9.2 Electrical heaters

-  The auxiliary electrical heaters are ready for operation in two 

power stages.    

 

-  The  electrical  heaters  acquired  with  the  unit  will  be 

incorporated to it modifying the electric panel in the factory, 
so that it is compatible with the electronic control.

-  The  electrical  heaters  requested  for  units  already  shipped 

will be sent in a kit, and the installer will need to assemble 
the  elements  required  for  the  operation  of  the  unit  and  for 
compliance with the legal regulations that are applied to the 
modifi ed unit with regard to safety.

Models 90 to 360

In these models, the connection is made at the fan outlet:

-  In models 90 to 120 each of the rows of electrical heaters has 

an output of 1 kW. As from model 160, the output of each row 
will be 2 or 3 kW according to the total output.

-  In models with two supply fan outlets (two frames), as well as 

in the case of 1 supply outlet with 2 rails, the electrical heaters 
are  distributed  as  symmetrically  as  possible  between  both 
frames.

Rail

40ZS/ZF

Total output (kW)

Dimensions (mm)

A

B

C

90 / 100 / 120 
(1 supply outlet)

6 / 9 (1 row)

150

482

443

12 (2 rows)

262

482

443

160 / 180 
(1 supply outlet)

12 / 15 / 18 (1 row)

189

1.142

443

182 / 200 / 240 
(2 supply outlet)

15 / 18 (1 row)

189

1.142

443

24 / 30 / 36 (2 rows)

297

1.142

443

320 / 360 
(2 supply outlet)

15 / 18 / 24 / 30 / 36 (1 row)

189

1.142

443

Frame  for  assembly  of  the  auxiliary  heater  in  the  supply 
fan outlet:

To access the electrical heaters , the 2 screws that fasten the 
frame side panel must be unscrewed as shown in the following 
image:

In order to remove the 
electrical  heaters  the 
power  supply  cables 
must be disconnected 
f r o m   t h e   t e r m i n a l 
board  and  the  hose 
taken out.

Hose

Electrical 

heaters

Then,  unscrew  the  screw  that  fastens  the  electrical  heaters’ 
frame and take out by the rail, as shown in the following images.

Safety

thermistors

9 - OPTIONS

Note:

 in models with centrifugal return fan it is not possible to 

assemble electrical heaters with outputs of 30 and 36 kW.

Access for maintenance:

The  frame  has  access  designed  from  the  right  side  for 
maintenance.  In  the  case  of  2  frames  (2  supply  outlets)  are 
placed symmetrically so that the electrical heaters can be taken 
out without problems, that is, one will be accessed from the right 
and the other one from the left.

Access panel

Summary of Contents for 40ZF Series

Page 1: ...Nominal cooling capacity 20 135 kW Nominal heating capacity 20 145 kW Indoor units INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Translation of the original document 80259...

Page 2: ...SSIONING 9 7 1 Electrical connections 9 7 2 Checks in the centrifugal fans 9 7 3 Checks in plug fans optional 10 7 4 Air ducts connections 11 7 5 Condensate drain connection 11 8 SAFETY ELEMENTS 12 9...

Page 3: ...ak to atmospheric pressure the liquid phase evaporates The resulting vapours are still hazardous because they are heavier than air and can force the latter out of the machine rooms If refrigerant is a...

Page 4: ...11 I MS221 I R N R N MC111 N E R I R MC011 MC021 N E R R I N N E E MC001 I I 40ZS ZF 420 to 600 assemblies with mixing box raised view N E MC101 R I I I I Designation 1 Rear Return 2 Top 3 Right hand...

Page 5: ...t causing damage to the units or to workers These slings will be hooked to the two grips screwed on each crossbar in models 420 to 600 Make sure that the unit is protected from contact with the hooks...

Page 6: ...0 705 1 044 MC0 1 088 1 350 660 1 224 MC1 1 148 1 350 930 1 697 40ZS ZF MS module Centre of gravity mm Weight kg X Y Z 90 100 120 Montajes 111 116 413 314 411 114 113 311 121 126 423 324 421 124 123 3...

Page 7: ...ade With the help of the crane or the forklift truck the unit will be raised to a su cient height that the silent blocks can be screwed into its base The 4 silent blocks of the corners must remain obl...

Page 8: ...600 1 300 2 061 40ZS ZF 90 to 360 40ZS ZF 420 to 600 6 3 Anchorage for silent blocks 6 4 Recommended service clearance for unit start up and maintenance operations mm 1000 1000 500 1700 500 1000 A 500...

Page 9: ...fans Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check the operation conditions pressures ows and consumptions The over...

Page 10: ...entrifugal motorfans are coupled through pulleys and belts In these fans the following must be taken into consideration Pulley alignment The pulleys must be on the same plane so it is important to che...

Page 11: ...G Models 90 to 360 These indoor units are equipped with a condensate drain pan with a bronze gas threaded 3 4 M drain junction Condensate drain CONNECT SIPHON METTRE SIPHON PONER SIFON V220014 7 5 Con...

Page 12: ...nsidered when selecting fans the pressure drop graphs in the options can be seen in the technical brochure 9 1 Mixing box In models 90 to 360 of the 40ZS ZF unit the mixing box is a separate module Th...

Page 13: ...imensions mm A B C 90 100 120 1 supply outlet 6 9 1 row 150 482 443 12 2 rows 262 482 443 160 180 1 supply outlet 12 15 18 1 row 189 1 142 443 182 200 240 2 supply outlet 15 18 1 row 189 1 142 443 24...

Page 14: ...to connect the hose to the electric power supply If it is not possible to perform the previous step the distance between holes as well as the frame dimensions are displayed in the following schemes S...

Page 15: ...se frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the four M4 screws included in the kit The height of the frame on the support will de...

Page 16: ...l in the technical brochure of this series Water outlet Water inlet Models 40ZS ZF 90 to 360 Recomendations Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Page 17: ...re assembled over a sheet steel pro le Models 40ZS ZF 90 to 360 Modelos 40ZS ZF 420 to 600 Opacimetric filters Gravimetric filters Sheet profile Tab for displacement of gravimetric filters Tab for dis...

Page 18: ...oise we recommend the use of noise dampening headgear Caution Before intervening in the unit cut o main power 10 1 General recommendations Do not lean on the unit A platform must be used to work on a...

Page 19: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Page 20: ...Order No 10259 12 2020 Supersedes order No 07 2019 Manufactured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: