Table 7 — Fan Performance, 50GJ008 − Vertical Discharge Units
AIRFLOW
(Cfm)
BELT DRIVE MOTOR
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.2
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
2250
511
0.52
592
0.74
659
0.95
722
1.19
778
1.43
829
1.68
2300
518
0.55
599
0.77
665
0.98
727
1.22
783
1.47
834
1.72
2400
534
0.61
613
0.84
677
1.06
738
1.30
794
1.55
844
1.81
2500
549
0.67
627
0.90
690
1.14
750
1.38
805
1.64
855
1.91
2550
557
0.71
633
0.94
697
1.18
756
1.42
811
1.69
861
1.96
2600
565
0.74
639
0.97
703
1.22
761
1.46
816
1.74
866
2.01
2700
581
0.81
652
1.04
717
1.31
773
1.55
827
1.83
878
2.12
2800
597
0.89
665
1.12
733
1.40
786
1.66
839
1.93
889
2.23
2900
613
0.97
679
1.20
745
1.50
799
1.76
850
2.04
900
2.34
3000
629
1.06
694
1.29
759
1.59
812
1.88
862
2.15
911
2.46
3100
646
1.15
709
1.39
772
1.70
825
1.99
875
2.28
923
2.58
3200
662
1.25
724
1.50
785
1.80
840
2.11
887
2.41
934
2.71
3300
679
1.35
740
1.61
798
1.91
854
2.24
900
2.54
946
2.85
3400
696
1.46
756
1.73
811
2.02
868
2.37
914
2.69
959
3.00
3500
712
1.57
771
1.85
824
2.14
881
2.50
928
2.84
971
3.16
3600
729
1.69
787
1.98
839
2.21
894
2.64
942
2.99
984
3.22
3700
746
1.85
803
2.12
854
2.42
907
2.78
956
3.15
997
3.49
3750
755
1.89
811
2.20
862
2.49
914
2.85
963
3.23
—
—
AIRFLOW
(Cfm)
BELT DRIVE MOTOR (cont)
External Static Pressure (in. wg)
1.4
1.6
1.8
2.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
2250
884
1.97
937
2.33
947
2.66
1022
3.10
2300
885
2.00
939
2.36
979
2.69
1025
3.12
2400
892
2.08
944
2.40
987
2.76
1039
3.20
2500
902
2.18
949
2.48
1002
2.84
1041
3.25
2550
908
2.24
953
2.53
1003
2.87
1045
3.28
2600
913
2.29
957
2.58
1004
2.91
1050
3.31
2700
924
2.40
967
2.70
1010
3.01
1056
3.37
2800
935
2.52
978
2.62
1019
3.13
1061
3.47
2900
946
2.65
989
2.96
1030
3.27
—
—
3000
957
2.78
1000
3.09
1040
3.41
—
—
3100
968
2.91
1011
3.24
—
—
—
—
3200
980
3.04
1022
3.38
—
—
—
—
3300
991
3.18
—
—
—
—
—
—
3400
1003
3.32
—
—
—
—
—
—
3500
1014
3.48
—
—
—
—
—
—
3600
—
—
—
—
—
—
—
—
3700
—
—
—
—
—
—
—
—
3750
—
—
—
—
—
—
—
—
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 6.)
2.
Indicates field-supplied motor and drive are required.
3. Maximum continuous bhp is 2.90. Extensive motor and electrical
testing on these units ensures that the full range of the motor can
be utilized with confidence. Using your fan motors up to the
ratings shown will not result in nuisance tripping or premature mo-
tor failure. Unit warranty will not be affected. For additional infor-
mation on motor performance, refer to Table 4 on page 19.
4. Values include losses for filters, unit casing, and wet coils.
5. Use of a field-supplied motor may affect wire sizing. Contact
Carrier representative to verify.
6. Standard motor drive range: 840 to 1085 rpm. All other rpms re-
quire field-supplied drive.
7. Interpolation is permissible. Do not extrapolate.
20