Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s service port.
3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa.
4). Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge
needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the vacuum pump.
Summary of Contents for 42QHE09D8SH
Page 1: ...SUPER INVERTER SERIES MULTI TYPE Service Manual ...
Page 21: ...18 4 5 6 Easy operation 4 5 7 Remote control and optional wired control method ...
Page 25: ...22 5 4 Console 16 Drain pipe 195 Hanging arm 700 600 210 N A ...
Page 29: ...25 6 Service Space unit mm 6 1 Four way cassette compact 6 2 Four way cassette super slim ...
Page 31: ...27 6 5 Under Ceiling 6 6 Hi wall Cool Easy 18C AG ...
Page 32: ...Specifications 7 Electrical Wiring Diagrams 7 1 Indoor unit A6 Duct type 7K 9K ...
Page 33: ...Specifications 12K 18K 24K ...
Page 34: ...Specifications Page 67 Compact Cassette type 7K 9K ...
Page 35: ...Specifications Page 68 12K ...
Page 36: ...Specifications Page 69 18K ...
Page 37: ...Specifications Page 69 24K ...
Page 38: ...Specifications Page 70 Wall mounted type 18C 7K 9K 12K 18K ...
Page 39: ...Specifications Page 71 18C 24K ...
Page 42: ...Specifications Page 81 21K 27K 16022000035910 ...
Page 44: ...Specifications Page 78 36k ...
Page 45: ...Specifications Page 79 42k ...
Page 55: ...Specifications 14K 18K s n o i s n e m i D 3 1 ...
Page 56: ...Specifications 21K 27K ...
Page 57: ...Specifications 28K 36K 42K ...
Page 81: ...83 EC 50 Open or short circuit of outdoor unit temperature sensor T3 T4 T5 ...
Page 112: ......