23
Filter Drier
Replace whenever refrigerant system is exposed to
atmosphere. Only use factory specified liquid--line filter
driers with working pressures no less than 650 psig. Do
not install a suction--line filter drier in liquid line. A
liquid--line filter drier designed for use with Puron
refrigerant is required on every unit.
Condenser--Fan Adjustment
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser--fan assembly (grille, motor, and
fan).
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 30.
5. Tighten setscrews.
6. Replace condenser--fan assembly.
Conduit
0.14 in + 0.0 / -0.03
C08448
Fig. 30 -- Condenser Fan Adjustment
Troubleshooting Cooling System
Refer to Table 6 for additional troubleshooting topics.
48H
C
Summary of Contents for 48HC*04-14
Page 94: ...94 APPENDIX IV WIRING DIAGRAMS C14007 Fig 80 48HC A04 A06 YAC Power Diagram 230 1 60 48HC ...
Page 96: ...96 APPENDIX IV WIRING DIAGRAMS C14013 Fig 82 48HC A04 A06 YAC Power Diagram 575 3 60 48HC ...
Page 97: ...97 APPENDIX IV WIRING DIAGRAMS C14018 48HC ...
Page 98: ...98 APPENDIX IV WIRING DIAGRAMS C14019 48HC ...
Page 99: ...99 APPENDIX IV WIRING DIAGRAMS C13484 Fig 83 48HC D08 D09 YAC Power Diagram 230 460 3 60 48HC ...
Page 100: ...100 APPENDIX IV WIRING DIAGRAMS C14024 Fig 84 48HC D08 D09 YAC Power Diagram 575 3 60 48HC ...
Page 101: ...101 APPENDIX IV WIRING DIAGRAMS C14027 Fig 85 48HC D12 YAC Power Diagram 230 460 3 60 48HC ...
Page 102: ...102 APPENDIX IV WIRING DIAGRAMS C14029 Fig 86 48HC D12 YAC Power Diagram 575 3 60 48HC ...
Page 104: ...104 APPENDIX IV WIRING DIAGRAMS C14032 Fig 88 48HC D14 YAC Power Diagram 230 460 3 60 48HC ...
Page 105: ...105 APPENDIX IV WIRING DIAGRAMS C12462 Fig 89 48HC D14 YAC Power Diagram 575 3 60 48HC ...
Page 123: ...123 APPENDIX IV WIRING DIAGRAMS C12690 Fig 107 PremierLink System Control Wiring Diagram 48HC ...
Page 125: ...125 APPENDIX IV WIRING DIAGRAMS C14034 Fig 109 RTU Open Wiring Diagram 48HC ...