Fan Performance — 48PME28 — Horizontal Supply/Return Units
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
N6500
E
799
2.58
E
883
2.79
E
872
3.05
F
914
3.36
F
958
3.71
N7000
856
3.19
887
3.41
F
921
3.67
958
3.98
999
4.33
N7500
F
913
3.89
F
941
4.12
972
4.39
1006
4.69
1042
5.04
N8000
971
4.69
996
4.93
G
1024
5.20
G
1055
5.51
G
1088
5.86
N8500
G
1029
5.60
G
1052
5.85
1078
6.12
1106
6.44
1136
6.78
N9000
1087
6.62
1108
6.87
1132
7.16
1158
7.47
H
1185
7.82
N9500
1145
7.75
1165
8.02
H
1187
8.31
H
1211
8.63
1236
8.99
N10000
H
1203
9.01
H
1222
9.29
1243
9.59
1265
9.92
1288
10.28
N10500
1261
10.40
1279
10.69
1299
11.00
1319
11.34
1341
11.70
N11000
1320
11.93
1337
12.23
1355
12.55
1374
12.89
1394
13.26
N11500
1378
13.61
—
—
—
—
—
—
—
—
N12000
—
—
—
—
—
—
—
—
—
—
N12500
—
—
—
—
—
—
—
—
—
—
Airflow
(Cfm)
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
Rpm
Bhp
N6500
F
1005
4.12
G
1052
4.57
G
1100
5.06
G
1148
5.60
H
1195
6.17
N7000
G
1041
4.72
1084
5.16
1128
5.64
1172
6.17
1217
6.74
N7500
1080
5.43
1119
5.86
1160
6.33
H
1201
6.84
1242
7.40
N8000
1122
6.24
1158
6.66
H
1195
7.13
1233
7.63
1272
8.17
N8500
1167
7.16
H
1200
7.58
1234
8.04
1269
8.53
1304
9.06
N9000
H
1214
8.21
1244
8.62
1275
9.07
1308
9.56
1340
10.08
N9500
1262
9.37
1290
9.78
1319
10.23
1349
10.71
1379
11.23
N10000
1312
10.66
1338
11.08
1365
11.52
1392
12.00
—
—
N10500
1363
12.09
1387
12.51
—
—
—
—
—
—
N11000
—
—
—
—
—
—
—
—
—
—
N11500
—
—
—
—
—
—
—
—
—
—
N12000
—
—
—
—
—
—
—
—
—
—
N12500
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
- Brake Horsepower Input to Fan
Boldface
indicates field-supplied drive required.
NOTES
:
1. Motor drive ranges:
(E)
Low Range: 687-873 rpm, 5.75 Bhp
(F)
Mid‐Low Range: 805 to 1007 rpm, 5.75 Bhp
(G)
Mid‐High Range: 941 to 1176 rpm, 8.63 Bhp
(H)
High Range: 1014 to 1297 rpm, 11.50 Bhp
All other rpms require field-supplied drive.
2. See General Fan Performance Notes.
48/50PG and PM
Summary of Contents for 48/50PG C03-14
Page 31: ...31 C07009 Fig 18 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 32: ...32 C08077 Fig 19 Air Baffle Dimensions 48 50PM16 28 48 50PG and PM...
Page 56: ...56 C08549 Fig 25 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 57: ...57 C08550 Fig 26 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 62: ...62 C08471 Fig 31 Typical 48PM16 28 Control Schematic 48 50PG and PM...
Page 63: ...63 C08062 Fig 32 Typical 48PM16 28 with Humidi MiZert System Control Schematic 48 50PG and PM...
Page 64: ...64 C101251 Fig 33 Typical 50PM16 28 Control Schematic 48 50PG and PM...
Page 65: ...65 C08064 Fig 34 Typical 50PM16 28 with Humidi MiZert Control Schematic 48 50PG and PM...
Page 66: ...66 C10902 Fig 35 Typical 48 50PM16 28 Power Schematic 48 50PG and PM...
Page 67: ...67 C09213 Fig 36 Typical 48 50PM16 28 with Humidi MiZert System Power Schematic 48 50PG and PM...
Page 69: ...69 C08067 Fig 38 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 70: ...70 C101252 Fig 39 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...