Table 34 — Fan Rpm At Motor Pulley Settings* — 50PG20-28
*Approximate fan rpm shown.
NOTE: Factory pulley speed setting is at 3 turns open.
CONTROLS QUICK START
The following information will provide a quick guide to
setting up and configuring the 48/50PG series units with
Comfort
Link™ controls. Unit controls are pre-configured at
the factory for factory-installed options. Field-installed acces-
sories will require configuration at start-up. Additionally,
specific job requirements may require changes to default
configuration values. See the CCN and Display parameter
tables and other sections of these instructions for more details.
Thermostat Control —
Wire accessory thermostat to
the corresponding R, Y1, Y2, W1, W2, and G terminals on the
field connection terminal board located at the unit control box.
The Unit Control Type configuration,
Configuration
→
UNIT
→
U.CTL,
default value is for Thermostat (2) so there
is no need to configure this item.
Space Temperature Sensor Control — Direct
Wired (T-55 or T-56) —
Wire accessory space tempera-
ture sensor(s) to the T-55 terminals on the field connection
terminal board located at the unit control box. Refer to Field-
Installed Accessories section.
The Unit Control Type configuration,
Configuration
→
UNIT
→
U.CTL
, must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and
W1 for heating mode to operate.
Space Temperature Sensor Control — CCN
(T-58) —
Install the T-58 communicating thermostat. Con-
nect the CCN communication bus from the T-58 to the CCN
terminals on the field connection terminal board located at the
unit control box. Configure the 48/50PG unit CCN communi-
cation element number, bus number, and baud rate. Configure
the T-58 thermostat CCN communication element number and
also configure the T-58 with the 48/50PG unit element number.
The Unit Control Type configuration,
Configuration
→
UNIT
→
U.CTL
, must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and
W1 for heating mode to operate.
Space Temperature Control — CCN Link-
age —
The CCN communication must be properly configured
for the 48/50PG unit and all devices. Linkage configuration is
automatically done by the supervisory CCN Linkage device.
The Unit Control Type configuration,
Configuration
→
UNIT
→
U.CTL
must be set to Space Sensor (3). The jumper
wire in the installer’s packet must be connected between R and
W1 for heating mode to operate.
Installation of an accessory supply air temperature (SAT)
sensor in the supply duct is recommended for Linkage applica-
tions. A supply duct SAT measurement is valid for heating
mode display, while the factory-standard internal SAT is not
valid for heating due to its location upstream of the heating sec-
tion. When installing the supply duct SAT, the heating mode
display is enabled by setting
Configuration
→
HEAT
→
SAT.H
to ENBL.
Space Humidity Control — Humidistat —
Wire
the Humidistat accessory to terminals Humidistat 1 and 2 locat-
ed on the field connection terminal strip in the bottom of the
control box. The Space Humidity Switch setting is located at
Configuration
→
Unit
→
RH.SW
. The factory default for units
with Humidi-MiZer™ system is 1 (normally open).
Space Humidity Control — Thermidistat™ —
Wire the Thermidistat accessory Dehum output to terminal
Humidistat1 located on the field connection terminal strip in
the bottom of the control box. The Space Humidity Switch set-
ting is located at
Configuration
→
Unit
→
RH.SW
. The factory
default for units with Humidi-MiZer system is 1 (normally
open).
Space Humidity Control — Relative Humidity
Sensor —
Wire the humidity sensor to terminals 3 (–) and
4 (+) located on the field connection terminal strip in the
bottom of the control box. The RH Sensor on OAQ Input set-
ting is located at
Configuration
→
Unit
→
RH.S
. The setting
must be configured to YES to use the relative humidity sensor.
CCN Communication —
Configure
Configuration
→
CCN
→
CCN.A
to desired element number. (Default is 1.) Con-
figure
Configuration
→
CCN
→
CCN.B
to desired bus number.
(Default is 0.) Configure
Configuration
→
CCN
→
BAUD
to
desired code number for baud rate. (Default is 3 = 9600 baud.)
Accessories —
See the Field-Installed Accessories sec-
tion, control connection tables, and CCN or Display parameter
tables for required connections and configurations.
Service Test —
The Service Test function can be used to
verify proper operation of compressors, heating stages,
indoor fan, outdoor fans, power exhaust fans, economizer,
Humidi-MiZer system, and alarm relay. Use of Service Test is
recommended at initial system start-up and during trouble-
shooting.
50PG
DRIVE
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
20 and 24
(230 and
460 volt)
Low Range Vertical
685
706
727
749
770
791
812
833
854
876
897
918
939
Mid-Low Range Vertical
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
Mid-High Range Vertical
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Vertical
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low Range Horizontal
685
706
727
749
770
791
812
833
854
876
897
918
939
Mid-Low Range Horizontal
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
Mid-High Range Horizontal
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Horizontal
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
20 and 24
(575 Volt)
Low Range Vertical
751
768
785
802
819
836
853
869
886
903
920
937
954
Mid-Low Range Vertical
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
Mid-High Range Vertical
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Vertical
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low Range Horizontal
751
768
785
802
819
836
853
869
886
903
920
937
954
Mid-Low Range Horizontal
949
970
992
1013
1035
1056
1078
1099
1120
1142
1163
1185
1206
Mid-High Range Horizontal
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Horizontal
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
28
(all voltages)
Low Range Vertical
687
703
718
734
749
765
780
796
811
827
842
858
873
Mid-Low Range Vertical
805
822
839
856
872
889
906
923
940
957
973
990
1007
Mid-High Range Vertical
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Vertical
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Low Range Horizontal
687
703
718
734
749
765
780
796
811
827
842
858
873
Mid-Low Range Horizontal
805
822
839
856
872
889
906
923
940
957
973
990
1007
Mid-High Range Horizontal
941
961
980
1000
1019
1039
1059
1078
1098
1117
1137
1156
1176
High Range Horizontal
1014
1038
1061
1085
1108
1132
1156
1179
1203
1226
1250
1273
1297
Summary of Contents for 48PG24
Page 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Page 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Page 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Page 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Page 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Page 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Page 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Page 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Page 105: ......