background image

10

1.

Choose “Dry contacts” on the

 

“Advanced Information”

interface to display status of unit and dry contact outputs.

2.

Touch the      or       icon to switch between IDUs.

SERVICE MENU SETTINGS

Service menu password — 

1.

Choose “Service” on the “Menu” interface

.

2.

Enter the password to access the settings. The default
password is 0000.

3.

Touch the Edit icon to access password settings.

4.

Slide the submenu to view more options.

5.

Enter the correct password. The sub-options under
Service settings are displayed.

See Table 7 and the following sections for details on

 

additional Service Menu settings.

Setting r

oom temp location

 — 

Select

 

“Room temp

location” setting on the “Service” interface.

Fig. 35 —Query Dry Contact Status

Fig. 36 —Service Menu Password Entry

Fig. 37 —Room temp location

The  room  temperature  location  can  be  set  to  Indoor  unit  or

 

Wired remote control as required. The default setting is Wired

 

remote control.

Room temp sensor offset — 

Select

 

“Room temp

 

sensor offset” setting on the “Service” interface.

Fig. 38 —Room temp sensor offset

The Room temp sensor offset sets the temperature compen-
sation value for the wired controller. The default value is 0

°

F.

Setpoint limit — 

Select

 

“Setpoint limit” setting on the

 

“Service” interface.

Fig. 39 —Setpoint limit

The  setpoint  limit  can  set  the  upper  limit  of  the  temperature

 

range to heating and the lower limit to cooling. The default is

 

86

°

F for heating and 50

°

F for cooling.

                 

Fig. 34 —Error Code/Address Field

 

Querying dry contact status  — 

Summary of Contents for 40VM Series

Page 1: ...sult in severe personal injury or death WARNING signifies hazards that could result in personal injury or death CAUTION is used to identify unsafe practices Table 2 Wired Controller Accessory Usage NA...

Page 2: ...he central controller locks the IDU function and the wired controller cannot use the corresponding functions of the IDU 16 Schedule Turns on when the weekly schedule is available on the wired controll...

Page 3: ...3 DIMENSIONAL DRAWING 7 1 4 4 7 8 1 1 8 Front View Side View Rear View 2 1 4 3 1 8 Fig 2 Dimensions Note All dimensions are shown in inches...

Page 4: ...indoor units see Fig 4 2 Connect field provided 24VAC power to R and C terminals 1 Remove back cover from controller as shown in Figure 5 2 Cut a hole in the wall for the 2 wire bundles Run the wires...

Page 5: ...is turned on as shown in Figure 10 Touch the corresponding fan speed text or the icon to set the fan speed See Figure 12 Fig 8 Snap controller into place Push WALL Fig 9 Turn screen on Fig 10 On Off s...

Page 6: ...E AND TIME Used to configure date and time settings and corrections DAYLIGHT SAVINGS TIME Used to adjust the clock in observance of daylight savings time ROOM TEMP Used to set display room temperature...

Page 7: ...Reset to reset all the scheduled tasks Holiday settings 1 Touch the icon from the Setting Schedule screen Figure 20 to access Holiday settings Touch to create a new Holiday Touch Edit to adjust the ex...

Page 8: ...ose Daylight savings time on the Menu interface 2 Turn the Daylight savings time ON OFF 3 Touch the Edit icon 4 Slide the corresponding items to set the start date and end date respectively 5 Touch th...

Page 9: ...rds Touch the Delete icon to delete all the error messages It displays the unit address 0 63 for indoor unit and 128 for outdoor unit and the related error code An address is not displayed when the wi...

Page 10: ...tion setting on the Service interface Fig 35 Query Dry Contact Status Fig 36 Service Menu Password Entry Fig 37 Room temp location The room temperature location can be set to Indoor unit or Wired remo...

Page 11: ...below this setting Default setting is 68F Fig 43 Thermo Off Fan Speed This determines IDU fan behavior when the zone is satisfied thermo off for both heating and cooling mode For cooling mode the defa...

Page 12: ...tal Heat Aux Heat Status These settings are used when the IDU is controlling a field provided auxiliary heat source via its ACB interface contact output Turning Aux Heat Status on enables this functio...

Page 13: ...hedules room temperature display etc Reset setting 1 Choose Reset setting on the Service interface 2 Touch the Reset icon to reset 3 Touch the YES icon to confirm the operation Fig 52 Firmware Update...

Page 14: ...tic pressure of the DC fan 0 0 in WC default 1 0 04 in WC 2 0 08 in WC 3 0 12 in WC 4 0 16 in WC 5 0 20 in WC 6 0 24 in WC 7 0 28 in WC 8 0 32 in WC 9 0 36 in WC 10 0 40 in WC 11 0 44 in WC 12 0 48 in...

Reviews: