background image

23

START--UP

Before starting unit, check the following and correct as

necessary:

S

Is unit solidly supported?

S

Is fan adjusted for speed and pulley alignment?

S

Are pulleys, motor, and bearings securely mounted?

S

Are there any loose parts that will rattle or vibrate?

S

Is condensate drain pan pitched for correct drainage?

S

Are coil baffle plates tight against coil to prevent air
bypass?

S

Are all panels securely fastened?

S

Are all electrical connections correct and tight?

40RUA and 40RUQ ONLY —

S

Is TXV bulb located on suction tube per Fig. 21?

S

Is the capillary tube to the bulb free of kinks and not
subject to pinching?

S

Is the bulb well secured to the suction tube with strap?

Also refer to condensing unit or outdoor heat pump section

instructions before starting a split system. A split system

start--up checklist is provided at the end of these instructions.

 

IMPORTANT! / IMPORTANT

40RU500072  2.0

The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping 

access holes. Clamp the TXV sensor bulb on a vertical portion of the suction line, outside the unit. 
See Fig. 7 in the installation, start-up and service instruction. Super heat must be adjusted in field.

Les tubes capillaires du capteur doivent être acheminé à partir du détendeur thermostatique situé à l'intérieur 

de l'appareil au travers de l'un des trous d'accès de conduites. Attacher le capteur sur une portion verticale 

de la conduite de succion, à l'extérieur de l'appareil. Voir la Figure 7 dans le manuel d'installation, de mise 

en marche, et d'entretien. La surchauffe doit être ajustée sur place.

AIR FLOW
CIRCULATION 
        D'AIR

UPPER SPLIT
BLOC SUPÉRIEUR

LOWER
SPLIT
BLOC 
INFÉRIEUR

AIR FLOW

CIRCULATION 

       D'AIR

15 DIAMS MIN

15 x DIA. MIN

10 DIAMS

10 x DIA. MIN

TXV SENSING
BULB
CAPTEUR TXV

15 DIAMS MIN

15 x DIA. MIN

10 DIAMS

10 x DIA. MIN

TXV
SENSING
BULB
CAPTEUR TXV

EQUALIZER LINE
CONDUITE D'ÉQUILIBRAGE

SIGHT GLASS
HUBLOT

8 DIAMS MIN
8 x DIA. MIN

TXV

SOLENOID
VALVE
VANNE 
SOLÉNOÏDE

FILTER

DRIER

FILTRE 

DESSICCATEUR

TXV

EQUALIZER LINE

CONDUITE D'ÉQUILIBRAGE

8 DIAMS MIN

8 x DIA. MIN

INDOOR COIL
ÉCHANGEUR INTÉRIEUR

C10827

Fig. 21 -- Label, TXV Bulb Location

Adjusting TXV for Superheat

(40RUA and RUQ only) —

The unit--mounted thermostatic expansion valve(s) is/are

factory set to provided superheat at the bulb location in

10

_

F to 15

_

F (5.5

_

C to 8.3

_

C) range. Actual system load

conditions may require adjustment of the factory setting.

To adjust the TXV superheat setting:

1. Remove the seal cap from the bottom of the TXV

body.

2. To increase superheat, turn the stem clockwise. To de-

crease the superheat, turn the stem counterclockwise.

Do not turn the stem more than one full turn.

3. Wait until suction pressure and superheat stabilize.

This may take more than 30 minutes.

4. Continue adjustment until superheat reaches 10

_

F to

15

_

F (5.5

_

C to 8.3

_

C).

5. Replace the seal cap; tighten.

INSTALLER / INSTALLATEUR

TXV superheat must be checked at initial 
unit start-up and adjusted if necessary. 
Superheat must be 10 - 15 deg F.

La surchauffe TXV doit être vérifiée au 
moment de la mise en route initiale et 
ajustée si nécessaire. La surchauffe doit 
être comprise entre 10 et 15 degrés F. 

40RU500073  2.0

C10828

Fig. 22 -- Label, TXV Adjustment

SERVICE

Inspection and maintenance should be performed at

regular intervals and should include the following:

S

Complete cleaning of cabinet, fan wheel, cooling coil,
condensate pan and drain, heating coils, and return--air
grille (if present).

S

Inspection of panels and sealing of unit against air
leakage.

S

Adjustment of fan motor, belt, bearings, and wheels.

S

Cleaning or replacement of filters.

S

Testing for cooling/heating system leaks.

S

Checking of all electrical connections.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before performing service or maintenance operations

on unit, always turn off main power switch to unit and

install lockout tag. Unit may have more than one

power switch.

!

WARNING

Most unit service can be performed by removing one or

both of the unit’s side panels. Coil cleaning or removal or

insulation cleaning may require removal of a rear, top, or

bottom panel, depending on the unit’s orientation. When

service is completed, replace unit panels.

Panels --

Panels are fastened to unit frame with sheet metal

screws. Fan and coil compartment must be sealed tightly

after service to prevent air from bypassing the cooling coil.

Fan Motor Lubrication --

Fan motor supplied with unit is

permanently lubricated and requires no further lubrication.

40RU

Summary of Contents for 40RU

Page 1: ...property damage Consult a qualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessor...

Page 2: ...llation must conform with local building codes and with the NEC National Electrical Code or ANSI American National Standards Institute NFPA National Fire Protection Association latest revision Refer t...

Page 3: ...6 67 8 33 10 0 13 25 17 67 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins in 15 15 15 15 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 4: ...62 0 77 0 93 0 93 1 64 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins m 591 591 670 591 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 5: ...its per Split 15 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid...

Page 6: ...er Split 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 3 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid R...

Page 7: ...ace Area sq ft Upper 8 3 9 9 8 3 8 3 Face Area sq ft Lower 5 5 8 3 Rows Fins in 3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out...

Page 8: ...a sq m Upper 0 77 0 91 0 77 0 77 Face Area sq m Lower 0 51 0 77 Rows Fins m 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out 1 1...

Page 9: ...2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field ins...

Page 10: ...c heat accessory Front 2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory...

Page 11: ...08 Only 5 208 230 3 60 Size 16 and Indoor Fan 3 Only 6 460 3 60 Design Rev Catalog Model Number 1 Design Revision original Brand Packaging 0 Standard Not Used A Place Holder Service Options 0 Non Pain...

Page 12: ...it with return air entering top panel of unit Condensate will not drain from unit Typical positioning and alternate return air locations are shown in Fig 6 Alternate return air locations can be used b...

Page 13: ...2 for part numbers Knockouts are provided in the unit corner posts for 40RU refrigerant piping See Fig 8 which also lists recommended knockouts and access holes to use for each 40RU unit size Recommen...

Page 14: ...R LINE Single Circuit Coil Piping Configuration RU 07 08 For single compressor condensing units Dual Circuit Coil Piping Configuration RU 12 16 For single compressor condensing units UPPER SPLIT AIRFL...

Page 15: ...NO CONNECTION TYPE CIRCUIT FITTINGS REQUIRED in 40RUA 07 40RUQ 07 1 Suction 11 8 Street Elbow 11 8 Nipple 105 8 L 11 8 Long Radius Elbow 3 Liquid 5 8 Street Elbow 5 8 Nipple 85 8 L 5 8 Long Radius El...

Page 16: ...Radius Elbow 11 8 Nipple 13 L 11 8 Long Radius Elbow 40RUA 16 1 Suction Lower 11 8 Street Elbow 11 8 Nipple 723 4 L 11 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 13 8 L 5 8 Long Ra...

Page 17: ...n sizes For ease in brazing it it recommended that all internal solder joints be made before unit is placed in final position Knockouts are provided in the unit corner posts for 40RUS refrigerant pipi...

Page 18: ...or sump Provide service clearance around drain line to permit removal of unit panels Observe all local sanitary codes C10692 Fig 14 Drain Pan Slope Adjustment As shipped the unit s condensate drain pa...

Page 19: ...ocal codes See Fig 15 17 and the unit label diagram For units with motor sizes less than 5 Hp 3 7 kW connect power wiring to unit with no 10 ring terminal For units with motor sizes of 5 Hp 3 7 kW or...

Page 20: ...Legend and Notes on page 21 Table 5 Electrical Data Alternate Motors UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA Minimum Circuit Amps MOCP 40RUA 07 40RUQ 07 208 230 1 60 187 253 2 4 1...

Page 21: ...lation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclos...

Page 22: ...to the supply duct using a canvas connection to prevent vibration It is important that this connection be properly fabricated to prevent high air friction losses and air noise RETURN CONNECTIONS When...

Page 23: ...TXV for Superheat 40RUA and RUQ only The unit mounted thermostatic expansion valve s is are factory set to provided superheat at the bulb location in 10_F to 15_F 5 5_C to 8 3_C range Actual system l...

Page 24: ...an and fan shaft assembly are not properly centered blades may scrape against the blower side scroll plate or may create an objectionable whistling noise It may be necessary to adjust individual fan w...

Page 25: ...of motor terminal box cover for proper reversing procedure of single phase motor C10701 Fig 26 Fan Rotation Fan Pulley Alignment Align as follows 1 Loosen setscrews on pulleys 2 Align pulleys visuall...

Page 26: ...or compressed air when coil is dry If coil is wet or if water is to be used for cleaning guard against splashing water on electrical components or damaging surrounding area Clean coil baffles as appli...

Page 27: ...HZ Shaft Dia in 5 8 7 8 7 8 7 8 7 8 LEGEND NEMA National Electrical Manufacturers Association Table 8B Fan Motor Data Alternate Motor English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12...

Page 28: ...Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 LEGEND NEMA National Electrical Manufacturers Association Table 8D Fan Motor Data Alternate Motor SI UNIT 40RUA 07 40RUQ0 7 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40...

Page 29: ...5 5 5 5 5 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 9B Medium Static Drive Data 60 Hz English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA...

Page 30: ...single phase motor pulley pitch diameter is 7 in And resulting fan speed is 837 1096 rpm It is possible to adjust drive so that fan speed exceeds maximum allowable DO NOT exceed 1200 rpm 575 v unit h...

Page 31: ...0 Hz SI UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40RUQ 12 40RUS 12 40RUA 14 40RUS 14 40RUA 16 40RUQ 16 40RUS 16 MOTOR DRIVE Motor Pulley Pitch Diameter mm 86 4 111 8 86 4 111 8 86 4...

Page 32: ...11 827 2 51 886 2 92 6 000 542 1 29 578 1 43 649 1 74 721 2 11 791 2 55 855 3 00 914 3 46 6 800 604 1 83 637 1 99 700 2 32 763 2 70 826 3 15 888 3 64 946 4 15 7 500 660 2 42 690 2 59 747 2 95 804 3 3...

Page 33: ...78 10 15 1 00 11 48 1 27 12 70 1 57 13 78 1 87 14 76 2 18 2830 9 03 0 96 9 63 1 07 10 81 1 30 12 01 1 58 13 18 1 90 14 25 2 24 15 23 2 58 3210 10 07 1 37 10 62 1 48 11 66 1 73 12 71 2 01 13 77 2 35 1...

Page 34: ...1 07 617 1 37 696 1 74 767 2 13 830 2 53 888 2 94 6 000 555 1 34 590 1 48 659 1 79 730 2 17 798 2 59 860 3 04 918 3 49 6 800 620 1 91 651 2 06 712 2 39 774 2 78 836 3 22 896 3 71 952 4 21 7 500 677 2...

Page 35: ...51 14 27 1 78 2500 8 32 0 71 8 97 0 80 10 29 1 02 11 59 1 30 12 78 1 59 13 84 1 89 14 80 2 19 2830 9 25 1 00 9 83 1 10 10 99 1 33 12 16 1 62 13 29 1 93 14 34 2 27 15 30 2 60 3210 10 33 1 42 10 85 1 5...

Page 36: ...000 0 11 4 000 0 17 5 000 0 23 40RUA 14 40RUS 14 3 750 0 06 5 000 0 10 6 250 0 13 40RUA 16 40RUQ 16 40RUS 16 4 500 0 08 6 000 0 12 7 500 0 17 Legend and Notes for Tables 10B and 10D LEGEND ESP Externa...

Page 37: ...37 40RU...

Page 38: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Page 39: ...HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN...

Page 40: ...UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP OUTDOOR UNIT ENTERING WATER TEMP 40RUS ONLY OUTDOOR UNI...

Reviews: