CL-3
MODE — CONFIGURATION (cont)
LEGEND
FIOP — Factory-Installed Option
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
CONFIGURATION (cont)
OFC (cont)
3.OFF
Fan Lev3 Off Temperature 0 to 100 F
no Humidi-MiZer FIOP:
55
Humidi-MiZer FIOP:
78 (20)
62 (24)
62 (28)
HMZR
Humidimizer Config
REHT
Humidimizer Equipped
Yes/No
No: no Humidi-MiZer
FIOP
Yes: Humidi-MiZer FIOP
R.DEC
Reheat2 Stage Decr.
Time
0 to 999 secs
60
R.INC
Reheat2 Stage Incr. Time 0 to 999 secs
300
RH.FN
Reheat Fan Control
Yes/No
Yes
RF.LV
Reheat2 ODF Fan On
Level
0 to 3
2
RF.ON
Reheat2 ODF Fan On
Temp
0 to 100 F
93 (20)
93 (24)
85 (28)
RF.OF
Reheat2 ODF Fan Off
Temp
0 to 100 F
83 (20)
88 (24)
80 (28)
RA.LO
Reheat2 OAT Limit A
20 to 70 F
40
RA.LP
Reheat2 SSP Lo Limit A
50 to 100 psig
80
RA.HP
Reheat2 SSP Hi Limit A
50 to 100 psig
90
RB.LO
Reheat2 OAT Limit B, C
20 to 70 F
50
RB.LP
Reheat2 SSP Lo
Limit B, C
50 to 100 psig
80
RB.HP
Reheat2 SSP Hi
Limit B, C
50 to 100 psig
90
HEAT
Heating Configuration
HT.TY
Type of Heat Installed
0 = No Heat
1 = Gas
2 = Electric
0 (50 series with no
electric heat)
1 (48 series)
2 (50 series with electric
heat)
N.HTR
Number of Heat Stages
1 to 2
1 (48 series 1-phase,
50 series <15kW)
2 (48 series 3-phase,
50 series >=15kW)
MRT.H
Heat Minimum On Time
60 to 999 sec
120
MOT.H
Heat Minimum Off Time
60 to 999 sec
120
H.DEC
Heat Stage Decrease
Rate
120 to 999 sec
300
H.INC
Heat Stage Increase Rate 120 to 999 sec
450
FOD.E
Fan-off Delay, Elect Heat
10 to 600 sec
30
FOD.G
Fan-off Delay, Gas Heat
45 to 600 sec
45
HT.LO
Heating Lockout Temp
40 to 125 dF
75
SAT.H
SAT Heat Mode Sensing
Enable/Disable
Disable
SPT
Space Temperature
Sensor
HT.PD
SPT Heat Demand (+)
Level
0.5 to 5 ^F
1
HT.ND
SPT Heat Demand (–)
Level
–5 to –0.5 ^F
–1
H.LAG
Heat Thermal Lag Factor 0 to 5 min
1
ECON
Economizer Configuration
EC.EN
Economizer Installed
Yes/No
No: no FIOP
Yes: FIOP
E.CTL
Economizer Control Type 1=Digital, Position Feed-
back
2=Digital, Command
Feedback
3=Analog Control
1
EC.MN
Econo Minimum Position
0 to 100 %
30
EC.MX
Econo Cool Max Position 0 to 100 %
100
EH.LO
Econo Cool Hi Temp Limit 40 to 100 dF
65
EL.LO
Econo Cool Lo Temp
Limit
–30 to 50 dF
0
UEFC
Unoccupied Free Cooling 0=Disabled
1=Entire Unoccupied
Period
2=PreOccupancy Time
2
Summary of Contents for 48PG24
Page 68: ...68 Fig 14 Low Voltage Control Schematic 48PG20 28 Units without Humidi MiZer System a48 7627...
Page 69: ...69 Fig 15 Low Voltage Control Schematic 48PG20 28 Units with Humidi MiZer System a48 8227...
Page 70: ...70 Fig 16 Low Voltage Control Schematic 50PG20 28 Units without Humidi MiZer System a48 7778...
Page 71: ...71 Fig 17 Low Voltage Control Schematic 50PG20 28 Units with Humidi MiZer System a50 8101...
Page 72: ...72 Fig 18 Power Schematic Units without Humidi MiZer System a48 7628...
Page 73: ...73 Fig 19 Power Schematic Units with Humidi MiZer System a48 8228...
Page 74: ...74 Fig 20 Component Arrangement Units without Humidi MiZer System a48 8229...
Page 75: ...75 Fig 21 Component Arrangement Units with Humidi MiZer System a48 8230...
Page 105: ......