11
Table 3 – Setting an Occupied Time Schedule — Weekdays Only for 7:30 to 22:30
DISPLAY
MENU
SUB‐SUB
MODE
KEYPAD
ENTRY
ITEM
DISPLAY
ITEM EXPANSION
COMMENT
TIMECLOCK
SCH.L
ENTER
Local Occupancy Schedule
PER.1
ENTER
OCC.1
Period Occupied Time
ENTER
00.00
Scrolling stops
ENTER
00.00
Hours Flash
07.00
Select 7
ENTER
07.00
Change accepted, minutes flash
07.30
Select 30
ENTER
07.30
Change accepted
ESCAPE
OCC.1
07.30
Period Occupied Time
Item/Value/Units scrolls again
UNC.1
00.00
Period Unoccupied Time
ENTER
00.00
Scrolling stops
ENTER
00.00
Hours Flash
22.00
Select 22
ENTER
22.00
Change accepted, minutes flash
22.30
Select 30
ENTER
22.30
Change accepted
ESCAPE
UNC.1
22.30
Period Unoccupied Time
Item/Value/Units scrolls again
MON.1
NO
Monday In Period
ENTER
NO
Scrolling stops
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
MON.1
YES
Monday In Period
Item/Value/Units scrolls again
TUE.1
NO
Tuesday In Period
ENTER
NO
Scrolling stops
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
TUE.1
YES
Tuesday In Period
Item/Value/Units scrolls again
WED.1
NO
Wednesday In Period
ENTER
NO
Scrolling stops
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
WED.1
YES
Wednesday In Period
Item/Value/Units scrolls again
THU.1
NO
Thursday In Period
ENTER
NO
Scrolling stops
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
THU.1
YES
Thursday In Period
Item/Value/Units scrolls again
FRI.1
NO
Friday In Period
ENTER
NO
Scrolling stops
YES
Select YES
ENTER
YES
Change accepted
ESCAPE
FRI.1
YES
Friday In Period
Item/Value/Units scrolls again
ESCAPE
ESCAPE
48/50PG and PM
Summary of Contents for 48/50PG C03-14
Page 31: ...31 C07009 Fig 18 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 32: ...32 C08077 Fig 19 Air Baffle Dimensions 48 50PM16 28 48 50PG and PM...
Page 56: ...56 C08549 Fig 25 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 57: ...57 C08550 Fig 26 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 62: ...62 C08471 Fig 31 Typical 48PM16 28 Control Schematic 48 50PG and PM...
Page 63: ...63 C08062 Fig 32 Typical 48PM16 28 with Humidi MiZert System Control Schematic 48 50PG and PM...
Page 64: ...64 C101251 Fig 33 Typical 50PM16 28 Control Schematic 48 50PG and PM...
Page 65: ...65 C08064 Fig 34 Typical 50PM16 28 with Humidi MiZert Control Schematic 48 50PG and PM...
Page 66: ...66 C10902 Fig 35 Typical 48 50PM16 28 Power Schematic 48 50PG and PM...
Page 67: ...67 C09213 Fig 36 Typical 48 50PM16 28 with Humidi MiZert System Power Schematic 48 50PG and PM...
Page 69: ...69 C08067 Fig 38 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 70: ...70 C101252 Fig 39 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...