background image

Compressor restart is accomplished by manual reset at the

thermostat by turning the selector switch to OFF position
and then ON position.

Heating —

To start unit, turn on main power supply.

Set thermostat at HEAT position and a setting above room

temperature, fan at AUTO position.

First stage of thermostat energizes the first-stage electric

heater elements; second stage energizes second-stage elec-
tric heater elements if installed. Check heating effects at air
supply grille(s).

If accessory electric heaters do not energize, reset limit

switch (located on evaporator-fan scroll) by depressing but-
ton located between terminals on the switch.

TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting heating selector lever below room tem-
perature temporarily shuts unit off until space temperature
falls below thermostat setting.

Safety Relief —

A soft solder joint in the suction line at

the loss-of-charge/low-pressure switch fitting provides
pressure relief under abnormal temperature and pressure
conditions.

Ventilation (Continuous Fan) —

Set fan and sys-

tem selector switches at ON and OFF positions, respec-
tively. Evaporator fan operates continuously to provide con-
stant air circulation.

Operating Sequence

COOLING, 50GJ006 UNITS WITHOUT ECONOMIZER
— When thermostat calls for cooling, terminals G and Y1
are energized. The indoor (evaporator) fan contactor (IFC),
compressor contactor (C), and outdoor (condenser) fan are
energized and the evaporator-fan motor, compressor, and con-
denser fan start. The condenser-fan motor runs continuously
while unit is cooling.

COOLING, 50GJ008,012 UNITS WITHOUT ECONO-
MIZER — When the thermostat calls for cooling, terminals
G and Y1 are energized. The indoor (evaporator) fan con-
tactor (IFC) and compressor contactor no. 1 (C1) are ener-
gized and the evaporator-fan motor, compressor no. 1, and
condenser fan start. The condenser-fan motor runs continu-
ously while unit is cooling. If the thermostat calls for a sec-
ond stage of cooling by energizing Y2, compressor contac-
tor no. 2 (C2) is energized and compressor no. 2 starts.

HEATING, 50GJ006 UNITS WITHOUT ECONOMIZER (If
Accessory Heater is Installed) — Upon a call for heating
through terminal W1, IFC and heater contactor no. 1 (HC1)
are energized. On units equipped for 2 stages of heat, when
additional heat is needed HC2 is energized through W2.

HEATING, 50GJ008,012 UNITS WITHOUT ECONO-
MIZER (If Accessory Heater is Installed) — Upon a call for
heating through terminal W1, IFC and heater contactor no.
1 (HC1) are energized. On units equipped for 2 stages of
heat, when additional heat is needed, HC2 is energized through
W2.

COOLING, 50GJ006 UNITS WITH VARISLIDE™ ECONO-
MIZER — When the outdoor-air temperature is above the
outdoor-air thermostat (OAT) setting and the room thermo-
stat calls for cooling, compressor contactor is energized to
start compressor and the outdoor (condenser) fan motor (OFM).
The indoor (evaporator) fan motor (IFM) is energized and
the economizer damper moves to the minimum position. Af-
ter the thermostat is satisfied, there is a 30-second delay be-
fore the evaporator fan turns off. The damper then moves to
the fully closed position. When using continuous fan, the
damper moves to the minimum position.

When the outdoor-air temperature is below the OAT set-

ting and the thermostat calls for cooling, the economizer damper
moves to the minimum position. If the supply-air tempera-
ture is above 57 F, the damper continues to open until it reaches
the fully open position or until the supply-air temperature
drops below 52 F.

When the supply-air temperature falls between 57 F and

52 F, the damper will remain at an intermediate open posi-
tion. If the supply-air temperature falls below 52 F, the damper
will modulate closed until it reaches the minimum position
or until the supply-air temperature is above 52 F. When the
thermostat is satisfied, the damper moves to the fully closed
position when using AUTO. fan or to the minimum position
when using continuous fan.

If the outdoor air alone cannot satisfy the cooling require-

ments of the conditioned space, economizer cooling is in-
tegrated with mechanical cooling, providing 2 stages of cooling.
Compressor and the condenser fan will be energized and the
position of the economizer damper will be determined by
the supply-air temperature. When the second stage of cool-
ing is satisfied, the compressor and OFM will be deener-
gized. The damper position will be determined by the supply-
air temperature. When the first stage of cooling is satisfied,
there is a 30-second delay before the evaporator fan shuts
off. The damper then moves to the fully closed position. When
using a continuous fan, the damper moves to the minimum
position.

COOLING, 50GJ008,012 UNITS WITH VARISLIDE
ECONOMIZER — When the outdoor-air temperature is above
the OAT setting and the room thermostat calls for cooling,
the compressor contactor no. 1 is energized to start com-
pressor no. 1 and outdoor (condenser) fan motor. The indoor
(evaporator) fan motor (IFM) is energized and the econo-
mizer damper moves to the minimum position. Upon a fur-
ther call for cooling, compressor contactor no. 2 will be en-
ergized, starting compressor no. 2. After the thermostat is
satisfied and the IFM is deenergized, the damper moves to
the fully closed position.

