OPTIONAL VARISLIDE™ ECONOMIZER — The op-
tional economizer hood assembly is packaged and shipped
in the filter section. Damper blades and control boards are
installed at the factory and the economizer is shipped in the
vertical discharge position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical dis-
charge application, discard this plate.
Assembly

1. Determine if ventilation air is required in building. If

so, determine the minimum amount to be supplied by
each unit and record quantity of ventilation air needed
for use in Step 8.

2. Remove filter access panel by raising panel and swing-

ing panel outward. Panel is now disengaged from track
and can be removed. No tools are required to remove
filter access panel. Remove outdoor-air opening panel.
Save panels and screws. See Fig. 11. Remove optional
outdoor-air damper hood package from filter section.

3. Assemble outdoor-air hood top and side plates as shown

in Fig. 12. Install seal strips on hoop top and sides. Put
aside screen retainer and retainer screw for later assem-
bly. Do not attach hood to unit at this time.

4. On 012 unit, install vertical discharge block-off plate over

duct openings. See Fig. 13.

5. Slide economizer into unit and secure with screws. See

Fig. 14.

NOTE: Be sure to engage rear economizer flange under tabs
in vertical return-air opening.

6. To convert to horizontal discharge application:

a. Rotate the economizer 90 degrees until the econo-

mizer motor faces the condenser section (see Fig. 15).

b. Rotate the barometric relief damper cover 90 degrees.
c. Install horizontal discharge block-off plate over the

opening on the access panel. (Block-off plate MUST
be installed before installing hood assembly.) See
Fig. 16.

7. Insert economizer plug into economizer harness. Re-

move tape from barometric relief damper. See Fig. 14.

8. If ventilation air is not required, proceed to Step 9. If

ventilation air is required, determine the minimum po-
sition setting for required airflow. See Fig. 17A or 17B.
Adjust minimum position setting by adjusting the screws
on the position setting bracket. See Fig. 18. Slide bracket
until the top screw is in the position determined by
Fig. 17A or 17B. Tighten screws.

9. Remove tape from outdoor-air thermostat (OAT). Fas-

ten OAT to inside of hood using screws and speed clips
provided. See Fig. 19. Make sure OAT terminals are po-
sitioned up.

10. Replace outdoor-air opening panel using screws from

Step 2. Replace filter access panel. Ensure the filter ac-
cess panel slides along the tracks and is securely
engaged.

11. Fasten hood top and side plate assembly to outdoor-air

opening panel with screws provided.

12. Place knob supplied with economizer on OAT. See

Fig. 19. Set for 3° F below indoor room thermostat set-
ting. If accessory enthalpy control (EC) is used in place
of OAT, see instructions shipped with EC for installa-
tion and adjustment. See Fig. 19.

13. Connect OAT per Fig. 20.

14. Slide outdoor-air inlet screen(s) into screen track on hood

side plate. On size 008 and 012 units, use screen clasp
to hold screens together. While holding screen(s) in place,
fasten screen retainer to hood using screws provided.

NOTE: Refer to Fig. 21 for economizer barometric relief damper
characteristics.

CONTROL
WIRING

APOLLO
CONTROL

WIRING TO
THERMOSTAT

Fig. 10 — Apollo Control Factory-Installed

in Typical Unit (50GJ008 Shown)

Fig. 11 — Typical Panel Locations

13

Summary of Contents for 50GJ006

Page 1: ...e air To minimize the possibility of moisture con tamination to the refrigerant system a special 100 molecu lar sieve filter drier is used Refrigerant R 407C must always be charged liquid Charg ing ga...

Page 2: ...E BOTTOM UNIT SIZE A ROOF CURB ACCESSORY 50GJ006 18 29 356 CRRFCURB001A00 28 09 610 CRRFCURB002A00 NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are in millimet...

Page 3: ...BOTTOM 11 49 NPT 1 29 NPT CRBTMPWR00A200 THRU THE BOTTOM UNIT SIZE A ROOF CURB ACCESSORY 50GJ008 012 18 29 356 CRRFCURB003A00 28 09 610 CRRFCURB004A00 NOTES 1 Roof curb accessory is shipped unassembl...

Page 4: ...external trap can be com pleted after the unit is in place All units must have an external trap for condensate drain age Install a trap at least 4 in deep and protect against freeze up See Fig 4 If d...

Page 5: ...n top skid when rigging to prevent rigging straps from damaging unit 3 Unit weights do not include economizer See Table 1 for econo mizer weights All panels must be in place when rigging 50GJ OPERATIN...

Page 6: ...pm 2100 2100 2100 Motor Pulley Pitch Diameter A B in 2 4 3 4 3 4 4 4 4 0 5 0 Nominal Motor Shaft Diameter in 7 8 7 8 7 8 Fan Pulley Pitch Diameter in 4 0 7 0 8 0 Belt Qty Type Length in 1 A 40 1 A 51...

Page 7: ...on horizontal discharge units with electric heat 1 in clearance to duct work for 1 ft b Condenser coil for proper airflow 36 in one side 12 in the other The side getting the greater clearance is optio...

Page 8: ...iction may prevail a Bottom to combustible surfaces when not using curb 0 in on horizontal discharge units with electric heat 1 in clearance to ductwork for 1 ft b Condenser coil for proper airflow 36...

Page 9: ...8 230 3 60 50GJ008 012 460 3 60 LEGEND C Contactor COMP S Compressors IFC Indoor Evaporator Fan Contactor NEC National Electrical Code OFC Outdoor Condenser Fan Contactor Terminal Block Field Wiring F...

Page 10: ...ithin 10 Use the formula shown in Tables 2A and 2B Note 2 on page 11 to determine the percentage of voltage imbalance Operation on improper line voltage or excessive phase imbalance con stitutes abuse...

Page 11: ...4 8 16 5 27 8 33 0 41 7 50 0 19 8 33 4 39 7 50 2 60 1 31 4 33 6 50 5 58 4 71 4 68 9 35 35 60 60 80 90 33 33 46 54 66 77 172 575 3 60 518 632 7 9 50 0 0 7 4 8 17 0 34 0 51 0 17 1 34 1 51 2 24 9 28 9 50...

Page 12: ...Refer to Fig 6A and 6B for drilling holes in basepan HEAT ANTICIPATOR SETTINGS For 50GJ006 units set first stage heat anticipator setting at 0 8 and set second stage heat anticipator setting at 0 3 Fo...

Page 13: ...horizontal discharge block off plate over the opening on the access panel Block off plate MUST be installed before installing hood assembly See Fig 16 7 Insert economizer plug into economizer harness...

Page 14: ...LIEF DAMPER ECONOMIZER MOUNTING SCREWS ECONOMIZER MOTOR Fig 14 Varislide Economizer Installed in Unit ECONOMIZER MOTOR ECONOMIZER CONTROL BOARD WIRING HARNESS Fig 15 Horizontal Varislide Economizer In...

Page 15: ...ide Economizer Minimum Position Damper Setting MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPE...

Page 16: ...ogic module T and T1 should be disconnected during adjustment b The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module Turn the lower potentiometer fully...

Page 17: ...d in Unit CONTROL CURVE CONTROL POINT APPROX DEG AT 50 RH A 73 23 B 70 21 C 67 19 D 63 17 Fig 23 Enthalpy Settings for PARABLADE Economizer Fig 24 Panels Reinstalled on Unit Fig 25 Outdoor Air Hood In...

Page 18: ...flange toward fixed flange to increase speed or away from fixed flange to decrease speed Increasing fan speed increases load on motor Do not exceed maxi mum speed specified in Table 1 5 Set movable fl...

Page 19: ...260 1 57 1330 1 78 2400 1107 1 24 1145 1 32 1222 1 52 1296 1 73 1365 1 94 2500 1150 1 39 1186 1 48 1262 1 68 1331 1 89 1400 2 12 2600 1193 1 56 1228 1 65 1301 1 86 1367 2 07 1435 2 31 2700 1237 1 74 1...

Page 20: ...VE MOTOR cont External Static Pressure in wg 1 4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2250 884 1 97 937 2 33 947 2 66 1022 3 10 2300 885 2 00 939 2 36 979 2 69 1025 3 12 2400 892 2 08 944 2 40...

Page 21: ...988 1 91 995 1 95 3100 892 1 78 947 2 00 995 2 05 1008 2 07 3200 899 1 85 951 2 06 1000 2 17 1021 2 20 3300 907 1 93 959 2 10 1004 2 33 1036 2 36 3400 915 2 01 966 2 17 1009 2 46 1043 2 47 3500 924 2...

Page 22: ...1359 1 60 1800 1178 1 14 1249 1 32 1316 1 52 1382 1 72 1900 1201 1 23 1274 1 43 1338 1 62 1402 1 83 2000 1226 1 33 1297 1 53 1363 1 73 1424 1 94 2100 1252 1 45 1320 1 64 1388 1 85 1448 2 07 2200 1280...

Page 23: ...888 2 24 903 2 55 911 2 85 2400 824 1 72 872 2 01 909 2 32 931 2 64 935 2 96 2500 832 1 79 882 2 09 925 2 40 955 2 72 972 3 06 2550 836 1 83 887 2 13 931 2 45 964 2 77 986 3 11 2660 839 1 87 891 2 17...

Page 24: ...3400 853 1 71 899 1 93 951 2 17 995 2 17 1008 2 32 3500 862 1 78 907 2 01 959 2 24 1000 2 33 1021 2 47 3600 871 1 86 915 2 09 965 2 32 1005 2 46 1036 2 59 3700 879 1 95 927 2 17 973 2 38 1013 2 57 10...

Page 25: ...ed in accordance with these installation instructions and applicable codes Operating Parameters The maximum outdoor entering air temperature is 115 F The minimum entering outdoor air temperature is 45...

Page 26: ...y air tempera ture is above 57 F the damper continues to open until it reaches the fully open position or until the supply air temperature drops below 52 F When the supply air temperature falls betwee...

Page 27: ...HEATING 50GJ008 012 UNITS WITH ECONOMIZER If Accessory Heater is Installed When the room thermostat calls for heat through terminal W1 the evaporator fan con tactor and heater contactor no 1 are energ...

Page 28: ...er Coil 50GJ006 Fig 31 Cleaning Condenser Coil 50GJ008 012 Fig 32 Propping Up Top Panel 50GJ006 Fig 33 Propping Up Top Panel 50GJ008 012 Fig 34 Separating Coil Sections 50GJ006 Fig 35 Separating Coil...

Page 29: ...ns Accurate pressure gage and tem perature sens ing device are required Units charged with R 407C must use dedicated hoses and pressure gages Connect the pres sure gage to the service port on the suct...

Page 30: ...Fig 37 Cooling Charging Chart 50GJ006 Fig 38 Cooling Charging Charts 50GJ008 30...

Page 31: ...Fig 39 Cooling Charging Charts 50GJ012 31...

Page 32: ...ant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset ther...

Page 33: ...and EC settings and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired pro...

Page 34: ...ot close No power to economizer 1 Disconnect power at TR and TR1 Disconnect jumper across P and P1 2 Connect jumper across TR and 1 3 Connect jumper across T1 and T 4 If connected remove enthalpy sens...

Page 35: ......

Page 36: ...TAGE L1 L2 L2 L3 L3 L1 CIRCUIT 1 COMPRESSOR AMPS L1 L2 L3 CIRCUIT 2 COMPRESSOR AMPS L1 L2 L3 INDOOR EVAPORATOR FAN AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB CO...

Reviews: