the operation of the unit...

Page 8: ...tection mesh in the discharge as per the current regulation Air ducts connections Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once ru...

Page 9: ...l circuit Magnetothermal switch that protects the operation circuit against continuous surges as well as against high currents of short duration short circuits Fans and compressors protection Both the...

Page 10: ...must be emptied Possible water freezing must be avoided glycolling water or by using anti frost thermostat that triggers the circulation pump In models 120 and 160 the hot water coil assembly is carr...

Page 11: ...e way to avoid breakdowns since the analysis of these data makes early detection of anomalies possible or the provision of the necessary means available to ensure that they do not take place Possible...

Page 12: ...l and taken from a can tightly closed until the moment of the charge Note Both the oil type as well as the volume needed for each model are stated in the Technical characteristic tables in chapter 3 R...

Page 13: ...charge fan of the internal circuit Access to the indoor of the frame through this lateral panel Condensates drain pans Access Firstly put the door switch in O position Later unscrew the screws that fi...

Page 14: ...element are open c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check differential fuses b Verify the safety chain of the electr...

Page 15: ......

Page 16: ...Order No 10055 03 2015 Supersedes order No New Manufactured for CARRIER in Spain The manufacturer reserves the right to change the specification without prior notice Printed in the European Union...

Reviews: