background image

30

14 - MAINTENANCE

● The refrigerant and lubricating oil, and the low-temperature 

liquid refrigerant in particular, may cause infl ammatory lesions 
similar to burns if they come into contact with the skin or eyes. 
Always wear protective eyewear, gloves and other protective 
equipment when opening pipes or tanks liable to have liquids 
in them. 

● Store  unused  refrigerant  in  the  appropriate  containers  and 

limit the amounts stored in mechanical rooms.

● Cylinders and tanks of refrigerant must be handled with care 

and  signs  warning  users  of  the  related  poisoning,  fi re  and 
explosion hazards must be clearly visible. 

Refrigerant that reaches the end of its life must be collected 
and recycled in accordance with applicable regulations.

14.3 access to the main components

Air coil

● Check that the coil is free from dust and grease. 

● Cleaning the accumulated dust on the coil can be performed 

using a soft-bristled brush or a vacuum cleaner perpendicular 
to the fi ns or with a low-pressure water cleaner. Grease can 
be removed with water with degreaser. Do not put stress on 
the fi ns as they could deform.

The  access  panels  to  fi lters,  supply  fans,  compressors  and 
electric panel are fi tted with  quarter-turn latches. These 
latches of stainless steel have triangular insert 8 mm. 

Quarter-turn latches

Condensate drainage pan

● Check that the condensate pan is suffi  ciently clean.

● Check that the drain is not clogged. 

● Cleaning of the pan can be done with water and non-abrasive 

detergent.

Outdoor coil protective grille (optional)

All the models can include a protection grille for this coil. This 
grille is fi xed by modules in the holes made for this goal in 
the unit’s support. 

Grille 

module

Holes

 Closing mode:

First rotate 90º (anti-clockwise): closing brings 
the  latch  to  the  locked  position.  The  door 
cannot be opened.

Use safety gloves for this task. Take care with the sharp 
parts of the coil. 

V-220005

Centrifugal fan (optional)

● Verify that the turbine and the motor remain clean.

● Foresee having a spare belt set for the fans.

● The  motors  and  the  fans  have  bearings  that  have  been 

lubricated and sealed and, thus, do not need further lubrication 
(except in the case of fans with a reinforced shaft).

14.2 Servicing

It’s  recommended  to  note  down  the  operating  readings  and 
perform the following checks at least twice a year and mandatory 
after each time a unit is started for seasonal use.

Weekly checks

With the unit running at full capacity, check the following values:

● LP  compressor  suction  pressure  and  HP  compressor 

discharge pressure.

● The oil level and its appearance. If the colour changes, check 

the quality.

● Also check whether the safety devices operate correctly.

● Check the entire system for traces of water or oil under or 

around the unit and for any unusual noises.

Monthly checks

● Check all the values listed in the table “Operating readings“ 

on chapter 13.

● Check for corrosion on all metal surfaces (chassis, casing, 

exchangers, electric panel, etc.).

● Make sure that the insulating foam is neither detached nor 

torn.

● Check  the  coolants  for  any  impurities  which  could  cause 

wearor corrosion in the exchanger.

● Check the circuits for leaks.

● Check whether the safety devices and the expansion valve(s)

operate correctly.

Annual checks

● Carry out the same inspections as during the monthly checks.

● Carry out an oil contamination test (every year or every 5000 

hours).  If  acid,  water  or  metal  particles  are  found,  replace 
the  oil  in  the  circuit  concerned  and  the  dryer.  Follow  the 
recommendations of paragraph 14.1.

● Check the electrical connections to ensure they are tight and 

in good condition.

● Check the condition of the contacts and the current at full load 

on all three phases.

● Check the electrical box for water seepage.

N.b.: The intervals for cleaning are given as a guide and should 
be adapted to each unit.

Summary of Contents for 50EH 1100

Page 1: ...E N A N C E I N S T R U C T I O N S Translation of the original document 80049 12 2018 Packaged rooftop units and separated gas module option 50EN EH 415 1200 Nominal cooling capacity 92 8 287 0 kW No...

Page 2: ...ntrifugal fans optional 17 9 4 Air ducts connections 18 10 CONDENSATE DRAIN 19 11 SAFETY ELEMENTS 20 12 FACTORY OPTIONS AND ACCESSORIES 22 12 1 Filters 22 12 2 Hot water coil 22 12 3 Electrical heater...

Page 3: ...serial Nbr A o An Year Producto Product Produit Ref Produit Item Nbr Max Intensidad Intensit Current Kit Elec Tension Voltage Refrig KG F brica Factory Usine Co2 Teq Refrigerant NoBo Peso Poids Weight...

Page 4: ...1 optional 2 optional Assembly Assemblies with mixing box and free cooling Standard assembly M0 assemblies Change of supply and or return air position in the indoor circuit ME assemblies Axial air ex...

Page 5: ...stics or in the regulatory documentation provided with the product The compressor and line surfaces can reach temperatures above 100 C causing burns to the body In the same fashion under certain condi...

Page 6: ...he weight and the gravity centre coordinates of each model stated in the following page The recommended length for the forks will be bigger than the unit width so that the entire weight bearing struct...

