background image

13

Unit Isolation --

Where extremely quiet operation is

essential, install isolators between floor and base of unit,

or between ceiling and top section of unit.

Be sure that unit is level and adequately supported. Use

channels at front and sides of unit for reference points

when leveling.

Refrigerant and Chilled Water Piping Access --

The

40RU Series units come with standard knockouts for

refrigerant and chilled water piping. These knockouts are

located on both sides of the unit for installation flexibility.

The standard knockouts provide sufficient access to the

unit’s coils for all 40RUA*07, 08, 12, 14, 16 and

40RUQ*07, 08, 12 units. 40RUQ*16 units, as well as

40RUS*08, 12, 14, and 16 units require additional holes

which must be field--fabricated to accommodate the

piping. See Fig. 8 for positions and dimensions of the

additional access holes required for the 40RUQ*16 and

40RUS units. Recommended access hole use is also listed

for all units. Note that Fig. 8 shows the access holes on

the control--box side of the unit; this is the side of the unit

with the coil headers, so it is used most often for piping

access.

IMPORTANT

: Do not bury refrigerant piping underground.

Refrigerant Piping --

See Tables 1A–1F for refrigerant

pipe connection sizes. For ease in brazing, it is

recommended that all internal solder joints be made

before unit is placed in final position.

The

40RU

direct--expansion

units

have

internal

factory--installed thermostatic expansion valves (TXVs),

distributors, and nozzles for use with R--410A. See Table 2

for part numbers. Knockouts are provided in the unit corner

posts for 40RU refrigerant piping. See Fig. 8, which also

lists recommended knockouts and access holes to use for

each 40RU unit size. Recommended fittings are listed in

Table 3.

The sensor bulb capillary tubes must be routed from the

TXVs inside the unit through one of the piping access

holes. Clamp the TXV sensor bulb on a vertical portion of

the suction line, outside the unit. See Fig. 9.

NOTE

: Be sure to remove the styrofoam shipping pad

from the TXV. Verify that it has been removed. See Fig. 5.

IMPORTANT

: Never attach the sensor to the suction

manifold. Do NOT mount the sensor on a trapped portion
of the suction line.
The 40RU Series evaporator coils have a face--split design.

Ensure that lower circuit of coil is first on/last off when

connected to the condensing unit and/or system controls. See

Fig. 10.

External TXV equalizer connections are provided and

factory--brazed into the coil suction manifolds.

If suction line must be horizontal, clamp bulb to suction

line at least 45 degrees above bottom, at approximately

the 4 o’clock or 8 o’clock position. See Fig.11.

4

3
2

1

7
6
5

A

B

C

C10686

UNIT

USE HOLE

NUMBERS

FIELD---FABRICATED HOLE DIAMATERS

in. (mm)

FIELD---FABRICATED HOLE POSITION

DIMENSIONS, in. (mm)

No. 5

No. 6

No. 7

A

B

C

40RUA*07, 08

40RUQ*07, 08

1, 3

40RUA*12, 14, 16

40RUQ12

1, 2, 3, 4

40RUS*08, 12

4, 5

1

3

/

4

(44.5)

6.25 (158.8)

40RUS*14, 16

4, 5, 6, 7

1

3

/

4

(44.5)

1

3

/

4

(44.5)

1

3

/

4

(44.5)

3.0 (76.2)

6.0 (152.5)

10.5 (266.7)

40RUQ*16

3

{

, 5, 6, 7

1

1

/8 (28.6)

1

1

/8 (28.6)

1

3

/

4

(44.5)

3.25 (82.6)

6.125 (155.6)

10.38 (263.7)

{

Must be enlarged from 1

1

/

8

in. (28.6mm) to 1

3

/

4

in. (44.5mm)

NOTE: Access hole knockouts 1--- 4 are factory--- supplied.

Fig. 8 -- Refrigerant and Chilled Water Piping Access Holes

40RU

Summary of Contents for 40RU

Page 1: ...property damage Consult a qualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessor...

Page 2: ...llation must conform with local building codes and with the NEC National Electrical Code or ANSI American National Standards Institute NFPA National Fire Protection Association latest revision Refer t...

