APPENDIX A — LOCAL DISPLAY AND CCN TABLES (cont)
MODE — CONFIGURATION (cont)
LEGEND
FIOP — Factory-Installed Option
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/ SUB-TABLE
CCN POINT
PAGE NO.
CONFIGURATION (cont)
COOL (cont)
CIR.B
Circuit B
42
CS.B1
B1 Current Sensing
Enable/Disable
Enable
B1_SENSE
55
B1.FN
B Circuit Level 1 Fans
0 to 7
No Humidi-MiZer FIOP
4
Humidi-MiZer FIOP
1
CIR_B_1
B2.FN
B Circuit Level 2 Fans
0 to 7
No Humidi-MiZer FIOP
6 (20)
2 (24, 28)
Humidi-MiZer FIOP
3 (20)
2 (24, 28)
CIR_B_2
B3.FN
B Circuit Level 3 Fans
0 to 7
No Humidi-MiZer FIOP
6
Humidi-MiZer FIOP
3
CIR_B_3
CIR.C
Circuit C
42
CS.C1
C1 Current Sensing
Enable/Disable
Disable
C1_SENSE
55
C1.FN
C Circuit Level 1 Fans
0 to 7
0
CIR_C_1
C2.FN
C Circuit Level 2 Fans
0 to 7
0
CIR_C_2
C3.FN
C Circuit Level 3 Fans
0 to 7
0
CIR_C_3
SST
Low Suction Control
LOW SUCTION CONTROL
SST.O
Suction OK Temperature
10 to 50
dF
18
SSTOK
SST.1
Low Suction — Level 1
10 to 50
dF
20
SSTLEV1
55
SST.2
Low Suction — Level 2
5 to 50
dF
15
SSTLEV2
55
SST.3
Low Suction — Level 3
0 to 50
dF
10
SSTLEV3
55
OFC
Outdoor Fan Control
OUTDOOR FAN CONTROL
42
OFC.3
OFC3 Enable. CCH Disable
Yes/No
Yes
OFC3_CTL
56
0.MXP
Fan Lev0 Max Pressure
100 to 500
psig
200
LEV0MAXP
1.MXP
Fan Lev1 Max Pressure
100 to 500
psig
450
LEV1MAXP
2.MNP
Fan Lev2 Min Pressure
100 to 500
psig
200
LEV2MNP
2.ON
Fan Lev2 On Temperature
0 to 100
F
no Humidi-MiZer FIOP:
55 (20)
45 (24-28)
Humidi-MiZer FIOP:
68 (20)
61 (24)
61 (28)
LEV2ON
2.OFF
Fan Lev2 Off Temperature
0 to 100
F
no Humidi-MiZer FIOP:
50 (20)
40 (24-28)
Humidi-MiZer FIOP:
57 (20)
57 (24)
57 (28)
LEV2OFF
2.MXP
Fan Lev2 Max Pressure
100 to 500
psig
400
LEV2MAXP
3.MNP
Fan Lev3 Min Pressure
100 to 500
psig
250
LEV3MINP
3.ON
Fan Lev3 on Temperature
0 to 100
F
no Humidi-MiZer FIOP:
65
Humidi-MiZer FIOP:
88 (20)
68 (24)
68 (28)
LEV3ON
3.OFF
Fan Lev3 Off Temperature
0 to 100
F
no Humidi-MiZer FIOP:
55
Humidi-MiZer FIOP:
78 (20)
62 (24)
62 (28)
LEV3OFF
Summary of Contents for 48PG24
Page 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Page 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Page 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Page 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Page 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Page 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Page 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Page 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Page 105: ......