136
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
DEFAULT
ENTRY
CONFIGURATION (cont)
COOL
(cont)
SAT
Supply Air Temperature
SA.PD
SAT Cool Demand (+)
Level
0.5 to 10 ^F
1
SA.ND
SAT Cool Demand (–) Lev-
el
–10 to –0.5 ^F
–1
SAT.U
Minimum SAT Upper Level 35.0 to 65.0 dF
60
SAT.L
Minimum SAT Lower Level 35.0 to 65.0 dF
35 (03-07)
45 (08-14)
50 (16)
SPT
Space Temperature
CL.PD
SPT Cool Demand (+)
Level
0.5 to 5 ^F
1
CL.ND
SPT Cool Demand (–) Lev-
el
–5 to –0.5 ^F
–1
C.LAG
Cool Thermal Lag Factor
0 to 5 min
1
CIR.A
Circuit A
CS.A1
A1 Current Sensing
Enable/Disable
Disable (1-phase)
Enable (3-phase)
CS.A2
A2 Current Sensing
Enable/Disable
Disable
A1.FN
A Circuit Level 1 Fans
0 to 7
1
A2.FN
A Circuit Level 2 Fans
0 to 7
0 (03-07)
3 (08-16)
A3.FN
A Circuit Level 3 Fans
0 to 7
0 (03-07)
3 (08-16)
CIR.B
Circuit B
CS.B1
B1 Current Sensing
Enable/Disable
Disable (03-07)
Enable (08-16)
B1.FN
B Circuit Level 1 Fans
0 to 7
0 (03-07)
1 (08-16)
B2.FN
B Circuit Level 2 Fans
0 to 7
0 (03-07)
3 (08-16)
B3.FN
B Circuit Level 3 Fans
0 to 7
0 (03-07)
3 (08-16)
CIR.C
Circuit C
CS.C1
C1 Current Sensing
Enable/Disable
Disable (03-14)
Enable (16)
C1.FN
C Circuit Level 1 Fans
0 to 7
0 (03-14)
1 (16)
C2.FN
C Circuit Level 2 Fans
0 to 7
0 (03-14)
3 (16)
C3.FN
C Circuit Level 3 Fans
0 to 7
0 (03-14)
3 (16)
SST
Low Suction Control
SST.O
Suction OK Temperature
10 to 50 dF
18
SST.1
Low Suction — Level 1
10 to 50 dF
20
SST.2
Low Suction — Level 2
5 to 50 dF
15
SST.3
Low Suction — Level 3
0 to 50 dF
10
OFC
Outdoor Fan Control
OFC.3
OFC3 Enable. CCH
Disable
Yes/No
No (03-16)
Yes (20-28)
0.MXP
Fan Lev0 Max Pressure
100 to 500 psig
200
1.MXP
Fan Lev1 Max Pressure
100 to 500 psig
400 (03-16)
450 (20-28)
2.MNP
Fan Lev2 Min Pressure
100 to 500 psig
150 (03-16)
200 (20-28)
2.ON
Fan Lev2 On Temperature
0 to 100 F
no Humidi-MiZer FIOP:
55 (03-16)
55 (20)
45 (24-28)
Humidi-MiZer FIOP:
68 (20)
61 (24)
61 (28)
2.OFF
Fan Lev2 Off Temperature
0 to 100 F
no Humidi-MiZer FIOP:
45 (03-16)
50 (20)
40 (24-28)
Humidi-MiZer FIOP:
57 (20)
57 (24)
57 (28)
2.MXP
Fan Lev2 Max Pressure
100 to 500 psig
400
3.MNP
Fan Lev3 Min Pressure
100 to 500 psig
250
3.ON
Fan Lev3 on Temperature
0 to 100 F
no Humidi-MiZer FIOP:
65
Humidi-MiZer FIOP:
88 (20)
68 (24)
68 (28)
LEGEND
FIOP
--- --- Factory---Installed Option
48/
50P
G
C
03
--
16