9

7.1 Choice of location

When  choosing  the  location,  whatever  may  be  the  selected 
fashion,  the  following  precautions  have  to  be  taken  into 
consideration:

●  It is mandatory to comply with norm EN 378-3 on Safety and 

Environmental Requirements. Part 3: “In situ” installation and 
protection to people.

●  It is necessary to check that the structure supports the unit’s 

weigh  (please  consult  the  weight  in  paragraph  “  Weight 
overview”).

●  The  area  where  the  unit  will  be  located  must  be  perfectly 

accessible for cleaning and maintenance operations (please 
consult  the  “Recommended  service  clearance”).  Leave 
enough space for air circulation around the unit. 

● Since the unit is designed to work outdoors, some specifi c 

installation norms must be followed:

-  The unit will be located on the roof of the premises. If it is 

foreseen that it will work more on heating than on cooling, it 
is preferable to direct the coil towards the sun. If little work 
on heating is foreseen, choose North direction. 

-  Avoid  placing  obstacles  in  the  air  supply  or  return.  No 

obstacle may impede the air aspiration into the coils. Do not 
fi x the outdoor coil side in the predominant wind direction.

-  Do not install the unit in a closed enclosure or in conditions 

that originate air recirculation.

-  The chosen location must not fl ood and must be above the 

average height the snow reaches in that region.

7 - POSITIONING AND INSTALLATION

Foresee appropriate damping devices in these fi xings 
to  ensure  that  noise  and  vibration  transmission 
is  avoided  (refer  to  the  section  “Anchorage  for 
antivibrators”).   

Antivibrators assembly (silent-blocks)

Although the installer is the one who must decide on a case-by-
case basis the best way to place the unit in the ultimate location, 

Preassembly roofcurb (optional)

Optionally,  standardised  pre-assembly  roofcurb  made  of 
galvanised  steel  panelling  with  polyester  paint  and  thermally 
insulated with adjustable heights can be supplied.

Preparation of the ground

It is necessary to ensure that the surface where the unit is going 
to be installed in completely fl at. Any defect in the preparation of 
the unit support surface translates into stresses on the structure, 
which may result in its deformation. The unit must be perfectly 
level when installed.

These units can be installed on the fl oor or on a brick curb or steel 
profi le. Based on the fi xing solution defi ned in the installation 
project, it will be necessary to plan the placement in the base of 
threaded rods in the expectation that the unit supports can be 
fi xed later on. To do so, it is recommended that a template be 
made with the heights corresponding to the fi xings.

This  image  shows  how 
the  silent-block  option 
that  can  be  supplied  for 
this unit is fi xed to the unit.

Levelling 

system

Important:

 All of the necessary information for the installation of 

these roofcurbs is available in the specifi c instruction brochure 
on roofcurbs, No. 12.62 (supplied with the roofcurb).

Sound Level

These units are designed to work with a low acoustic level. In any 
case, the following must be taken into account for the design of 
the installation: the outdoor environment for acoustic radiation, 
the type of building for the noise transmitted by air, the solid 
elements for the transmission of vibrations. 

To reduce transmission through solid surfaces to the maximum, it 
is very advisable to install shock absorbers between the ground 
or structure and the unit frame. If necessary, a study must be 
commissioned to an acoustic technician.

Note: Sound levels can be found in the technical brochure of 
this series.

always in observation of the handling standards that have been 
described, below is a proposed assembly sequence that may 
facilitate  the  operation,  keeping  in  mind  that  the  sequence 
performed in the installation shall be the one most suitable to the 
solution chosen for each particular case based on the existence 
(or lack thereof) of brick frames, type of silent-blocks used, etc.

In the event of assembling directly on silent-blocks to the ground, 
it is recommended that a template of the unit’s footprint with the 
anchoring points of the silent-blocks be made, as described in 
the paragraph “Preparation of the ground”. 

With the help of the crane or the forklift truck, the unit will be 
raised to a suffi

  cient height that the silent-blocks can be screwed 

into  its  base. The  4  silent-blocks  of  the  corners  must  remain 
oblique and the interiors perpendicular to the unit.

M12 metric threads have been provided for their placement in 
the supports indicated in the following section “Anchorage for 
antivibrators”. A hex key 19 or Allen wrench 10 will be used for 
this operation based on the type of screw used.

Summary of Contents for 50EH 1100

Page 1: ...E N A N C E I N S T R U C T I O N S Translation of the original document 80049 12 2018 Packaged rooftop units and separated gas module option 50EN EH 415 1200 Nominal cooling capacity 92 8 287 0 kW No...

Page 2: ...ntrifugal fans optional 17 9 4 Air ducts connections 18 10 CONDENSATE DRAIN 19 11 SAFETY ELEMENTS 20 12 FACTORY OPTIONS AND ACCESSORIES 22 12 1 Filters 22 12 2 Hot water coil 22 12 3 Electrical heater...

Page 3: ...serial Nbr A o An Year Producto Product Produit Ref Produit Item Nbr Max Intensidad Intensit Current Kit Elec Tension Voltage Refrig KG F brica Factory Usine Co2 Teq Refrigerant NoBo Peso Poids Weight...

Page 4: ...1 optional 2 optional Assembly Assemblies with mixing box and free cooling Standard assembly M0 assemblies Change of supply and or return air position in the indoor circuit ME assemblies Axial air ex...

Page 5: ...stics or in the regulatory documentation provided with the product The compressor and line surfaces can reach temperatures above 100 C causing burns to the body In the same fashion under certain condi...

Page 6: ...he weight and the gravity centre coordinates of each model stated in the following page The recommended length for the forks will be bigger than the unit width so that the entire weight bearing struct...

Page 7: ...lies MRC1 assembly Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm 415 1 566...

Page 8: ...85 385 385 385 475 475 Gas burner module PCH065 414 414 414 PCH080 440 440 440 440 440 440 440 440 PCH105 468 468 468 468 468 468 468 468 PCH130 504 504 504 504 504 504 504 504 520 520 PCH160 555 555...

Page 9: ...en installed These units can be installed on the oor or on a brick curb or steel pro le Based on the xing solution de ned in the installation project it will be necessary to plan the placement in the...

Page 10: ...9 314 412 648 273 960 423 598 254 364 539 195 411 627 275 402 619 267 466 711 326 425 671 286 466 711 326 425 671 286 50EN EH MC0 Assembly MRC0 Assembly MC1 MWC1 Assemblies MRC1 Assembly R1 R2 R3 R4 R...

Page 11: ...R8 1100 330 536 475 288 357 564 502 316 330 536 475 288 357 564 502 316 1200 349 567 481 292 375 592 507 318 349 567 481 292 375 592 507 318 50EN EH MC0 Assembly MRC0 Assembly R1 R2 R3 R4 R5 R6 R7 R8...

Page 12: ...nd 960 50EN EH 1100 and 1200 LEGEND Indoor air coil Outdoor air coil Air supply Air return Condensates outlet 2 2 1 2000m m 2500mm 1500mm 1500mm 3 4 5 3500mm 2 2 1 1500mm 1500mm 3000m m 3 4 5 7 POSITI...

Page 13: ...tures refer to the technical brochure and the name plate The distance between the unit and its power source The protection to be placed at the power source Neutral operating conditions The electrical...

Page 14: ...the indoor circuit are connected Electric power supply inputs Main panel Auxiliary panel Main panel Electric power supply inputs Optionally these units can change the electronic control to CARRIERrtc...

Page 15: ...the cover clockwise g 4 Reversing valve heat pump Outdoor fan Compressor Low pressure High pressure Outdoor temperature probe B2 B7 Press transducer in the outdoor coil cir 1 Discharge T klixon switch...

Page 16: ...f the control board connector J18 Recommended cable section 1 5 mm2 V GND RH T CO2 GND 1 2 3 4 5 6 22 21 23 B10 J18 S13 Electric panel V GND GND CO2 NC Tpassive Tpassive 1 2 3 4 5 6 7 22 21 23 B10 J18...

Page 17: ...eck the operation conditions pressures ows and consumptions The coupling of characteristic curves of the fan and the room is very important so that the ows and pressures provided to the duct network a...

Page 18: ...Belt tension After xing the pulleys on the same plane the belt tension is made by tightening the tensor screw Excessive tension on the belt can lead to premature wear on the assembly Insu cient belt t...

Page 19: ...te pan is placed The drain piping must be slightly sloped to ease circulation towards the drain The original diameter of the piping must be respected No reduction can be made CONNECT SIPHON METTRE SIP...

Page 20: ...th low outdoor temperatures condensation control or in heating mode with high outdoor temperatures evaporation control This aids the unit s operation in all the seasons In the case of EC electronic fa...

Page 21: ...ction of the mixing box dampers optional mandatory for an outdoor temperature lower than 12 C WB Activation temperature 12 C WB Hot water coil circuit optional with anti freeze technology based on the...

Page 22: ...unit Note Refer to the operation mode of the pump with the GREAT COLD option in the chapter Safety elements Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Page 23: ...the following table To attach these frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the 4 Allen M4 screws included in the kit The heigh...

Page 24: ...op The stop drop can be installed in the indoor air coil and on the fresh air intake Indoor air coil available for models 415 to 960 and included in models 1100 and 1200 recommended in cases where a h...

Page 25: ...rews supplied with the unit Profiles for the attachment of the module For the transport and lifting to the roof using a crane cloth slings with rings will be used with the appropriate resistance separ...

Page 26: ...ame plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary information about the installation commissioning and...

Page 27: ...nection of the sensors supplied with the unit consult the chapter on Electrical connection That they are no cables close to heat sources Once the above veri cations have been carried out the control c...

Page 28: ...s signi cant temperatures in the cooling circuit see attached table other aspects considered interesting such as alarms detected by the electronic control of the unit The recording of these parameters...

Page 29: ...inal oil which has been stored in a hermetically sealed container until its time of use The oil type recommended for these units is Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL...

Page 30: ...opened Use safety gloves for this task Take care with the sharp parts of the coil V 220005 Centrifugal fan optional Verify that the turbine and the motor remain clean Foresee having a spare belt set...

Page 31: ...lable tighten them until they are snug then tighten a further turn Solder the suction and discharge piping Connect the compressor in accordance with the wiring diagram Make vacuum and next reload the...

Page 32: ...the module incorporate stainless steel quarter turn latches with 8 mm triangular inserts The procedure for extraction and cleaning of lters is equal to that described in the previous section Tabs in d...

Page 33: ...c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check di erential fuses b Verify the safety chain of the electronic control c Ver...

Page 34: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Page 35: ......

Page 36: ...tured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for RT Check ongo...

Reviews: