background image

1

48DU

Infinity

t

14 Single--Packaged Air Conditioner and

Gas Furnace System With Puron

®

(R--410A) Refrigerant

2 to 5 Nominal Tons (Sizes 024--060)

Installation Instructions

IMPORTANT

:

OAT sensor must be field installed. See

Accessory Installation for more details.

IMPORTANT

:

This Infinity

t

unit is designed for use with an

Infinity User Interface.
NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

Page

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECEIVING AND INSTALLATION

2--12

. . . . . . . . . . . . . . . .

Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identify Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Shipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ground Mount

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rig and Place Unit

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspection

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Use of Rigging Bracket

8

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Select and Install Ductwork

8

. . . . . . . . . . . . . . . . . . . . . . . . . .

Converting Horizontal Discharge Units to Downflow

(Vertical) Discharge Units

9

. . . . . . . . . . . . . . . . . . . . . . . . .

Provide for Condensate Disposal

10

. . . . . . . . . . . . . . . . . . . .

Install Flue Hood

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Install Gas Piping

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Install Electrical Connections

11

. . . . . . . . . . . . . . . . . . . . . . .

High--Voltage Connections

11

. . . . . . . . . . . . . . . . . . . . . . .

Routing Power Leads Into Unit

12

. . . . . . . . . . . . . . . . . . . .

Connecting Ground Lead to Ground Screw

12

. . . . . . . . . .

Routing Control Power Wires

12

. . . . . . . . . . . . . . . . . . . .

Accessory Installation

12

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 208--v Operation

12

. . . . . . . . . . . . .

PRE--START--UP

15

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START--UP

15--25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Unit Start--Up and Troubleshooting

15

. . . . . . . . . . . . . . . . . .

Sequence of Operation

19--24

. . . . . . . . . . . . . . . . . . . . . . . . .

Check for Refrigerant Leaks

24

. . . . . . . . . . . . . . . . . . . . . . . .

Start--Up Adjustments

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking Cooling and Heating Control Operation

25

. . . . .

Checking and Adjusting Refrigerant Charge

25

. . . . . . . . . .

Refrigerant Charge

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

No Charge

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Low Charge Cooling

25

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

To Use Cooling Charging Charts

25

. . . . . . . . . . . . . . . . . . .

Non--Communicating Emergency Cooling/Heating Mode

25

.

MAINTENANCE

27--29

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Filter

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Fan and Motor

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inducer Blower

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Limit Switch

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A05307

Fig. 1 -- Unit 48DU

Burner Ignition

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Main Burners

27

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inducer Pressure Switch

27

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, and Condensate Drain Pan

28

. . . .

Outdoor Fan

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Controls and Wiring

28

. . . . . . . . . . . . . . . . . . . . . .

Refrigerant Circuit

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Airflow

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure Switches

28

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss--of--Charge Switch

28

. . . . . . . . . . . . . . . . . . . . . . . . . . .

High--Pressure Switches

28

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Copeland Scroll Compressor (Puron

®

Refrigerant)

29

. . . . . . .

Refrigerant System

29

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant

29

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Oil

29

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Systems on Roofs with Synthetic Materials

29

. . .

Liquid--Line Filter Drier

29

. . . . . . . . . . . . . . . . . . . . . . . . .

Puron (R--410A) Refrigerant Charging

29

. . . . . . . . . . . . . .

TROUBLESHOOTING

29--31

. . . . . . . . . . . . . . . . . . . . . . . . . .

FINAL CHECKS

31

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE

31

. . . . . . . . . . . . . . . . . . . . . . .

START--UP CHECKLIST

35

. . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Installation and servicing of this equipment can be hazardous due to

mechanical and electrical components. Only trained and qualified

personnel should install, repair, or service this equipment.
Untrained personnel can perform basic maintenance functions, such

as cleaning and replacing air filters. All other operations must be
performed by trained service personnel. When working on this

equipment, observe precautions in the literature, on tags, and on
labels attached to or shipped with the unit and other safety

precautions that may apply.

Summary of Contents for 48DU Series

Page 1: ...Checking Cooling and Heating Control Operation 25 Checking and Adjusting Refrigerant Charge 25 Refrigerant Charge 25 No Charge 25 Low Charge Cooling 25 To Use Cooling Charging Charts 25 Non Communicat...

Page 2: ...w NOx units designed for California installations These models meet the California maximum oxides of nitrogen NOx emissions requirements of 40 nanograms joule or less as shipped from the factory and m...

Page 3: ...Support CTyp G E F G D E A05308 UNIT SIZE ODS CATALOG NUMBER A IN MM B IN MM C IN MM D IN MM E IN MM F IN MM G IN MM 024 030 CPRFCURB006A00 8 203 11 279 16 1 2 419 28 3 4 730 30 3 8 771 44 5 16 1126...

Page 4: ...4 A06323 Fig 5 48DU024 030 Unit Dimensions...

Page 5: ...5 A06324 Fig 6 48DU036 060 Unit Dimensions...

Page 6: ...OIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variable based on Comfort Roll back see User Interface i...

Page 7: ...e for high capacity type Air filter pressure drop for non standard filters must not exceed 0 08 in wg Step 3 Provide Clearances The required minimum service clearances are shown in Fig 5 and 6 Adequat...

Page 8: ...strip screws when re securing the unit If a screw is stripped replace the stripped one with a larger diameter screw included WARNING Rigging Lifting of Unit 1 Bend top of brackets down approximately...

Page 9: ...Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Contractors Association ACCA minimum installation standards for residential heating and air conditioning s...

Page 10: ...OUTLET C99013 Fig 9 Condensate Trap Step 8 Install Gas Piping The gas supply pipe enters the unit through the access hole provided The gas connection to the unit is made to the 1 2 in FPT gas inlet on...

Page 11: ...ot use a connector which has previously serviced another gas appliance WARNING 8 Check for gas leaks at the field installed and factory installed gas lines after all piping connections have been compl...

Page 12: ...HUMIDITY CONTROL COMFORT ROLLBACK ETC WILL BE LOST IF THE OAT IS NOT CONNECTED For detailed mounting instructions for the OAT sensor please refer to TSTATXXSEN01 B installation instructions catalog n...

Page 13: ...BLK GROUND LEAD SINGLE PHASE CONNECTIONS TO DISCONNECT PER NEC LEGEND NEC National Electrical Code Field Wiring Splice Connections NOTE Use copper wire only L1 L2 A06299 Fig 12 Line Power Connections...

Page 14: ...Supply fuse The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire I fother than 60 C wire is used or if length exceeds wire length in...

Page 15: ...orrectly positioned in fan orifice Top 1 3 of condenser fan blade should be within fan orifice venturi c Ensure fan hub is positioned correctly with respect to motor housing See Fig 23 d Make sure tha...

Page 16: ...can be replaced MOTOR TURNS SLOWLY 1 Low static pressure loading of blower while access panel is removed will cause blower to run slowly Particularly at low airflow requests This is normal do not ass...

Page 17: ...17 6 0 A06310 Fig 16 Wiring Schematic 48DU Single Phase 48DU...

Page 18: ...system defective switch or connections or inadequate combustion air supply flame roll out switch open STATUS CODE 34 IGNITION PROVING FAILURE Control will try three more times before lockout 14 occurs...

Page 19: ...rststageandsecondstagecoolingare satisfied the compressorwill shut off NOTE When two stage unit is operating at low stage system vapor suction pressure will be higher than a standard single stage syst...

Page 20: ...age Ther mal Cutout 72 Compressor voltage sensed then disappears while cooling or heat ing demand exists Possible causes are internal compressor over load trip or start relay not releasing if installe...

Page 21: ...nes what heating stage to run based on feedback from the UI If the UI is asking for low stage gas heat the ignition control will changetheinducerspeedtolow speedand keepthe gasvalve energized on low s...

Page 22: ...ate and clockwise in to increase input rate REGULATOR COVER SCREW PLASTIC ADJUST SCREW LOW STAGE GAS PRESSURE REGULATOR ADJUSTMENT MANIFOLD PRESSURE TAP INLET PRESSURE TAP ON OFF SWITCH REGULATOR SPRI...

Page 23: ...one revolution takes 84 sec and the heating value of the gas is 1050 Btu ft3 Proceed as follows a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90...

Page 24: ...oblem in the case of a gas component failure To initiate the component test procedure ensure that there arenoUIinputstothecontrol theABCDconnectorcan beremoved fromthe Infinitycontrol boardfor thisope...

Page 25: ...eading Indoor air CFM must be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to...

Page 26: ...578 41 39 36 30 384 108 103 98 88 2647 42 40 37 31 394 110 105 100 90 2716 44 41 38 32 404 112 107 102 92 2785 45 42 39 33 414 114 109 104 94 2854 46 43 40 34 424 116 111 106 96 2923 47 44 41 35 434 1...

Page 27: ...nsional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean cleanable type at least twice d...

Page 28: ...ly After inspecting the electrical controls and wiring replace all the panels Start the unit and observe at least one complete cooling cycle to ensure proper operation If discrepancies are observed in...

Page 29: ...performing any service that may risk exposure ofcompressor oil to the roof take appropriate precautions to protect roofing Procedures which risk oil leakage include but are not limited to compressor r...

Page 30: ...mand for compressor operation the contactor may be stuck closed or there is a wiring error The control will flash the appropriate fault code COMPRESSOR THERMAL CUTOUT If the control senses the compres...

Page 31: ...should fail low ambient cooling will not be allowed Defrost will occur at each time interval during heating operation but will terminate after 5 minutes If there is a thermistor out of range error de...

Page 32: ...h 520 psig low side retard S Use hoses with 750 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE oils S...

Page 33: ...operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size UI temperature set too low Reset UI setting Low refrigerant charge Locate leak repair...

Page 34: ...unit 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace fil...

Page 35: ...ESS III START UP ELECTRICAL SUPPLY VOLTAGE __________________________________ COMPRESSOR AMPS_________________________________ INDOOR EVAPORATOR FAN AMPS___________ TEMPERATURES OUTDOOR CONDENSER AIR...

Page 36: ...W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 48DU 2SI Replaces 48DU 1SI Print...