When the outdoor air temperature is below the OAT set-

ting and the thermostat calls for Y1 and G, the economizer
damper moves to the minimum position when the indoor
(evaporator) fan starts. The first stage of cooling is provided
by the economizer. If the supply-air temperature is above
57 F, a switch on the supply-air thermostat is closed between
the T2 terminal and the 24 vac terminal. This causes the damper
to continue to modulate open until the supply-air tempera-
ture falls below 55 F or the damper reaches the fully open
position.

When the supply-air temperature is between 55 F and

52 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals and between the T1 and 24 vac
terminals. This causes the economizer damper to remain in
an intermediate open position.

If the supply-air temperature falls below 52 F, a switch on

the supply-air thermostat is closed between the T1 terminal
and the 24 vac terminal. This causes the damper to modulate
closed until the supply-air temperature rises above 55 F or
the damper reaches the minimum position.

When the supply-air temperature is between 55 F and

57 F, the supply-air thermostat has open switches between
the T2 and 24 vac terminals. This causes the economizer damper
to remain in an intermediate open position.

If the outdoor air alone cannot satisfy the cooling require-

ments of the conditioned space, economizer cooling is in-
tegrated with mechanical cooling, providing second stage
cooling. Compressor no. 1 and outdoor (condenser) fan will
be energized, and the position of the economizer damper will
be determined by the supply-air temperature. Compressor no.
2 is locked out.

26

Summary of Contents for 50GJ006

Page 1: ...e air To minimize the possibility of moisture con tamination to the refrigerant system a special 100 molecu lar sieve filter drier is used Refrigerant R 407C must always be charged liquid Charg ing ga...

Page 2: ...E BOTTOM UNIT SIZE A ROOF CURB ACCESSORY 50GJ006 18 29 356 CRRFCURB001A00 28 09 610 CRRFCURB002A00 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimet...

Page 3: ...BOTTOM 11 49 NPT 1 29 NPT CRBTMPWR00A200 THRU THE BOTTOM UNIT SIZE A ROOF CURB ACCESSORY 50GJ008 012 18 29 356 CRRFCURB003A00 28 09 610 CRRFCURB004A00 NOTES 1 Roof curb accessory is shipped unassembl...

Page 4: ...external trap can be com pleted after the unit is in place All units must have an external trap for condensate drain age Install a trap at least 4 in deep and protect against freeze up See Fig 4 If d...

Page 5: ...n top skid when rigging to prevent rigging straps from damaging unit 3 Unit weights do not include economizer See Table 1 for econo mizer weights All panels must be in place when rigging 50GJ OPERATIN...

Page 6: ...pm 2100 2100 2100 Motor Pulley Pitch Diameter A B in 2 4 3 4 3 4 4 4 4 0 5 0 Nominal Motor Shaft Diameter in 7 8 7 8 7 8 Fan Pulley Pitch Diameter in 4 0 7 0 8 0 Belt Qty Type Length in 1 A 40 1 A 51...

Page 7: ...on horizontal discharge units with electric heat 1 in clearance to duct work for 1 ft b Condenser coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optio...

Page 8: ...iction may prevail a Bottom to combustible surfaces when not using curb 0 in on horizontal discharge units with electric heat 1 in clearance to ductwork for 1 ft b Condenser coil for proper airflow 36...

Page 9: ...8 230 3 60 50GJ008 012 460 3 60 LEGEND C Contactor COMP S Compressors IFC Indoor Evaporator Fan Contactor NEC National Electrical Code OFC Outdoor Condenser Fan Contactor Terminal Block Field Wiring F...

Page 10: ...ithin 10 Use the formula shown in Tables 2A and 2B Note 2 on page 11 to determine the percentage of voltage imbalance Operation on improper line voltage or excessive phase imbalance con stitutes abuse...

Page 11: ...4 8 16 5 27 8 33 0 41 7 50 0 19 8 33 4 39 7 50 2 60 1 31 4 33 6 50 5 58 4 71 4 68 9 35 35 60 60 80 90 33 33 46 54 66 77 172 575 3 60 518 632 7 9 50 0 0 7 4 8 17 0 34 0 51 0 17 1 34 1 51 2 24 9 28 9 50...

Page 12: ...Refer to Fig 6A and 6B for drilling holes in basepan HEAT ANTICIPATOR SETTINGS For 50GJ006 units set first stage heat anticipator setting at 0 8 and set second stage heat anticipator setting at 0 3 Fo...

Page 13: ...horizontal discharge block off plate over the opening on the access panel Block off plate MUST be installed before installing hood assembly See Fig 16 7 Insert economizer plug into economizer harness...

Page 14: ...LIEF DAMPER ECONOMIZER MOUNTING SCREWS ECONOMIZER MOTOR Fig 14 Varislide Economizer Installed in Unit ECONOMIZER MOTOR ECONOMIZER CONTROL BOARD WIRING HARNESS Fig 15 Horizontal Varislide Economizer In...

Page 15: ...ide Economizer Minimum Position Damper Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPE...

Page 16: ...ogic module T and T1 should be disconnected during adjustment b The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module Turn the lower potentiometer fully...

Page 17: ...d in Unit CONTROL CURVE CONTROL POINT APPROX DEG AT 50 RH A 73 23 B 70 21 C 67 19 D 63 17 Fig 23 Enthalpy Settings for PARABLADE Economizer Fig 24 Panels Reinstalled on Unit Fig 25 Outdoor Air Hood In...

Page 18: ...flange toward fixed flange to increase speed or away from fixed flange to decrease speed Increasing fan speed increases load on motor Do not exceed maxi mum speed specified in Table 1 5 Set movable fl...

Page 19: ...260 1 57 1330 1 78 2400 1107 1 24 1145 1 32 1222 1 52 1296 1 73 1365 1 94 2500 1150 1 39 1186 1 48 1262 1 68 1331 1 89 1400 2 12 2600 1193 1 56 1228 1 65 1301 1 86 1367 2 07 1435 2 31 2700 1237 1 74 1...

Page 20: ...VE MOTOR cont External Static Pressure in wg 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 884 1 97 937 2 33 947 2 66 1022 3 10 2300 885 2 00 939 2 36 979 2 69 1025 3 12 2400 892 2 08 944 2 40...

Page 21: ...988 1 91 995 1 95 3100 892 1 78 947 2 00 995 2 05 1008 2 07 3200 899 1 85 951 2 06 1000 2 17 1021 2 20 3300 907 1 93 959 2 10 1004 2 33 1036 2 36 3400 915 2 01 966 2 17 1009 2 46 1043 2 47 3500 924 2...

Page 22: ...1359 1 60 1800 1178 1 14 1249 1 32 1316 1 52 1382 1 72 1900 1201 1 23 1274 1 43 1338 1 62 1402 1 83 2000 1226 1 33 1297 1 53 1363 1 73 1424 1 94 2100 1252 1 45 1320 1 64 1388 1 85 1448 2 07 2200 1280...

Page 23: ...888 2 24 903 2 55 911 2 85 2400 824 1 72 872 2 01 909 2 32 931 2 64 935 2 96 2500 832 1 79 882 2 09 925 2 40 955 2 72 972 3 06 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11 2660 839 1 87 891 2 17...

Page 24: ...3400 853 1 71 899 1 93 951 2 17 995 2 17 1008 2 32 3500 862 1 78 907 2 01 959 2 24 1000 2 33 1021 2 47 3600 871 1 86 915 2 09 965 2 32 1005 2 46 1036 2 59 3700 879 1 95 927 2 17 973 2 38 1013 2 57 10...

Page 25: ...ed in accordance with these installation instructions and applicable codes Operating Parameters The maximum outdoor entering air temperature is 115 F The minimum entering outdoor air temperature is 45...

Page 26: ...y air tempera ture is above 57 F the damper continues to open until it reaches the fully open position or until the supply air temperature drops below 52 F When the supply air temperature falls betwee...

Page 27: ...HEATING 50GJ008 012 UNITS WITH ECONOMIZER If Accessory Heater is Installed When the room thermostat calls for heat through terminal W1 the evaporator fan con tactor and heater contactor no 1 are energ...

Page 28: ...er Coil 50GJ006 Fig 31 Cleaning Condenser Coil 50GJ008 012 Fig 32 Propping Up Top Panel 50GJ006 Fig 33 Propping Up Top Panel 50GJ008 012 Fig 34 Separating Coil Sections 50GJ006 Fig 35 Separating Coil...

Page 29: ...ns Accurate pressure gage and tem perature sens ing device are required Units charged with R 407C must use dedicated hoses and pressure gages Connect the pres sure gage to the service port on the suct...

Page 30: ...Fig 37 Cooling Charging Chart 50GJ006 Fig 38 Cooling Charging Charts 50GJ008 30...

Page 31: ...Fig 39 Cooling Charging Charts 50GJ012 31...

Page 32: ...ant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset ther...

Page 33: ...and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired pro...

Page 34: ...ot close No power to economizer 1 Disconnect power at TR and TR1 Disconnect jumper across P and P1 2 Connect jumper across TR and 1 3 Connect jumper across T1 and T 4 If connected remove enthalpy sens...

Page 35: ......

Page 36: ...TAGE L1 L2 L2 L3 L3 L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 INDOOR EVAPORATOR FAN AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB CO...

Reviews: