95
18.3.3.4 Voltage protection(ODU E5)
Outdoor unit low AC voltage protection(PC10)
Outdoor unit main control board DC bus high voltage protection(PC11)
Outdoor unit main control board DC bus high voltage protection /341 MCE error(PC12)
Voltage protection
Check the voltage of
outdoor unit power supply,
whether the voltage
between L(L1) and N (L2) is
about 220~240VAC
Check the power supply
Check whether the voltage
of IPM board P and N is
normal? DC277-356V for
18-27KBtu/h; DC277-410V
for 36-42KBtu/h
Replace bridge rectifiers,
and then check whether the
system can run normally
Replace IPM board, and
then check whether the
system can run normally
Replace outdoor main board
Yes
No
No
No
No
Yes
Trouble is solved
Yes
Yes
Summary of Contents for 42QHE09D8SH
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual ...
Page 21: ...18 4 5 6 Easy operation 4 5 7 Remote control and optional wired control method ...
Page 25: ...22 5 4 Console 16 Drain pipe 195 Hanging arm 700 600 210 N A ...
Page 29: ...25 6 Service Space unit mm 6 1 Four way cassette compact 6 2 Four way cassette super slim ...
Page 31: ...27 6 5 Under Ceiling 6 6 Hi wall Cool Easy 18C AG ...
Page 32: ...Specifications 7 Electrical Wiring Diagrams 7 1 Indoor unit A6 Duct type 7K 9K ...
Page 33: ...Specifications 12K 18K 24K ...
Page 34: ...Specifications Page 67 Compact Cassette type 7K 9K ...
Page 35: ...Specifications Page 68 12K ...
Page 36: ...Specifications Page 69 18K ...
Page 37: ...Specifications Page 69 24K ...
Page 38: ...Specifications Page 70 Wall mounted type 18C 7K 9K 12K 18K ...
Page 39: ...Specifications Page 71 18C 24K ...
Page 42: ...Specifications Page 81 21K 27K 16022000035910 ...
Page 44: ...Specifications Page 78 36k ...
Page 45: ...Specifications Page 79 42k ...
Page 55: ...Specifications 14K 18K s n o i s n e m i D 3 1 ...
Page 56: ...Specifications 21K 27K ...
Page 57: ...Specifications 28K 36K 42K ...
Page 81: ...83 EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 ...
Page 112: ......