background image

3 - INSTALLATION OF THE UNIT

3.1 - Installing the unit in the false ceiling

The positioning of the unit must not create an obstacle that may 

lead to an unequal distribution and/or return flow of the air. The 

ceiling  must  be  sufficiently  even  to  allow  a  simple  installation 

without danger from the unit. The supporting structure must be 

able to carry the unit weight and prevent deformation, breaks or 

vibrations during operation.

INSTALLATION  PRECAUTIONS:  During  the  installation 

process, remove all debris and construction material from 

the ducts to prevent any damage to the unit.

3.2 - Installation procedure

 

-

Position the unit close to where it is to be installed in the 

ceiling void or under the floor. For installation in a false ceiling 

use  a  hydraulic  lift  and  a  folding  ladder  to  make  the  task 

easier (Fig. 6).

 

-

Underfloor installation: install the adjustable rubber feet to 

the unit. These feet are available as an accessory. Please 

contact your local Carrier contact.

 

-

Check that the clearances around the unit are sufficient to 

allow easy maintenance. Please refer to the diagram that 

shows the service clearances.

 

-

Mark the position of the threaded hangers on the ceiling. If 

several  units  need  to  be  installed,  it  may  be  advisable  to 

produce a drilling template (see Fig. 2). The method of fixing 

the threaded hangers (not supplied by Carrier) depends on 

the ceiling type (maximum diameter of the threaded hangers 

is 8 mm). Once the threaded hangers are fixed to the ceiling, 

tighten the first nuts.

WARNING: When moving the units, do not use water pipes, 

condensate drain pan, valves or flexible pipes to lift them. 

Lift the unit and align it on the threaded hangers, insert the second 

nuts and tighten them slightly.

NOTE: At this point do not tighten the nuts fully and do not 

clamp the unit up to the ceiling (leave a space between the 

ceiling and the unit). The nuts will be adjusted finally, when 

the unit has been connected to the pipework and ducts and 

levelled.

Level the unit (Figs. 7 and 8)

Adjust the hanger nuts so that the unit is inclined 0.5% towards 

the condensate drain pan. In the other direction (air flow direction) 

the unit must be perfectly level (Fig. 8). 
Condensate drain pipe (Fig. 9): Use a flexible pipe with an inside 

diameter of 16 mm and provide a constant fall of 20 mm/m over 

the whole horizontal pipe run. Install a 50 mm (minimum) siphon 

to prevent gases and odours from flowing back into the ceiling 

void.
If several units are connected to a common collector, a device 

must be installed (Fig. 10). Before operating the unit, ensure that 

the water flows into the internal condensate drain pan by pouring 

some water into it. If problems are detected, check the drain pipe 

slope and look for possible obstructions. In all cases the connection 

duct(s)  at  the  unit  outlet  must  be  insulated  to  prevent  any 

condensate formation on the walls. 

NOTE: The pressure losses of these ducts must be compatible 

with the unit performance. The duct must be as smooth as 

possible. Avoid sharp bends. Check that there are no leaks 

or kinks, and that there is no dirt or installation debris inside 

the ducts. Debris within the ducts might damage the fan wheel 

and the damper in the air diffusers.

When installation is complete - i.e. when the 42BJ is attached to 

the ceiling, air ducts are complete, water manifolds are in position 

with  stop  valves  ready  on  the  connection  stubs,  and  electrical 

installation is prepared - then connect the water pipes (Carrier 

recommends the use of flexible water pipes that can be supplied 

as  an  accessory).  Each  flexible  pipe  has  a  1/2”  gas  screw 

connector, depending on the model. Ensure that a gasket (not 

supplied by Carrier) is installed between the screw connector and 

the stop valve.
When all units are installed, open the stop valves on the manifolds, 

bleed and then pressurize the circuits. To bleed the coils, remove 

the plastic plugs on the coil access door and then slightly undo 

the bleed screws with a screwdriver. Close the valve firmly when 

all air has escaped.

NOTE: Do not switch on the power until all connections are 

made and earthed.

3.3 - Remocal procedure

Switch off the unit power supply at the isolator provided for 

the purpose during installation (isolator not supplied by 

Carrier).

 

-

Disconnect the power supply and connection cables.

 

-

Close the isolating valves on the manifolds.

 

-

Disconnect the flexible water pipes by unscrewing the gas 

connectors. 

WARNING: Since the flexible water pipes do not have drain 

valves, a receiver must be provided to allow the cooling coil 

to be drained.

 

-

Disconnect the supply and return air ducts.

 

-

Disconnect  the  flexible  condensate  drain  pipe.  Drain  the 

siphon into a suitable vessel.

 

-

Support the unit lightly and release it by unscrewing the four 

nuts on the threaded hangers. Lower the unit carefully.

10

Summary of Contents for 42BJ ULTRA

Page 1: ...I N S TA L L AT I O N I N S T R U C T I O N S Original document INDIVIDUAL COMFORT MODULE FOR VARIABLE AIR VOLUME SYSTEMS 42BJ MCI LEC Sizes 1 9 2 9 4 9 ...

Page 2: ...2 ...

Page 3: ...n conditions 9 2 4 Caution for the control of the 42BJ ICM LEC 9 2 5 Regulations 9 3 INSTALLATION OF THE UNIT 10 3 1 Installing the unit in the false ceiling 10 3 2 Installation procedure 10 3 3 Remocal procedure 10 4 COMPONENTS 11 4 1 Fan motor assembly 11 4 2 Water coil 11 4 3 Duct connection spigots 11 4 4 Optional air filter and filter access air filter replacement 11 4 5 Constant volume fresh...

Page 4: ...B C D E F G H I 4 ...

Page 5: ...m m 50 mm l s m3 h A B MR60 17 60 4 4 4 4 MR75 21 75 4 3 4 3 MR85 24 85 3 3 3 2 MR90 25 90 3 2 2 2 MR100 28 100 2 1 2 1 MR105 29 105 2 1 1 1 MR110 31 110 1 1 1 1 MR120 33 120 3 3 MR130 36 130 2 1 MR140 39 140 1 1 MR160 44 160 L M N O 5 ...

Page 6: ... A 2 wV In Out In Out Cold Hot Ø 16 61 75 75 10 5 4 Ø 1 2 gas 25 82 5 69 188 A 3 wV In 42BJ A 1 9 151 mm 2 9 190 mm 42BJ MCI LEC 4 9 Out Ø 16 75 61 4 Ø 1 2 gas 163 5 192 225 69 2 wV In In Out Cold Hot Out Ø 16 75 61 4 Ø 1 2 gas 163 5 192 62 5 69 3 wV In In Out Cold Hot 6 ...

Page 7: ...g device for installation in a false ceiling H I Levelling the unit J Condensate drain pipe K Several units connected to one condensate collector L Fresh air controller modification M Fan motor assembly removal 12a Door 12b Locking screw 12C Fan fixing screw N Electric heater removal O Underfloor installation P Coil water inlet outlet positions sizes 1 9 and 4 9 In Water in Out Water out Hot Hot w...

Page 8: ...acteria and chemicals in order to avoid problems due to corrosion and scaling The water circuit must include all the necessary elements for the treatment of the water filters additives intermediate exchangers purges drains isolating valves etc according to the analysis results The results must be in accordance with the values shown below Total hardness in mmol l 1 mmol l 1 5 Chloride CL 10 mg litre...

Page 9: ...rown green yellow and its cross section and type must comply with the specifications set out by the applicable EN or IEC standard Refer to the selection sheet or the name plate to determine the maximum input current These devices are not supplied by Carrier In general terms the following rules must be applied Upstream over voltage protection Unit without electric heater T2A Unit with electric heat...

Page 10: ... over the whole horizontal pipe run Install a 50 mm minimum siphon to prevent gases and odours from flowing back into the ceiling void If several units are connected to a common collector a device must be installed Fig 10 Before operating the unit ensure that the water flows into the internal condensate drain pan by pouring some water into it If problems are detected check the drain pipe slope and l...

Page 11: ...d all air from the coil during refilling ATTENTION It is advisable to tighten the valve body to the coils with caution 15 N m is sufficient to ensure they are not damaged 4 2 2 Coil inlet outlet positions Fig 15 Water inlets outlets sizes 1 9 2 9 Water inlets outlets size 4 9 ATTENTION Carefully observe the direction indicated by the arrow on the valves based on the connection side and the valve typ...

Page 12: ...e actuators must be connected to the power supply to open the valves via a command from the wall thermostats or from the BMS 4 6 2 Actuator replacement procedure The actuators on both the chilled water and the hot water valves may be replaced if either develops a fault Disconnect the power supply to the unit before carrying out any work on a unit Disconnect the actuator power supply cable equipped...

Page 13: ...umeric controller 4 10 Adjustable feet accessories for installation in a false floor void 4 10 1 Introduction An ICM may be installed in a floor void Adjustable feet with built in vibration absorbers are available as accessories for installation on site For further information please contact your local Carrier representative 4 10 2 Procedure for fitting see Figs 14 and 15 a Install angle bracket 1 u...

Page 14: ... high pressure PTC 4 wired stages Digit 14 F F5 access from below G F5 side access H F5 access from above K F6 access from below L F6 side access M F6 access from above S Activated carbon filters UVPCO access from below T Activated carbon filters UVPCO side access U Activated carbon filters UVPCO access from above Digit 15 None A 125 mm Ø fresh air spigot only B 8 3 l s 30 m3 h C 16 6 44 4 l s 21 ...

Page 15: ...15 ...

Page 16: ...7 2021 replaces No 14281 11 2011 The manufacturer reserves the right to modify the product specifications without prior notice Manufacturer Carrier S C S Rte de Thil 01120 Montluel France Printed in the European Union ...

Reviews: