11 - SAFETY ELEMENTS

High pressure pressostat

Connected to the compressor discharge, it will stop its operation 
when  the  pressure  at  that  point  reaches  the  setpoint.  It 
disconnects at 42 bar and it is automatically reactivated.

Low pressure pressostat

When  connected  to  the  compressor  suction,  it  will  stop  its 
operation when the pressure at that point goes down below the 
tare value (caused by obstructions in the circuit, excessive dirt 
in the fi lters, fan stop or ice formation in the evaporator).

This  pressostat  disconnects  at  2  bar  and  is  automatically 
reactivated.

Magnetothermals for line protection

They  are  located  at  the  beginning  of  the  power  lines  for  the 
compressors and motor fan(s) to protect them. 

Automatic switch in the control circuit

Magnetothermal switch that protects the operation circuit against 
continuous  surges  as  well  as  against  high  currents  of  short 
duration (short circuits).

Defrost control

This  safety  device  is  intended  to  eliminate  ice  which  could 
accumulate in the outdoor coil when the unit is working in the 
heating cycle. Defrosting is carried out by the control depending 
on the value measured by the sensors on the outdoor coils and 
the time set between defrosting operations.

Main door switch

By using a mechanical device, it impedes access to the electric 
panel when the unit is with voltage.

Safety at the compressor

Temperature probe for the discharge from the compressor to 
protect the unit with discharge temperatures greater than 135ºC.

Condensation and evaporation pressure control 

This safety device, integrated in the control, enables managing 
the outdoor fans when the units are working in cooling mode with 
low outdoor temperatures (condensation control) or in heating 
mode with high outdoor temperatures (evaporation control). This 
aids the unit’s operation in all the seasons.

In the case of EC electronic fans, such as those that are found in 
these units by default, speed control will be proportional based 
on the average pressure measured by the pressure transducers 
in the outdoor coils.

Smoke detector (optional)

In accordance with standard NF S 61-961, this smoke detection 
station uses a LED to indicate the installation status, and if the 
probe detects the presence of smoke in the installation, it stops 
the operation of the unit. 

The station is installed in the factory in the main electric panel 
or in the auxiliary electric panel (depending on the model). The 
probe is placed on a pillar next to the supply fans.

Anti-fi re safety

The electronic control can activate an anti-fi re safety device that 
detains the unit when the return air surpasses a temperature 
of 60°C (by default). 

It cannot return to operation until the temperature has dropped 
to below 40ºC.

Smoke detecting station

Smoke detecting probe

Air inlet tube

Control of air fl ow

-  The  supply  plug-fans  (standard)  adapt  their  speed  to  the 

average  fl ow  measured  by  the  diff erential  pressure  sensor 
and the value set as a setpoint in the electronic control.

-  For  those  units  with  centrifugal  supply  fans  (optional),  a 

diff erential pressostat can be incorporated in order to measure 
the variation in air fl ow. This pressostat allows the detection of 
fan belt breakages, since the fan relay only detects operating 
faults that have arisen in the motor. This pressostat is installed 
in  the  factory  in  the  main  electric  panel  or  in  the  auxiliary 
electric panel (depending on the model). This safety device 
is  mandatory  for  units  with  electrical  heaters  and  with  gas 
burners if the unit does not have the supply plug-fans.

Summary of Contents for 50EH 1100

Page 1: ...E N A N C E I N S T R U C T I O N S Translation of the original document 80049 12 2018 Packaged rooftop units and separated gas module option 50EN EH 415 1200 Nominal cooling capacity 92 8 287 0 kW No...

Page 2: ...ntrifugal fans optional 17 9 4 Air ducts connections 18 10 CONDENSATE DRAIN 19 11 SAFETY ELEMENTS 20 12 FACTORY OPTIONS AND ACCESSORIES 22 12 1 Filters 22 12 2 Hot water coil 22 12 3 Electrical heater...

Page 3: ...serial Nbr A o An Year Producto Product Produit Ref Produit Item Nbr Max Intensidad Intensit Current Kit Elec Tension Voltage Refrig KG F brica Factory Usine Co2 Teq Refrigerant NoBo Peso Poids Weight...

Page 4: ...1 optional 2 optional Assembly Assemblies with mixing box and free cooling Standard assembly M0 assemblies Change of supply and or return air position in the indoor circuit ME assemblies Axial air ex...

Page 5: ...stics or in the regulatory documentation provided with the product The compressor and line surfaces can reach temperatures above 100 C causing burns to the body In the same fashion under certain condi...

Page 6: ...he weight and the gravity centre coordinates of each model stated in the following page The recommended length for the forks will be bigger than the unit width so that the entire weight bearing struct...

Page 7: ...lies MRC1 assembly Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg Centre of gravity Weight kg X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm X mm Y mm Z mm 415 1 566...

Page 8: ...85 385 385 385 475 475 Gas burner module PCH065 414 414 414 PCH080 440 440 440 440 440 440 440 440 PCH105 468 468 468 468 468 468 468 468 PCH130 504 504 504 504 504 504 504 504 520 520 PCH160 555 555...

Page 9: ...en installed These units can be installed on the oor or on a brick curb or steel pro le Based on the xing solution de ned in the installation project it will be necessary to plan the placement in the...

Page 10: ...9 314 412 648 273 960 423 598 254 364 539 195 411 627 275 402 619 267 466 711 326 425 671 286 466 711 326 425 671 286 50EN EH MC0 Assembly MRC0 Assembly MC1 MWC1 Assemblies MRC1 Assembly R1 R2 R3 R4 R...

Page 11: ...R8 1100 330 536 475 288 357 564 502 316 330 536 475 288 357 564 502 316 1200 349 567 481 292 375 592 507 318 349 567 481 292 375 592 507 318 50EN EH MC0 Assembly MRC0 Assembly R1 R2 R3 R4 R5 R6 R7 R8...

Page 12: ...nd 960 50EN EH 1100 and 1200 LEGEND Indoor air coil Outdoor air coil Air supply Air return Condensates outlet 2 2 1 2000m m 2500mm 1500mm 1500mm 3 4 5 3500mm 2 2 1 1500mm 1500mm 3000m m 3 4 5 7 POSITI...

Page 13: ...tures refer to the technical brochure and the name plate The distance between the unit and its power source The protection to be placed at the power source Neutral operating conditions The electrical...

Page 14: ...the indoor circuit are connected Electric power supply inputs Main panel Auxiliary panel Main panel Electric power supply inputs Optionally these units can change the electronic control to CARRIERrtc...

Page 15: ...the cover clockwise g 4 Reversing valve heat pump Outdoor fan Compressor Low pressure High pressure Outdoor temperature probe B2 B7 Press transducer in the outdoor coil cir 1 Discharge T klixon switch...

Page 16: ...f the control board connector J18 Recommended cable section 1 5 mm2 V GND RH T CO2 GND 1 2 3 4 5 6 22 21 23 B10 J18 S13 Electric panel V GND GND CO2 NC Tpassive Tpassive 1 2 3 4 5 6 7 22 21 23 B10 J18...

Page 17: ...eck the operation conditions pressures ows and consumptions The coupling of characteristic curves of the fan and the room is very important so that the ows and pressures provided to the duct network a...

Page 18: ...Belt tension After xing the pulleys on the same plane the belt tension is made by tightening the tensor screw Excessive tension on the belt can lead to premature wear on the assembly Insu cient belt t...

Page 19: ...te pan is placed The drain piping must be slightly sloped to ease circulation towards the drain The original diameter of the piping must be respected No reduction can be made CONNECT SIPHON METTRE SIP...

Page 20: ...th low outdoor temperatures condensation control or in heating mode with high outdoor temperatures evaporation control This aids the unit s operation in all the seasons In the case of EC electronic fa...

Page 21: ...ction of the mixing box dampers optional mandatory for an outdoor temperature lower than 12 C WB Activation temperature 12 C WB Hot water coil circuit optional with anti freeze technology based on the...

Page 22: ...unit Note Refer to the operation mode of the pump with the GREAT COLD option in the chapter Safety elements Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Page 23: ...the following table To attach these frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the 4 Allen M4 screws included in the kit The heigh...

Page 24: ...op The stop drop can be installed in the indoor air coil and on the fresh air intake Indoor air coil available for models 415 to 960 and included in models 1100 and 1200 recommended in cases where a h...

Page 25: ...rews supplied with the unit Profiles for the attachment of the module For the transport and lifting to the roof using a crane cloth slings with rings will be used with the appropriate resistance separ...

Page 26: ...ame plate featuring the main gas characteristics as well as the 50EN EH unit serial number on which it is to be mounted Important All the necessary information about the installation commissioning and...

Page 27: ...nection of the sensors supplied with the unit consult the chapter on Electrical connection That they are no cables close to heat sources Once the above veri cations have been carried out the control c...

Page 28: ...s signi cant temperatures in the cooling circuit see attached table other aspects considered interesting such as alarms detected by the electronic control of the unit The recording of these parameters...

Page 29: ...inal oil which has been stored in a hermetically sealed container until its time of use The oil type recommended for these units is Copeland 3MAF 32cST Danfoss POE 160SZ ICI Emkarate RL 32CF Mobil EAL...

Page 30: ...opened Use safety gloves for this task Take care with the sharp parts of the coil V 220005 Centrifugal fan optional Verify that the turbine and the motor remain clean Foresee having a spare belt set...

Page 31: ...lable tighten them until they are snug then tighten a further turn Solder the suction and discharge piping Connect the compressor in accordance with the wiring diagram Make vacuum and next reload the...

Page 32: ...the module incorporate stainless steel quarter turn latches with 8 mm triangular inserts The procedure for extraction and cleaning of lters is equal to that described in the previous section Tabs in d...

Page 33: ...c Timing of anti cycle short does not allow the starting d Open contact e Contactor coil burnt f Indoor klixon open a Check di erential fuses b Verify the safety chain of the electronic control c Ver...

Page 34: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Page 35: ......

Page 36: ...tured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for RT Check ongo...

Reviews: