96
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — RUN STATUS (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUBTABLE
CCN POINT
CCN
WRITE
STATUS
MENU
WRITE
STATUS
STRT
Component Starts
A1
Compressor A1 Starts
xxxxxx
ST_A1
forcible
A2
Compressor A2 Starts
xxxxxx
ST_A2
forcible
B1
Compressor B1 Starts
xxxxxx
ST_B1
forcible
C1
Compressor C1 Starts
xxxxxx
ST_C1
forcible
CCH
Crankcase Heat Starts
xxxxxx
ST_CCH
forcible
IDF
Indoor Fan Starts
xxxxxx
ST_IDF
forcible
OFC.1
Outdoor Fan 1 Starts
xxxxxx
ST_OFC_1
forcible
OFC.2
Outdoor Fan 2 Starts
xxxxxx
ST_OFC_2
forcible
OFC.3
Outdoor Fan 3 Starts
xxxxxx
ST_OFC_3
forcible
HT.1
Heat Stage 1 Starts
xxxxxx
ST_HTR_1
forcible
HT.2
Heat Stage 2 Starts
xxxxxx
ST_HTR_2
forcible
PE.1
Power Exhaust 1 Starts
xxxxxx
ST_PE_1
forcible
PE.2
Power Exhaust 2 Starts
xxxxxx
ST_PE_2
forcible
ALRM
Alarm Relay Starts
xxxxxx
ST_ALM
forcible
CRC
Reheat1 Valve Starts
xxxxxx
ST_CRC
forcible
RH2.A
Reheat2 Valve A Starts
xxxxxx
ST_RH2_A
forcible
RH2.B
Reheat2 Valve BC Starts
xxxxxx
ST_RH2_B
forcible
(ALRMDISP) =
CCN only)
ALRMDISP
Active Alarm 1 Code
xxx
ALMCODE1
Active Alarm 2 Code
xxx
ALMCODE2
Active Alarm 3 Code
xxx
ALMCODE3
Active Alarm 4 Code
xxx
ALMCODE4
Active Alarm 5 Code
xxx
ALMCODE5
Reset All Current Alarms
No/Yes
ALRESET
forcible
Reset Alarm History
No/Yes
ALHISCLR
forcible
(GENERIC =
CCN only)
GENERIC
up to 20 points
(LON_DATA =
CCN only)
LON_DATA
nviSpaceTemp
xxx.x
°F
NVI_SPT
Forcible
nviSetPoint
xxx.x
°F
NVI_SP
forcible
nvoSpaceTemp
xxx.x
°F
NVO_SPT
nvoUnitStatus.mode
xxxx
NVO_MODE
nvoUnitStatus.heat_out_p
xxx.x
%
NVO_HPRI
nvoUnitStatus.heat_out_s
xxx.x
%
NVO_HSEC
nvoUnitStatus.cool_out
xxx.x
%
NVO_COOL
nvoUnitStatus.econ_out
xxx.x
%
NVO_ECON
nvoUnitStatus.fan_out
xxx
%
NVO_FAN
nvoUnitStatus.in_alarm
xxx
NVO_ALRM
nviSetPtOffset
xxx.x
^F
NVI_SPTO
forcible
nviOutsideTemp
xxx.x
°F
NVI_OAT
forcible
nviOutsideRH
xxxx.x
%
NVI_OARH
forcible
nvoEffectSetPt
xxx.x
°F
NVO_EFSP
nvoOutsideTemp
xxxx.x
°F
NVO_OAT
nvoOutsideRH
xxx.x
%
NVO_OARH
nviSpaceRH
xxx.x
%
NVI_SPRH
forcible
nviCO2
xxxxx
NVI_CO2
forcible
nvoCO2
xxxxx
NVO_CO2
nvoTEMP1
xxx.x
°F
NVO_SAT
nvoTEMP2
xxx.x
°F
NVO_RAT
nviPCT1
xxx.x
%
NVI_RHSP
forcible
nvoPCT1
xxx.x
%
NVO_SPRH
nviDISCRETE1
Off/On
NVI_FSD
forcible
nviDISCRETE2
No/Yes
NVI_OCC
forcible
nviDISCRETE3
Off/On
NVI_IAQD
forcible
nvoDISCRETE1
Off/On
NVO_FSD
nvoDISCRETE2
No/Yes
NVO_OCC
nvoDISCRETE3
Off/On
NVO_IAQD
nciCO2Limit
xxxxx
NCI_CO2
forcible
nciSetPnts.occupied_cool
xxx.x
°F
NCI_OCSP
forcible
nciSetPnts.standby_cool
xxx.x
°F
NCI_SCSP
forcible
nciSetPnts.unoccupd_cool
xxx.x
°F
NCI_UCSP
forcible
nciSetPnts.occupied_heat
xxx.x
°F
NCI_OHSP
forcible
nciSetPnts.standby_heat
xxx.x
°F
NCI_SHSP
forcible
nciSetPnts.unoccupd_heat
xxx.x
°F
NCI_UHSP
forcible
48/50PG and PM
Summary of Contents for 48/50PG C03-14
Page 31: ...31 C07009 Fig 18 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Page 32: ...32 C08077 Fig 19 Air Baffle Dimensions 48 50PM16 28 48 50PG and PM...
Page 56: ...56 C08549 Fig 25 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 57: ...57 C08550 Fig 26 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Page 62: ...62 C08471 Fig 31 Typical 48PM16 28 Control Schematic 48 50PG and PM...
Page 63: ...63 C08062 Fig 32 Typical 48PM16 28 with Humidi MiZert System Control Schematic 48 50PG and PM...
Page 64: ...64 C101251 Fig 33 Typical 50PM16 28 Control Schematic 48 50PG and PM...
Page 65: ...65 C08064 Fig 34 Typical 50PM16 28 with Humidi MiZert Control Schematic 48 50PG and PM...
Page 66: ...66 C10902 Fig 35 Typical 48 50PM16 28 Power Schematic 48 50PG and PM...
Page 67: ...67 C09213 Fig 36 Typical 48 50PM16 28 with Humidi MiZert System Power Schematic 48 50PG and PM...
Page 69: ...69 C08067 Fig 38 48 50PM16 28 Component Arrangement 48 50PG and PM...
Page 70: ...70 C101252 Fig 39 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...