2

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could cause in personal

injury or death.
Before performing service or maintenance operations

on unit, always turn off main power switch to unit and

install lockout tag. Unit may have more than one

power switch.

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could cause in personal

injury,death and/or equipment damage.
Puron

R

(R--410A) refrigerant systems operate at

higher pressures than standard R--22 systems. Do not

use R--22 service equipment or components on Puron

refrigerant equipment.

!

WARNING

PERSONAL INJURY AND ENVIRONMENTAL

HAZARD

Failure to follow this warning could cause in personal

injury or death.
Relieve pressure and recover all refrigerant before

system repair or final unit disposal.
Wear safety glasses and gloves when handling

refrigerants. Keep torches and other ignition sources

away from refrigerants and oils.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal

injury.
Sheet metal parts may have sharp edges or burrs. Use

care and wear appropriate protective clothing, safety

glasses and gloves when handling parts and servicing

40RU units.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution could cause equipment

damage.
Ensure voltage listed on unit data plate agrees with

electrical supply provided for the unit.

CAUTION

!

PRE--INSTALLATION

1. The power supply (v, ph, and Hz) must correspond to

that specified on unit rating plate.

2. The electrical supply provided by the utility must be

sufficient to handle load imposed by this unit.

3. Refer to Installation, General section (page 2) and

Fig. 1 and Fig. 2 for locations of electrical inlets, con-

densate drain, duct connections, and required clear-

ances before setting unit in place.

4. This installation must conform with local building

codes and with the NEC (National Electrical Code) or

ANSI (American National Standards Institute)/NFPA

(National Fire Protection Association) latest revision.

Refer to provincial and local plumbing or wastewater

codes and other applicable local codes.

Moving and Storage --

To transfer unit from truck to

storage site, use a fork truck. Do not stack units more than

2 high during storage. If unit is to be stored for more than

2 weeks before installation, choose a level, dry storage

site free from vibration. Do not remove plastic wrap or

skid from unit until final installation.

Rigging --

All 40RU Series units can be rigged by using

the shipping skid. Units are shipped fully assembled. Do

not remove shipping skids or protective covering until unit

is ready for final placement; damage to bottom panels can

result. Use slings and spreader bars as applicable to lift

unit.

INSTALLATION

General --

Allow the following clearances for service

access and airflow:

S

Rear: 3 ft (914 mm) [2

1

/

2

ft (762 mm) with electric heat

accessory]

S

Front: 2

1

/

2

ft (762 mm)

S

Right Side: 3

1

/

2

ft (1067 mm)

S

Left Side: 2

1

/

2

ft (762 mm)

For units equipped with an economizer, refer to the

accessory installation instructions for additional clearance

requirements. Be sure floor, wall, or ceiling can support

unit weight (Tables 1A – 1F). See Fig. 1 and Fig. 2 for

dimensions.

Uncrating --

Move unit as near as possible to final

location before removing shipping skid.

Remove metal banding, top skid, and plastic wrap.

Examine unit for shipping damage. If shipping damage is

evident, file claim with transportation agency. Remove

base skid just prior to actual installation.

Check nameplate information against available power

supply and model number description in Fig. 3.

NOTE

: Be sure to remove the styrofoam shipping pad

from the thermostatic expansion valve (TXV). Verify that
it has been removed. See Fig. 5.

Accessories --

Refer to instructions shipped with each

accessory for specific information.

40RU

Summary of Contents for 40RU

Page 1: ...property damage Consult a qualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessor...

Page 2: ...llation must conform with local building codes and with the NEC National Electrical Code or ANSI American National Standards Institute NFPA National Fire Protection Association latest revision Refer t...

Page 3: ...6 67 8 33 10 0 13 25 17 67 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins in 15 15 15 15 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 4: ...62 0 77 0 93 0 93 1 64 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins m 591 591 670 591 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 5: ...its per Split 15 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid...

Page 6: ...er Split 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 3 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid R...

Page 7: ...ace Area sq ft Upper 8 3 9 9 8 3 8 3 Face Area sq ft Lower 5 5 8 3 Rows Fins in 3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out...

Page 8: ...a sq m Upper 0 77 0 91 0 77 0 77 Face Area sq m Lower 0 51 0 77 Rows Fins m 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out 1 1...

Page 9: ...2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field ins...

Page 10: ...c heat accessory Front 2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory...

Page 11: ...08 Only 5 208 230 3 60 Size 16 and Indoor Fan 3 Only 6 460 3 60 Design Rev Catalog Model Number 1 Design Revision original Brand Packaging 0 Standard Not Used A Place Holder Service Options 0 Non Pain...

Page 12: ...it with return air entering top panel of unit Condensate will not drain from unit Typical positioning and alternate return air locations are shown in Fig 6 Alternate return air locations can be used b...

Page 13: ...2 for part numbers Knockouts are provided in the unit corner posts for 40RU refrigerant piping See Fig 8 which also lists recommended knockouts and access holes to use for each 40RU unit size Recommen...

Page 14: ...R LINE Single Circuit Coil Piping Configuration RU 07 08 For single compressor condensing units Dual Circuit Coil Piping Configuration RU 12 16 For single compressor condensing units UPPER SPLIT AIRFL...

Page 15: ...NO CONNECTION TYPE CIRCUIT FITTINGS REQUIRED in 40RUA 07 40RUQ 07 1 Suction 11 8 Street Elbow 11 8 Nipple 105 8 L 11 8 Long Radius Elbow 3 Liquid 5 8 Street Elbow 5 8 Nipple 85 8 L 5 8 Long Radius El...

Page 16: ...Radius Elbow 11 8 Nipple 13 L 11 8 Long Radius Elbow 40RUA 16 1 Suction Lower 11 8 Street Elbow 11 8 Nipple 723 4 L 11 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 13 8 L 5 8 Long Ra...

Page 17: ...n sizes For ease in brazing it it recommended that all internal solder joints be made before unit is placed in final position Knockouts are provided in the unit corner posts for 40RUS refrigerant pipi...

Page 18: ...or sump Provide service clearance around drain line to permit removal of unit panels Observe all local sanitary codes C10692 Fig 14 Drain Pan Slope Adjustment As shipped the unit s condensate drain pa...

Page 19: ...ocal codes See Fig 15 17 and the unit label diagram For units with motor sizes less than 5 Hp 3 7 kW connect power wiring to unit with no 10 ring terminal For units with motor sizes of 5 Hp 3 7 kW or...

Page 20: ...Legend and Notes on page 21 Table 5 Electrical Data Alternate Motors UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA Minimum Circuit Amps MOCP 40RUA 07 40RUQ 07 208 230 1 60 187 253 2 4 1...

Page 21: ...lation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclos...

Page 22: ...to the supply duct using a canvas connection to prevent vibration It is important that this connection be properly fabricated to prevent high air friction losses and air noise RETURN CONNECTIONS When...

Page 23: ...TXV for Superheat 40RUA and RUQ only The unit mounted thermostatic expansion valve s is are factory set to provided superheat at the bulb location in 10_F to 15_F 5 5_C to 8 3_C range Actual system l...

Page 24: ...an and fan shaft assembly are not properly centered blades may scrape against the blower side scroll plate or may create an objectionable whistling noise It may be necessary to adjust individual fan w...

Page 25: ...of motor terminal box cover for proper reversing procedure of single phase motor C10701 Fig 26 Fan Rotation Fan Pulley Alignment Align as follows 1 Loosen setscrews on pulleys 2 Align pulleys visuall...

Page 26: ...or compressed air when coil is dry If coil is wet or if water is to be used for cleaning guard against splashing water on electrical components or damaging surrounding area Clean coil baffles as appli...

Page 27: ...HZ Shaft Dia in 5 8 7 8 7 8 7 8 7 8 LEGEND NEMA National Electrical Manufacturers Association Table 8B Fan Motor Data Alternate Motor English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12...

Page 28: ...Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 LEGEND NEMA National Electrical Manufacturers Association Table 8D Fan Motor Data Alternate Motor SI UNIT 40RUA 07 40RUQ0 7 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40...

Page 29: ...5 5 5 5 5 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 9B Medium Static Drive Data 60 Hz English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA...

Page 30: ...single phase motor pulley pitch diameter is 7 in And resulting fan speed is 837 1096 rpm It is possible to adjust drive so that fan speed exceeds maximum allowable DO NOT exceed 1200 rpm 575 v unit h...

Page 31: ...0 Hz SI UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40RUQ 12 40RUS 12 40RUA 14 40RUS 14 40RUA 16 40RUQ 16 40RUS 16 MOTOR DRIVE Motor Pulley Pitch Diameter mm 86 4 111 8 86 4 111 8 86 4...

Page 32: ...11 827 2 51 886 2 92 6 000 542 1 29 578 1 43 649 1 74 721 2 11 791 2 55 855 3 00 914 3 46 6 800 604 1 83 637 1 99 700 2 32 763 2 70 826 3 15 888 3 64 946 4 15 7 500 660 2 42 690 2 59 747 2 95 804 3 3...

Page 33: ...78 10 15 1 00 11 48 1 27 12 70 1 57 13 78 1 87 14 76 2 18 2830 9 03 0 96 9 63 1 07 10 81 1 30 12 01 1 58 13 18 1 90 14 25 2 24 15 23 2 58 3210 10 07 1 37 10 62 1 48 11 66 1 73 12 71 2 01 13 77 2 35 1...

Page 34: ...1 07 617 1 37 696 1 74 767 2 13 830 2 53 888 2 94 6 000 555 1 34 590 1 48 659 1 79 730 2 17 798 2 59 860 3 04 918 3 49 6 800 620 1 91 651 2 06 712 2 39 774 2 78 836 3 22 896 3 71 952 4 21 7 500 677 2...

Page 35: ...51 14 27 1 78 2500 8 32 0 71 8 97 0 80 10 29 1 02 11 59 1 30 12 78 1 59 13 84 1 89 14 80 2 19 2830 9 25 1 00 9 83 1 10 10 99 1 33 12 16 1 62 13 29 1 93 14 34 2 27 15 30 2 60 3210 10 33 1 42 10 85 1 5...

Page 36: ...000 0 11 4 000 0 17 5 000 0 23 40RUA 14 40RUS 14 3 750 0 06 5 000 0 10 6 250 0 13 40RUA 16 40RUQ 16 40RUS 16 4 500 0 08 6 000 0 12 7 500 0 17 Legend and Notes for Tables 10B and 10D LEGEND ESP Externa...

Page 37: ...37 40RU...

Page 38: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Page 39: ...HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN...

Page 40: ...UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP OUTDOOR UNIT ENTERING WATER TEMP 40RUS ONLY OUTDOOR UNI...