93
APPENDIX A — LOCAL DISPLAY AND CCN TABLES
MODE — RUN STATUS
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUB-TABLE
CCN
POINT
WRITE
STATUS
RUN STATUS
STATUS DISPLAY
VIEW
Auto View of Run Status
(VIEW = Display only)
HVAC
HVAC Mode Status
1=Disabled
2=Fan Only
3=Cool
4=Heat
OCC
Currently Occupied
Yes/No
SAT
Supply Air Temperature
xxx.x
dF
ALRM
Current Alarms & Alerts
xx
TIME
Time of Day
xx.xx
hh.mm
VERS
Software Version Numbers
VERSIONS
MBB
CESR131320-xx-xx
ECB
CESR131249-xx-xx
MARQ
CESR131171-xx-xx
HRS
Component Run Hours
STRTHOUR
A1
Compressor A1 Run Hours
xxxxx.xx
hours
HR_A1
Forcible
A2
Compressor A2 Run Hours
xxxxx.xx
hours
HR_A2
Forcible
B1
Compressor B1 Run Hours
xxxxx.xx
hours
HR_B1
Forcible
C1
Compressor C1 Run Hours
xxxxx.xx
hours
HR_C1
Forcible
CCH
Crankcase Heat Run Hours
xxxxx.xx
hours
HR_CCH
Forcible
IDF
Indoor Fan Run Hours
xxxxx.xx
hours
HR_IDF
Forcible
OFC.1
Outdoor Fan 1 Run Hours
xxxxx.xx
hours
HR_OFC_1
Forcible
OFC.2
Outdoor Fan 2 Run Hours
xxxxx.xx
hours
HR_OFC_2
Forcible
OFC.3
Outdoor Fan 3 Run Hours
xxxxx.xx
hours
HR_OFC_3
Forcible
HT.1
Heat Stage 1 Run Hours
xxxxx.xx
hours
HR_HTR_1
Forcible
HT.2
Heat Stage 2 Run Hours
xxxxx.xx
hours
HR_HTR_2
Forcible
PE.1
Power Exhaust1 Run Hours
xxxxx.xx
hours
HR_PE_1
Forcible
PE.2
Power Exhaust2 Run Hours
xxxxx.xx
hours
HR_PE_2
Forcible
ALRM
Alarm Relay Run Hours
xxxxx.xx
hours
HR_ALM
Forcible
CRC
Reheat1 Valve Run Hours
xxxxx.xx
hours
HR_CRC
Forcible
RH2.A
Reheat2 Valve A Run Hrs
xxxxx.xx
hours
HR_RH2_A
Forcible
RH2.B
Reheat2 Valve BC Run Hrs
xxxxx.xx
hours
HR_RH2_B
Forcible
STRT
Component Starts
A1
Compressor A1 Starts
xxxxxx
ST_A1
Forcible
A2
Compressor A2 Starts
xxxxxx
ST_A2
Forcible
B1
Compressor B1 Starts
xxxxxx
ST_B1
Forcible
C1
Compressor C1 Starts
xxxxxx
ST_C1
Forcible
CCH
Crankcase Heat Starts
xxxxxx
ST_CCH
Forcible
IDF
Indoor Fan Starts
xxxxxx
ST_IDF
Forcible
OFC.1
Outdoor Fan 1 Starts
xxxxxx
ST_OFC_1
Forcible
OFC.2
Outdoor Fan 2 Starts
xxxxxx
ST_OFC_2
Forcible
OFC.3
Outdoor Fan 3 Starts
xxxxxx
ST_OFC_3
Forcible
HT.1
Heat Stage 1 Starts
xxxxxx
ST_HTR_1
Forcible
HT.2
Heat Stage 2 Starts
xxxxxx
ST_HTR_2
Forcible
PE.1
Power Exhaust1 Starts
xxxxxx
ST_PE_1
Forcible
PE.2
Power Exhaust2 Starts
xxxxxx
ST_PE_2
Forcible
ALRM
Alarm Relay Starts
xxxxxx
ST_ALM
Forcible
CRC
Reheat1 Valve Starts
xxxxxx
ST_CRC
Forcible
RH2.A
Reheat2 Valve A Starts
xxxxxx
ST_RH2_A
Forcible
RH2.B
Reheat2 Valve BC Starts
xxxxxx
ST_RH2_B
Forcible
MODE
Control Modes
MODEDISP
SYS
System Mode
1=Disabled
2=Enabled
3=Test
SYS_MODE
HVAC
HVAC Mode
1=Off
2=Fan Only
3=Cool
4=Heat
HVACMODE
OCC
Currently Occupied
Yes/No
OCCUPIED
Forcible
T.OVR
Timed Override in Effect
Yes/No
MODETOVR
LINK
Linkage Active
Yes/No
MODELINK
C.LOC
Circuit OAT Lockout
Yes/No
COMPLOCK
H.LOC
Heat OAT Lockout
Yes/No
HEATLOCK
E.LOC
Econo Cool OAT Lockout
Yes/No
ECONLOCK
COOL
Cooling Status
COOLDISP
DMD.C
Cooling Demand
xxx.x
^F
COOL_DMD
AVL.C
Available Cooling Stages
x
AVLCSTGS
REQ.C
Requested Cooling Stages
x
REQCSTGS
IDF
Indoor Fan Relay
On/Off
IDF
CCH
Crankcase Heat Relay
On/Off
CCH
OFC.1
Outdoor Fan 1 Relay
On/Off
OFC_1
OFC.2
Outdoor Fan 2 Relay
On/Off
OFC_2
OFC.3
Outdoor Fan 3 Relay
On/Off
OFC_3
CRC
Cool
−>
Reheat1 Control
On/Off
CRC
CIR.A
Refrigerant Circuit A
CMP.A
Compressors A
On/Off
COMP_A
TG.A
Timeguard A
xxx
sec
TIMGD_A
CS.A1
Compressor A1 Feedback
On/Off
CS_A1
CS.A2
Compressor A2 Feedback
On/Off
CS_A2
RH2.A
Reheat2 Valve A
On/Off
RH2_A
SST.A
Sat. Suction Temp A
xxx.x
dF
SST_A
SSP.A
Suction Pressure A
xxx.x
psig
SSP_A
SCT.A
Sat. Condenser Temp A
xxx.x
dF
SCT_A
SCP.A
Condenser Pressure A
xxx.x
psig
SCP_A
Summary of Contents for 48PG24
Page 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Page 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Page 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Page 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Page 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Page 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Page 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Page 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Page 105: ......