Page 7: ...lies MRC1 assembly Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm 415 1 566...

Page 8: ...85 385 385 385 475 475 Gas burner module PCH065 414 414 414 PCH080 440 440 440 440 440 440 440 440 PCH105 468 468 468 468 468 468 468 468 PCH130 504 504 504 504 504 504 504 504 520 520 PCH160 555 555...

Page 9: ...en installed These units can be installed on the oor or on a brick curb or steel pro le Based on the xing solution de ned in the installation project it will be necessary to plan the placement in the...

Page 10: ...9 314 412 648 273 960 423 598 254 364 539 195 411 627 275 402 619 267 466 711 326 425 671 286 466 711 326 425 671 286 50EN EH MC0 Assembly MRC0 Assembly MC1 MWC1 Assemblies MRC1 Assembly R1 R2 R3 R4 R...

Page 11: ...R8 1100 330 536 475 288 357 564 502 316 330 536 475 288 357 564 502 316 1200 349 567 481 292 375 592 507 318 349 567 481 292 375 592 507 318 50EN EH MC0 Assembly MRC0 Assembly R1 R2 R3 R4 R5 R6 R7 R8...

Page 12: ...nd 960 50EN EH 1100 and 1200 LEGEND Indoor air coil Outdoor air coil Air supply Air return Condensates outlet 2 2 1 2000m m 2500mm 1500mm 1500mm 3 4 5 3500mm 2 2 1 1500mm 1500mm 3000m m 3 4 5 7 POSITI...

Page 13: ...tures refer to the technical brochure and the name plate The distance between the unit and its power source The protection to be placed at the power source Neutral operating conditions The electrical...

Page 14: ...the indoor circuit are connected Electric power supply inputs Main panel Auxiliary panel Main panel Electric power supply inputs Optionally these units can change the electronic control to CARRIERrtc...

Page 15: ...the cover clockwise g 4 Reversing valve heat pump Outdoor fan Compressor Low pressure High pressure Outdoor temperature probe B2 B7 Press transducer in the outdoor coil cir 1 Discharge T klixon switch...

Page 16: ...f the control board connector J18 Recommended cable section 1 5 mm2 V GND RH T CO2 GND 1 2 3 4 5 6 22 21 23 B10 J18 S13 Electric panel V GND GND CO2 NC Tpassive Tpassive 1 2 3 4 5 6 7 22 21 23 B10 J18...

Page 17: ...eck the operation conditions pressures ows and consumptions The coupling of characteristic curves of the fan and the room is very important so that the ows and pressures provided to the duct network a...

Page 18: ...Belt tension After xing the pulleys on the same plane the belt tension is made by tightening the tensor screw Excessive tension on the belt can lead to premature wear on the assembly Insu cient belt t...

Page 19: ...te pan is placed The drain piping must be slightly sloped to ease circulation towards the drain The original diameter of the piping must be respected No reduction can be made CONNECT SIPHON METTRE SIP...

Page 20: ...th low outdoor temperatures condensation control or in heating mode with high outdoor temperatures evaporation control This aids the unit s operation in all the seasons In the case of EC electronic fa...

Page 21: ...ction of the mixing box dampers optional mandatory for an outdoor temperature lower than 12 C WB Activation temperature 12 C WB Hot water coil circuit optional with anti freeze technology based on the...

Page 22: ...unit Note Refer to the operation mode of the pump with the GREAT COLD option in the chapter Safety elements Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Page 23: ...the following table To attach these frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the 4 Allen M4 screws included in the kit The heigh...

Page 24: ...op The stop drop can be installed in the indoor air coil and on the fresh air intake Indoor air coil available for models 415 to 960 and included in models 1100 and 1200 recommended in cases where a h...

Page 25: ...rews supplied with the unit Profiles for the attachment of the module For the transport and lifting to the roof using a crane cloth slings with rings will be used with the appropriate resistance separ...

Page 26: ...ame plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary information about the installation commissioning and...

Page 27: ...nection of the sensors supplied with the unit consult the chapter on Electrical connection That they are no cables close to heat sources Once the above veri cations have been carried out the control c...

Page 28: ...s signi cant temperatures in the cooling circuit see attached table other aspects considered interesting such as alarms detected by the electronic control of the unit The recording of these parameters...

Page 29: ...inal oil which has been stored in a hermetically sealed container until its time of use The oil type recommended for these units is Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL...

Page 30: ...opened Use safety gloves for this task Take care with the sharp parts of the coil V 220005 Centrifugal fan optional Verify that the turbine and the motor remain clean Foresee having a spare belt set...

Page 31: ...lable tighten them until they are snug then tighten a further turn Solder the suction and discharge piping Connect the compressor in accordance with the wiring diagram Make vacuum and next reload the...

Page 32: ...the module incorporate stainless steel quarter turn latches with 8 mm triangular inserts The procedure for extraction and cleaning of lters is equal to that described in the previous section Tabs in d...

Page 33: ...c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check di erential fuses b Verify the safety chain of the electronic control c Ver...

Page 34: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Page 35: ......

Page 36: ...tured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for RT Check ongo...

Reviews: