Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit
connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out,
the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and 3-way
valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port..
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa. If
the meter does not indicate -0.1Mpa after pumping 30 minutes, it should be pumped 20 minutes more. If the
pressure can’t achieve -0.1Mpa after pumping 50 minutes, please check if there are some leakage points.
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm
that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas
coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a
little higher than the atmosphere pressure. Then remove the charge hose from the 3 way valve.
8) Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve.
(Indoor unit)
(Liquid side)
(Gas side)
Vacuum
pump
Vacuum
pump
Lo
Hi
Handle Hi
Two-way valve
Close
Manifold valve
Compound meter
Pressure
gauge
-0.1MPa
Handle Lo
Charge hose
Charge hose
(Outdoor unit)
Close
Three-way valve
Summary of Contents for 42QHE09D8SH
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual ...
Page 21: ...18 4 5 6 Easy operation 4 5 7 Remote control and optional wired control method ...
Page 25: ...22 5 4 Console 16 Drain pipe 195 Hanging arm 700 600 210 N A ...
Page 29: ...25 6 Service Space unit mm 6 1 Four way cassette compact 6 2 Four way cassette super slim ...
Page 31: ...27 6 5 Under Ceiling 6 6 Hi wall Cool Easy 18C AG ...
Page 32: ...Specifications 7 Electrical Wiring Diagrams 7 1 Indoor unit A6 Duct type 7K 9K ...
Page 33: ...Specifications 12K 18K 24K ...
Page 34: ...Specifications Page 67 Compact Cassette type 7K 9K ...
Page 35: ...Specifications Page 68 12K ...
Page 36: ...Specifications Page 69 18K ...
Page 37: ...Specifications Page 69 24K ...
Page 38: ...Specifications Page 70 Wall mounted type 18C 7K 9K 12K 18K ...
Page 39: ...Specifications Page 71 18C 24K ...
Page 42: ...Specifications Page 81 21K 27K 16022000035910 ...
Page 44: ...Specifications Page 78 36k ...
Page 45: ...Specifications Page 79 42k ...
Page 55: ...Specifications 14K 18K s n o i s n e m i D 3 1 ...
Page 56: ...Specifications 21K 27K ...
Page 57: ...Specifications 28K 36K 42K ...
Page 81: ...83 EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 ...
Page 112: ......