background image

START-UP

Unit Preparation —

Make sure that unit has been in-

stalled in accordance with these installation instructions and
applicable codes. Make sure that Start-Up Checklist has been
completed and filled out.

Return-Air Filters —

Make sure correct filters are in-

stalled in filter tracks (see Table 1). Do not operate unit with-
out return-air filters.

Outdoor-Air Inlet Screens —

Outdoor-air inlet screens

must be in place before operating unit.

Compressor Mounting —

Compressors are inter-

nally spring mounted. Do not loosen or remove compressor
holddown bolts. On 48TJ014 units, remove the tiedown bands
that hold the compressors together.

Internal Wiring —

Check all electrical connections in

unit control boxes. Tighten as required.

Refrigerant Service Ports —

Each refrigerant sys-

tem has 4 Schrader-type service gage ports: one on the suc-
tion line, one on the liquid line, and two on the compressor
discharge line. Be sure that caps on the ports are tight. One
Schrader-type valve is located under both the high-pressure
switch and the low-pressure switch when ordered as an option.

Compressor Rotation —

On 3-phase units with scroll

compressors, it is important to be certain compressor is
rotating in the proper direction. To determine whether or not
compressor is rotating in the proper direction:
1. Connect service gages to suction and discharge pressure

fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-

sure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge

pressure does not rise to normal levels:
1. Note that the evaporator fan is probably also rotating in

the wrong direction.

2. Turn off power to the unit.
3. Reverse any two of the unit power leads.
4. Reapply power to the compressor.

The suction and discharge pressure levels should now move

to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit will make an elevated level of noise and
will not provide cooling.

Cooling —

To start unit, turn on main power supply. Set

system selector switch at COOL position and fan switch at
AUTO. position. Adjust thermostat to a setting below room
temperature. Compressor starts on closure of contactor.

Check unit charge. Refer to Service, Refrigerant Charge

section, page 26.

Reset thermostat at a position above room temperature.

Compressor will shut off. Evaporator fan will shut off after
30-second delay.
TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting thermostat at a position above room tem-
perature shuts unit off temporarily until space temperature
exceeds thermostat setting.

Main Burners —

Main burners are factory set and should

require no adjustment.
TO CHECK ignition of main burners and heating controls,
move thermostat set point above room temperature and verify
that the burners light and evaporator fan is energized. After
ensuring that the unit continues to heat the building, lower
the thermostat setting below the room temperature and verify
that the burners and evaporator fan turn off (fan will turn off
only if fan selector switch is in the AUTO. position). Refer
to Table 15 for the correct orifice to use at high altitudes.
NOTE: Upon a call for heat, the main burners will remain
on for a minimum of 60 seconds.

Heating

1. Purge gas supply line of air by opening union ahead of

gas valve. When gas odor is detected, tighten union and
wait 5 minutes before proceeding.

2. Turn on electrical supply and open manual gas valve.
3. Set system switch selector at HEAT position and fan switch

at AUTO. or ON position. Set heating temperature lever
above room temperature.

4. The induced-draft motor will start.
5. After a call for heating, the main burners should light within

5 seconds. If the burners do not light, then there is a
22-second delay before another 5-second try. If the burn-
ers still do not light, the time delay is repeated. If the
burners do not light within 15 minutes, there is a lockout.
To reset the control, break the 24 v power to W1.

6. The evaporator-fan motor will turn on 45 seconds after

the burners are ignited.

7. The evaporator-fan motor will turn off 45 seconds after

the thermostat temperature is satisfied.

8. Adjust airflow to obtain a temperature rise within the range

specified on the unit nameplate and in Table 1.
NOTE: The default value for the evaporator-fan motor
ON and OFF delay is 45 seconds. The Integrated Gas Unit
Controller (IGC) modifies this value when abnormal limit
switch cycles occur. Based upon unit operating condi-
tions, the ON delay can be reduced to 0 seconds and the
OFF delay can be extended to 180 seconds.
When one flash of the LED (light-emitting diode) is ob-
served, the evaporator-fan ON/OFF delay has been modi-
fied. If the limit switch trips at the start of the heating
cycle during the evaporator ON delay, the time period of
the ON delay for the next cycle will be 5 seconds less
than the time at which the switch tripped. (Example: If
the limit switch trips at 30 seconds, the evaporator-fan
ON delay for the next cycle will occur at 25 seconds.) To
prevent short-cycling, a 5-second reduction will only oc-
cur if a minimum of 10 minutes has elapsed since the last
call for heating.
The evaporator-fan OFF delay can also be modified. Once
the call for heating has ended, there is a 10-minute period
during which the modification can occur. If the limit switch
trips during this period, the evaporator-fan OFF delay will
increase by 15 seconds. A maximum of 9 trips can occur,
extending the evaporator-fan OFF delay to 180 seconds.
To restore the original default value, reset the power to
the unit.

TO SHUT OFF UNIT — Set system selector switch at OFF
position. Resetting heating selector lever below room tem-
perature will shut unit off temporarily until space tempera-
ture falls below thermostat setting.

23

Summary of Contents for 48TJD008

Page 1: ...replaced before use When pressure testing field supplied gas piping at pressures of 1 2 psig or less a unit connected to such piping must be isolated by manually closing the gas valve s Before perform...

Page 2: ...e the bottom drain connection for a roof curb in stallation relocate the factory installed plug from the bottom connection to the side connection See Fig 4 The piping for the condensate drain and exte...

Page 3: ...3 49 NPT 1 2 9 NPT CRBTMPWR00A100 THRU THE BOTTOM 3 49 NPT 11 49 NPT 1 29 NPT CRBTMPWR00A200 THRU THE BOTTOM NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 3 Dimensions in are...

Page 4: ...be in accordance with the CAN1 B149 1 and CAN1 B149 2 installation codes for gas burning appliances MAXIMUM ALLOWABLE DIFFERENCE in A B B C A C 0 5 1 0 1 0 Fig 3 Unit Leveling Tolerances NOTE Drain p...

Page 5: ...5 1 15 x 15 Alt 1 15 x 15 1 15 x 15 1 15 x 15 Type Drive Std Belt Belt Belt Belt Alt Belt Belt Belt Nominal Cfm 3000 3400 4000 5000 Motor Hp Std Alt Maximum Continuous Bhp Std 2 40 2 40 2 40 4 20 Alt...

Page 6: ...Temperature Rise Range 20 50 35 65 45 75 20 50 35 65 45 75 35 65 35 65 40 70 35 65 40 70 Manifold Pressure in wg Natural Gas Std 3 5 3 5 3 5 3 5 Liquid Propane Alt 3 5 3 5 3 5 3 5 Gas Valve Quantity 1...

Page 7: ...r clearance is optional d Overhead 60 in to assure proper condenser fan operation e Between units control box side 42 in per NEC National Electrical Code f Between unit and ungrounded surfaces control...

Page 8: ...te If the 208 230 v unit is to be connected to a 208 v power sup ply the transformer must be rewired by moving the black wire from the 230 v red wire on the transformer and con necting it to the 200 v...

Page 9: ...4 30 24 134 Alt 3 4 24 2 30 25 173 575 3 phase Std 518 632 6 4 44 0 1 4 0 8 2 6 30 17 6 20 18 107 Alt 3 4 18 2 20 19 139 014 121 2 Tons 208 230 3 phase Std 187 254 23 0 146 0 1 4 1 4 10 6 57 65 2 65 2...

Page 10: ...minal Block Connection Splice Connection Factory Supplied Field Wiring Factory Wiring LEGEND AHA Adjustable Heat Anticipator CC Cooling Compensator TC Thermostat Cooling TH Thermostat Heating Field Wi...

Page 11: ...nel Save panels and screws See Fig 14 3 Separate hood and screen from basepan by removing the screws and brackets securing them Save all screws and discard brackets 4 Replace outdoor air opening panel...

Page 12: ...conomizer 90 degrees until the econo mizer motor faces the condenser section see Fig 22 b Rotate the barometric relief damper hinge 90 degrees Barometric relief damper should open ver tically to opera...

Page 13: ...CONTROL BOARD ECONOMIZER PLUG ECONOMIZER MOTOR TOP SCREW Fig 21 Durablade Economizer Installed in Unit ECONOMIZER CONTROL BOARD ECONOMIZER MOTOR POSITION SETTING BRACKET Fig 22 Horizontal Durablade Ec...

Page 14: ...T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPER CLOSED OPEN OUTDOOR TEMP F REV 97 3672 CW SETPOINTS CCW CONTACTS SHOWN...

Page 15: ...sconnected during adjustment b The 2 potentiometers with slots for adjustment are located on the face of the economizer logic module Turn the lower potentiometer fully clockwise The dampers should be...

Page 16: ...t keyway of pulley hub and tighten setscrew see Table 1 for speed change for each full turn of pulley flange To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along fan s...

Page 17: ...5 760 735 710 685 012 1085 1060 1035 1010 985 960 935 910 885 860 835 014 1080 1060 1035 1015 990 970 950 925 905 880 860 014 1260 1220 1185 1155 1130 1100 1075 1045 1015 990 960 930 900 Approximate r...

Page 18: ...N MOTOR MAXIMUM CONTINUOUS BHP MAXIMUM OPERATING WATTS UNIT VOLTAGE MAXIMUM AMP DRAW 008 Std 2 40 2120 208 230 6 1 460 2 7 575 2 7 009 Std 2 40 2120 208 230 6 1 460 2 7 575 2 7 012 Std 2 40 2120 208 2...

Page 19: ...remature motor failure Unit warranty will not be affected 7 Use of a field supplied motor may affect wire sizing Contact your Carrier representative to verify 8 Interpolation is permissible Do not ext...

Page 20: ...4 1 6 1 8 2 0 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3700 729 1 36 790 1 58 847 1 79 902 2 06 955 2 29 1008 2 55 1060 2 80 1108 3 05 1152 3 27 1190 3 46 3800...

Page 21: ...ion is permissible Do not extrapolate Table 12 Fan Performance 48TJ009 Horizontal Discharge Units AIRFLOW Cfm EXTERNAL STATIC PRESSURE in wg 0 2 0 4 0 6 0 8 0 9 1 0 1 2 1 4 1 6 Rpm Bhp Rpm Bhp Rpm Bhp...

Page 22: ...pm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 3700 677 1 20 748 1 43 810 1 65 869 1 89 928 2 17 984 2 43 1036 2 68 1080 2 90 1114 3 07 1135 3 17 3800 691 1 28 761 1 52 822 1 75 880 1 98 937 2 28 993 2 55 104...

Page 23: ...ture and verify that the burners light and evaporator fan is energized After ensuring that the unit continues to heat the building lower the thermostat setting below the room temperature and verify th...

Page 24: ...an auto fan or to the minimum position when using a continuous fan When the outdoor air temperature is below the OAT set ting and the thermostat calls for cooling the economizer damp ers move to the m...

Page 25: ...n off unit power 2 Remove top panel screws on condenser end of unit 3 Remove condenser coil corner post See Fig 37 To hold top panel open place coil corner post between top panel and center post See F...

Page 26: ...te chart are met Note the charging charts are different from the type normally used The charts are based on charging the units to the correct superheat for the various operating conditions Accurate pr...

Page 27: ...Fig 42 Cooling Charging Chart 48TJ009 Fig 43 Cooling Charging Chart 48TJ012 27...

Page 28: ...s a self diagnostic LED A single LED on the IGC pro vides a visual display of operational or sequential problems when the power supply is interrupted When a break in power occurs the module will be re...

Page 29: ...above CLEANING AND ADJUSTMENT 1 Remove burner rack from unit as described in Removal and Replacement of Gas Train section above 2 Inspect burners if dirty remove burners from rack 3 Using a soft brus...

Page 30: ...llimeters Fig 47 Spark Gap Adjustment 125 000 BTUH INPUT 48TJD008 009 120 000 180 000 BTUH INPUT 48TJD012 48TJE008 009 48TJD014 48TJE012 48TJF008 009 48TJE014 48TJF012 180 000 224 000 BTUH INPUT 200 0...

Page 31: ...spacing gaps etc Ensure that flame sense and ignition wires are prop erly terminated Verify that unit is obtaining proper amount of gas Induced draft motor fault LED 6 flashes IGC does not sense that...

Page 32: ...the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired properly and no 24 vac e...

Page 33: ...high enthalpy The motor should drive towards closed If these actions do not occur replace module 4 Disconnect 1 2 Kohm checkout resistor before resuming operation Damper does not close No power to ec...

Page 34: ...Compressor makes excessive noise 48TJ014 scroll only Compressor rotating in wrong direction Reverse the 3 phase power leads as described on page 23 Compressor operates continuously Dirty air filter Re...

Page 35: ...for restriction Clean as necessary Check orifice to burner alignment Burners will not turn off Unit is locked into Heating mode for a one minute minimum Wait until mandatory one minute time period has...

Page 36: ...Fig 48 Typical Wiring Schematic and Component Arrangement 36...

Page 37: ......

Page 38: ...urer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 4 Tab 1a 6a PC 111 Catalog No 564 934 Printed in U S A Fo...

Page 39: ......

Page 40: ...TART UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS L1 L2 L3 COMPRESSOR AMPS L1 L2 L3 INDOOR FAN AMPS L1 L2 L3 TEMPERATURES OUTDOOR AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOL...

Reviews: