55
factory with a supply--air temperature sensor and an
outdoor-- air temperature sensor. This allows for operation
of the EconoMi$er IV with outdoor air dry bulb
changeover control. Additional accessories can be added
to allow for different types of changeover control and
operation of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory
configured for outdoor dry bulb changeover control. The
outdoor air and supply air temperature sensors are
included as standard. For this control mode, the outdoor
temperature is compared to an adjustable setpoint selected
on the control. If the outdoor-air temperature is above the
setpoint, the EconoMi$er IV will adjust the outside air
dampers to minimum position. If the outdoor-air
temperature is below the setpoint, the position of the
outside air dampers will be controlled to provided free
cooling using outdoor air. When in this mode, the LED
next to the free cooling setpoint potentiometer will be on.
The changeover temperature setpoint is controlled by the
free cooling setpoint potentiometer located on the control.
See Fig. 68. The scale on the potentiometer is A, B, C,
and D. See Fig. 71 for the corresponding temperature
changeover values.
C06034
Fig. 68 -- EconoMi$er IV Controller Potentiometer
and LED Locations
LED ON
LED ON
LED ON
LED ON
LED OFF
19
18
LED OFF
LED OFF
LED OFF
17
16
15
14
13
12
11
10
9
40
45
50
55
60
65
70
75
80
85
90
95 100
DEGREES FAHRENHEIT
mA
D
C
B
A
C06035
Fig. 69 -- Outside Air Temperature Changeover
Setpoints
0
5
10
15
20
25
30
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
FLOW
IN
CUBIC
FEET
PER
MINUTE
(cfm)
C06031
Fig. 70 -- Outdoor--Air Damper Leakage
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional
accessory dry bulb sensor (p/n: CRTEMPSN002A00). The
accessory sensor must be mounted in the return airstream.
See Fig. 71. Wiring is provided in the EconoMi$er IV
wiring harness.
ECONOMI$ERIV
ECONOMI$ERIV
CONTROLLER
GROMMET
RETURN AIR
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
C07085
Fig. 71 -- Return Air Temperature or Enthalpy Sensor
Mounting Location
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower
temperature airstream is used for cooling. When using this
mode of changeover control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting. See Fig. 68.
48H
C
Summary of Contents for 48HC*04-14
Page 94: ...94 APPENDIX IV WIRING DIAGRAMS C14007 Fig 80 48HC A04 A06 YAC Power Diagram 230 1 60 48HC ...
Page 96: ...96 APPENDIX IV WIRING DIAGRAMS C14013 Fig 82 48HC A04 A06 YAC Power Diagram 575 3 60 48HC ...
Page 97: ...97 APPENDIX IV WIRING DIAGRAMS C14018 48HC ...
Page 98: ...98 APPENDIX IV WIRING DIAGRAMS C14019 48HC ...
Page 99: ...99 APPENDIX IV WIRING DIAGRAMS C13484 Fig 83 48HC D08 D09 YAC Power Diagram 230 460 3 60 48HC ...
Page 100: ...100 APPENDIX IV WIRING DIAGRAMS C14024 Fig 84 48HC D08 D09 YAC Power Diagram 575 3 60 48HC ...
Page 101: ...101 APPENDIX IV WIRING DIAGRAMS C14027 Fig 85 48HC D12 YAC Power Diagram 230 460 3 60 48HC ...
Page 102: ...102 APPENDIX IV WIRING DIAGRAMS C14029 Fig 86 48HC D12 YAC Power Diagram 575 3 60 48HC ...
Page 104: ...104 APPENDIX IV WIRING DIAGRAMS C14032 Fig 88 48HC D14 YAC Power Diagram 230 460 3 60 48HC ...
Page 105: ...105 APPENDIX IV WIRING DIAGRAMS C12462 Fig 89 48HC D14 YAC Power Diagram 575 3 60 48HC ...
Page 123: ...123 APPENDIX IV WIRING DIAGRAMS C12690 Fig 107 PremierLink System Control Wiring Diagram 48HC ...
Page 125: ...125 APPENDIX IV WIRING DIAGRAMS C14034 Fig 109 RTU Open Wiring Diagram 48HC ...