7.4 Air ducts connections

The air supply and return ducts must be calculated in accordance 
with the rated fl ow and the unit’s available pressure (refer to the 
technical brochure of this series). 

The  duct  calculation  and  design  must  be  made  by  qualifi ed 
technical personnel. 

It  is  advisable  to  take  into  consideration  the  following 
recommendations:

-  Curves  in  the  fan  supply  outlet(s)  must  be  avoided.  It  is 

recommendable to have a straight section of duct measuring 
approximately 1 metre. If it is not possible, they must be as 
smooth as possible, using indoor defl ectors when the duct is 
of large dimensions.

-  When  making  the  ducts,  direction  sharp  changes  must  be 

avoided since they can generate occasional pressure drops, 
which aff ect the available pressure and the fl ow. The location 
of discharge and aspiration grilles must be studied carefully to 
avoid the air recirculation and the transmission and generation 
of noises to the interior.

-  Flexible connections must be made between the ducts and 

the unit that avoid the noise and vibration transmission.

-  No  matter  the  type  of  ducts  type  to  use,  these  must  be 

insulated and not be composed of materials that propagate 
fi re nor expel toxic gases in the event of a fi re. The internal 
surfaces must be smooth and should not pollute the air that 
circulates within them. In any case, the eff ective legislation 
about this issue must be respected. 

7 - CHECKING BEFORE COMMISSIONING

Models 90 to 360

These  indoor  units  are  equipped  with  a 
condensate drain pan, with a bronze, gas 
threaded 3/4” M drain junction.

Condensate drain

CONNECT SIPHON

METTRE SIPHON

PONER SIFON

V220014

7.5 Condensate drain connection

Caution:

 These units are designed to be connected to 

a duct network. In the event that the outlet fan of the 
indoor  circuit  is  accessible  from  a  particular  point  in 
the duct network, the installer must install a protection 
mesh in the discharge as per the current regulation.

Siphon installation norms

All water drain tubes must be provided with a siphon to avoid 
bad smell and water spills. 

Pan in overpressure: 

It’s installed to avoid the access through the drain piping of bad 
smells.

Pan in underpressure: 

Besides the above application, water must be suctioned from 
the pan because of the depression with respect to the motorfan 
assembly.

-  Perform  the  siphon  assembly  as  per  the  scheme  of  the 

attached starting diagram:

•  For  the  correct  siphon  design,  the  “A”  height  must  be  at 

least twice that of the underpressure (mm.w.c) where the 
condensate pan is placed.

•  Check that the condensate outlet is not clogged.

•  The drain piping must be slightly sloped to ease circulation 

towards the drain.

•  The original diameter of the piping must be respected. No 

reduction can be made.

Check the watertightness of the connection.

Condensate drain

Models 420 to 600

These  indoor  units  are  equipped  with  a 
condensate drain pan, with a bronze, gas 
threaded 1 1/4” M drain junction.

CONNECT SIPHON

METTRE SIPHON

PONER SIFON

V220014

A

Condensates pan 

in depression

A

Siphon drain

Slight slope

5/1000

To drainage

Summary of Contents for 40ZF Series

Page 1: ...Nominal cooling capacity 20 135 kW Nominal heating capacity 20 145 kW Indoor units INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Translation of the original document 80259...

Page 2: ...SSIONING 9 7 1 Electrical connections 9 7 2 Checks in the centrifugal fans 9 7 3 Checks in plug fans optional 10 7 4 Air ducts connections 11 7 5 Condensate drain connection 11 8 SAFETY ELEMENTS 12 9...

Page 3: ...ak to atmospheric pressure the liquid phase evaporates The resulting vapours are still hazardous because they are heavier than air and can force the latter out of the machine rooms If refrigerant is a...

Page 4: ...11 I MS221 I R N R N MC111 N E R I R MC011 MC021 N E R R I N N E E MC001 I I 40ZS ZF 420 to 600 assemblies with mixing box raised view N E MC101 R I I I I Designation 1 Rear Return 2 Top 3 Right hand...

Page 5: ...t causing damage to the units or to workers These slings will be hooked to the two grips screwed on each crossbar in models 420 to 600 Make sure that the unit is protected from contact with the hooks...

Page 6: ...0 705 1 044 MC0 1 088 1 350 660 1 224 MC1 1 148 1 350 930 1 697 40ZS ZF MS module Centre of gravity mm Weight kg X Y Z 90 100 120 Montajes 111 116 413 314 411 114 113 311 121 126 423 324 421 124 123 3...

Page 7: ...ade With the help of the crane or the forklift truck the unit will be raised to a su cient height that the silent blocks can be screwed into its base The 4 silent blocks of the corners must remain obl...

Page 8: ...600 1 300 2 061 40ZS ZF 90 to 360 40ZS ZF 420 to 600 6 3 Anchorage for silent blocks 6 4 Recommended service clearance for unit start up and maintenance operations mm 1000 1000 500 1700 500 1000 A 500...

Page 9: ...fans Before commissioning check the blade rotation direction and that the axis turns without strokes nor vibrations Once running check the operation conditions pressures ows and consumptions The over...

Page 10: ...entrifugal motorfans are coupled through pulleys and belts In these fans the following must be taken into consideration Pulley alignment The pulleys must be on the same plane so it is important to che...

Page 11: ...G Models 90 to 360 These indoor units are equipped with a condensate drain pan with a bronze gas threaded 3 4 M drain junction Condensate drain CONNECT SIPHON METTRE SIPHON PONER SIFON V220014 7 5 Con...

Page 12: ...nsidered when selecting fans the pressure drop graphs in the options can be seen in the technical brochure 9 1 Mixing box In models 90 to 360 of the 40ZS ZF unit the mixing box is a separate module Th...

Page 13: ...imensions mm A B C 90 100 120 1 supply outlet 6 9 1 row 150 482 443 12 2 rows 262 482 443 160 180 1 supply outlet 12 15 18 1 row 189 1 142 443 182 200 240 2 supply outlet 15 18 1 row 189 1 142 443 24...

Page 14: ...to connect the hose to the electric power supply If it is not possible to perform the previous step the distance between holes as well as the frame dimensions are displayed in the following schemes S...

Page 15: ...se frames to the unit four supports are provided In the case of 2 frames screw each one of them to 2 supports with the four M4 screws included in the kit The height of the frame on the support will de...

Page 16: ...l in the technical brochure of this series Water outlet Water inlet Models 40ZS ZF 90 to 360 Recomendations Coil lling The coil lling must be made with the bleeder valve open until water runs through...

Page 17: ...re assembled over a sheet steel pro le Models 40ZS ZF 90 to 360 Modelos 40ZS ZF 420 to 600 Opacimetric filters Gravimetric filters Sheet profile Tab for displacement of gravimetric filters Tab for dis...

Page 18: ...oise we recommend the use of noise dampening headgear Caution Before intervening in the unit cut o main power 10 1 General recommendations Do not lean on the unit A platform must be used to work on a...

Page 19: ...ecovered for treatment Refrigerant Energy transfer uid depending on the installation water glycol water mix Compressor oil Important In order to recycle these units follow the stipulations of Directiv...

Page 20: ...Order No 10259 12 2020 Supersedes order No 07 2019 Manufactured for CARRIER in Spain Manufacturer reserves the right to change any product specifications without notice Printed in the European Union...

Reviews: