41
Table 9 – Menu Structure
a1
Menu
Parameter
Parameter
Default
Value
Parameter
Range and Increment
b
EXPANDED PARAMETER NAME
Notes
STATUS
ECON AVAIL
NO
YES/NO
ECONOMIZING AVAIALBLE
YES = economizing available; the system can use outside air for free
cooling when required
ECONOMIZING
NO
YES/NO
ECONOMIZING ACTIVE
YES = Outside air being used for 1
st
stage cooling.
NO = Economizing not active
OCCUPIED
NO
YES/NO
OCCUPIED
YES = OCC signal received from space thermostat
or unitary controller.
YES = 24 Vac on terminal OCC.
NO = 0 Vac on terminal OCC.
HEAT PUMP
n/a
c
COOL
HEAT
HEAT PUMP MODE
(Not available on 2---Speed configuration)
COOL Y1---IN
OFF
ON/OFF
FIRST STAGE COOLING DEMAND (Y1---IN)
Y1---I signal from space thermostat or unitary controller for Cooling Stage 1.
ON = 24 Vac on terminal Y1---I
OFF = 0Vac on terminal Y1---I
COOL Y1---OUT
OFF
ON/OFF
FIRST STAGE COOLING RELAY OUTPUT
ON = 24 Vac on terminal Y1---O; Stage 1 mechanical cooling called on
OFF = 0 Vac on terminal Y1---O; no mechanical cooling
COOL Y2---IN
OFF
ON/OFF
SECOND STAVE COOLING DEMAND (Y2---IN)
Y2---I signal from space thermostat or unitary controller for Cooling Stage 2.
ON = 24 Vac on terminal Y2---I
OFF = 0 Vac on terminal Y2---I
COOL Y2---OUT
OFF
ON/OFF
SECOND STAGE COOLING RELAY OUTPUT
ON = 24 Vac on terminal Y2---O; Stage 2 mechanical cooling called on
OFF = 0 Vac on terminal Y2---O; no Stage 2 mechanical cooling
MA TEMP
nn
_
F (or
_
C) 0 to 140
_
F
(---18 to 60
_
C)
SUPPLY AIR TEMPERATRUE, Cooling Mode
Displays value of measured mixed/cooled air from SAT sensor in fan
section.
Displays --- ---.--- if not connected, short or out---of---range. See Menu Note 2
DA TEMP
nn
_
F (or
_
C) 0 to 140
_
F
(---18 to 60
_
C)
DISCHARGE AIR TEMPERATRUE, after Heating section
(Accessory sensor required)
Displays when Discharge Air sensor is connected and displays measured
discharge temperature.
Displays --- --- --- --- --- --- if sensor sends invalid value, if not connected, short
or out---of---range.
OA TEMP
nn
_
F (or
_
C)
---40 to 140
_
F
(---40 to 60
_
C)
OUTSIDE AIR TEMPERATRUE
Displays measured value of outdoor air temperature.
Displays --- --- --- --- --- --- if sensor sends invalid value, if not connected, short
or out---of---range.
OA HUM
nn%
0 to 100%
OUTSIDE AIR RELATIVE HUMIDITY
Displays measured value of outdoor humidity from OA enthalpy sensor.
RA TEMP
nn
_
F (or
_
C) 0 to 140
_
F
(---18 to 60
_
C)
RETURN AIR TEMPERATRUE
(Accessory sensor required)
Displays measured value of return air temperature from RAT sensor.
RA HUM
nn%
0 to 100%
RETURN AIR RELATIVE HUMIDITY
(Accessory enthalpy sensor required)
Displays measured value of return air humidity from RA sensor.
IN CO2
___ppm
0 to 2000 ppm
SPACE/RETURN AIR CO2
(CO
2
sensor required, accessory or factory option)
Displays value of measured CO
2
from CO
2
sensor.
Invalid if not connected, short or out---of---range
DCV STATUS
n/a
ON/OFF
DEMAND CONTROL VENTILATION STATUS
(CO
2
sensor required, accessory or factory option)
Displays ON if IN CO2 value above setpoint DCV SET and OFF if below
setpoint DCV SET.
DAMPER OUT
2.0V
2.0 to 10.0V
Displays voltage output to the damper actuator.
0% = OSA Damper fully closed
100% = OSA Damper full open
See Menu Note 3.
ACT POS
nn%
0 to 100%
Displays actual position of outdoor air damper actuator
2.0V = OSA Damper fully---closed
10.0V = OSA Damper full open
ACT COUNT
n/a
1 to 65535
Displays number of times actuator has cycled.
1 Cycle equals accrued 180
_
of actuator movement in any direction
ACTUATOR
n/a
OK/Alarm
(on Alarm menu)
Displays Error if voltage or torque is below actuator range
EXH1 OUT
OFF
ON/OFF
EXHAUST STAGE 1 RELAY OUTPUT
Output of EXH1 terminal:
ON = relay closed
OFF = relay open
Summary of Contents for 50LC 07
Page 9: ...9 COOLING CHARGING CHARTS C150169 Fig 9 Cooling Charging Charts 07 ...
Page 10: ...10 COOLING CHARGING CHARTS C150172 Fig 10 Cooling Charging Charts 08 ...
Page 11: ...11 COOLING CHARGING CHARTS C150170 Fig 11 Cooling Charging Charts 09 ...
Page 12: ...12 COOLING CHARGING CHARTS C150171 Fig 12 Cooling Charging Charts 12 ...
Page 27: ...27 C150181 Fig 34 50LC 07 Control Wiring Diagram ...
Page 28: ...28 C150225 Fig 35 50LC 07 RTU Open Control Wiring Diagram ...
Page 29: ...29 C14095 Fig 36 50LC 07 Power Wiring Diagram 208 230V 460V and 575V Units ...
Page 30: ...30 C14013 Fig 37 50LC 08 12 Control Wiring Diagram ...
Page 31: ...31 C14104 Fig 38 50LC 08 12 RTU Open Control Wiring Diagram ...
Page 32: ...32 C14105 Fig 39 50LC 08 12 Power Wiring Diagram 208 230V Units ...
Page 33: ...33 C150216 Fig 40 50LC 08 12 Power Wiring Diagram 460V 575V Units ...
Page 57: ...57 C13683 Fig 62 Typical EconoMi er X Wiring Diagram ...