Table 9 -- Menu Structure
a
(cont)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
CHECKOUT
DAMPER VMIN .HS
n/a
n/a
Positions OA damper to VMIN High Speed position
DAMPER VMAX .HS
n/a
n/a
Positions OA damper to VMAX High Speed position
DAMPER OPEN
n/a
n/a
Positions OA damper to the full open position.
DAMPER CLOSE
n/a
n/a
Positions damper to the fully closed position
CONNECT Y1---O
n/a
n/a
Closes the Y1---O relay (Y1---O)
CONNECT Y2---O
n/a
n/a
Closes the Y2---O relay (Y2---O)
CONNECT AUX1O
n/a
n/a
Energizes the AUX1O output. If Aux setting is:
S
NONE --- not action taken
S
ERV --- 24 Vac out. Turns on or signals an ERV that the
conditions are not good for economizing but are good for
ERV operation.
d
S
SYS --- 24 Vac out. Issues a system alarm
ALARMS(_)
Alarms display only when they are active. The menu title “ALARMS(_)”
includes the number of active alarms in parenthesis ( ).
MA T SENS ERR
n/a
n/a
SUPPLY AIR TEMPERATURE SENSOR ERROR
CO2 SENS ERR
n/a
n/a
CO2 SENSOR ERROR
OA T SENS ERR
n/a
n/a
OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected at input terminals OAT
OA SYLK SENS ERR
n/a
n/a
OUTSIDE AIR TEMPERATURE SENSOR ERROR
OAT sensor connected on S--- bus
DA T SENS ERR
n/a
n/a
DISCHARGE AIR TEMPERATURE SENSOR ERROR
SYS ALARM
n/a
n/a
When AUX is set to SYS and there is any alarm (e.g., failed sensors,
etc.), the AUX terminal has 24 Vac out.
ACT UNDER V
n/a
n/a
ACTUATOR VOLTAGE LOW
Voltage received at actuator is below expected range
ACT OVER V
n/a
n/a
ACTUATOR VOLTAGE HIGH
Voltage received at actuator is above expected range
ACT STALLED
n/a
n/a
ACTUATOR STALLED
Actuator stopped before reaching commanded position
a
Table 9 illustrates the complete hierarchy. your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
2
) sensor, then none of the DCV parameters appear.
b
When values are displayed, pressing and holding the
Y
or
B
button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing --- the ERV terminal will be energized.
In the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
Menu Notes
1
STATUS ---> OCCUPIED –
The factory-standard Occupancy signal originates with a thermostat or other controller call for indoor fan operation at ISC termin-
al G. This signal passes through the Integrated Staging Control Board’s OCCUPIED jumper JMP1 to the ECONO connector and to the W7220’s OCC input
terminal. An external timeclock or relay is required to implement an Occupancy schedule on the economizer damper position.
2
STATUS -> MA TEMP, SETPOINTS -> MAT SET –
The W7220 menu parameters and labels include designations MA , MAT and Mixed Air for the econom-
izer cooling control sensor. On these rooftop units, the economizer control sensor is located downstream of the evaporator/indoor coil in the supply fan sec-
tion where this sensor is designated as Supply Air Temperature (SAT) sensor.
3
SETPOINTS -> DRYBLB SET –
This point is not displayed if a Return Air (differential) temperature sensor or an Outdoor Air enthalpy sensor is connected.
4
SYSTEM SETUP
parameters must be configured as noted for 2-Speed unit operation:
EQUIPMENT
= CONV
AUX2 I
= W
FAN TYPE
= 2SPEED
Summary of Contents for 50LC 07
Page 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Page 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Page 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Page 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Page 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Page 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Page 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Page 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Page 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Page 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Page 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Page 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...