Page 3: ...6 67 8 33 10 0 13 25 17 67 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins in 15 15 15 15 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 4: ...62 0 77 0 93 0 93 1 64 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins m 591 591 670 591 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 5: ...its per Split 15 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid...

Page 6: ...er Split 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 3 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid R...

Page 7: ...ace Area sq ft Upper 8 3 9 9 8 3 8 3 Face Area sq ft Lower 5 5 8 3 Rows Fins in 3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out...

Page 8: ...a sq m Upper 0 77 0 91 0 77 0 77 Face Area sq m Lower 0 51 0 77 Rows Fins m 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out 1 1...

Page 9: ...2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field ins...

Page 10: ...c heat accessory Front 2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory...

Page 11: ...08 Only 5 208 230 3 60 Size 16 and Indoor Fan 3 Only 6 460 3 60 Design Rev Catalog Model Number 1 Design Revision original Brand Packaging 0 Standard Not Used A Place Holder Service Options 0 Non Pain...

Page 12: ...it with return air entering top panel of unit Condensate will not drain from unit Typical positioning and alternate return air locations are shown in Fig 6 Alternate return air locations can be used b...

Page 13: ...2 for part numbers Knockouts are provided in the unit corner posts for 40RU refrigerant piping See Fig 8 which also lists recommended knockouts and access holes to use for each 40RU unit size Recommen...

Page 14: ...R LINE Single Circuit Coil Piping Configuration RU 07 08 For single compressor condensing units Dual Circuit Coil Piping Configuration RU 12 16 For single compressor condensing units UPPER SPLIT AIRFL...

Page 15: ...NO CONNECTION TYPE CIRCUIT FITTINGS REQUIRED in 40RUA 07 40RUQ 07 1 Suction 11 8 Street Elbow 11 8 Nipple 105 8 L 11 8 Long Radius Elbow 3 Liquid 5 8 Street Elbow 5 8 Nipple 85 8 L 5 8 Long Radius El...

Page 16: ...Radius Elbow 11 8 Nipple 13 L 11 8 Long Radius Elbow 40RUA 16 1 Suction Lower 11 8 Street Elbow 11 8 Nipple 723 4 L 11 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 13 8 L 5 8 Long Ra...

Page 17: ...n sizes For ease in brazing it it recommended that all internal solder joints be made before unit is placed in final position Knockouts are provided in the unit corner posts for 40RUS refrigerant pipi...

Page 18: ...or sump Provide service clearance around drain line to permit removal of unit panels Observe all local sanitary codes C10692 Fig 14 Drain Pan Slope Adjustment As shipped the unit s condensate drain pa...

Page 19: ...ocal codes See Fig 15 17 and the unit label diagram For units with motor sizes less than 5 Hp 3 7 kW connect power wiring to unit with no 10 ring terminal For units with motor sizes of 5 Hp 3 7 kW or...

Page 20: ...Legend and Notes on page 21 Table 5 Electrical Data Alternate Motors UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA Minimum Circuit Amps MOCP 40RUA 07 40RUQ 07 208 230 1 60 187 253 2 4 1...

Page 21: ...lation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclos...

Page 22: ...to the supply duct using a canvas connection to prevent vibration It is important that this connection be properly fabricated to prevent high air friction losses and air noise RETURN CONNECTIONS When...

Page 23: ...TXV for Superheat 40RUA and RUQ only The unit mounted thermostatic expansion valve s is are factory set to provided superheat at the bulb location in 10_F to 15_F 5 5_C to 8 3_C range Actual system l...

Page 24: ...an and fan shaft assembly are not properly centered blades may scrape against the blower side scroll plate or may create an objectionable whistling noise It may be necessary to adjust individual fan w...

Page 25: ...of motor terminal box cover for proper reversing procedure of single phase motor C10701 Fig 26 Fan Rotation Fan Pulley Alignment Align as follows 1 Loosen setscrews on pulleys 2 Align pulleys visuall...

Page 26: ...or compressed air when coil is dry If coil is wet or if water is to be used for cleaning guard against splashing water on electrical components or damaging surrounding area Clean coil baffles as appli...

Page 27: ...HZ Shaft Dia in 5 8 7 8 7 8 7 8 7 8 LEGEND NEMA National Electrical Manufacturers Association Table 8B Fan Motor Data Alternate Motor English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12...

Page 28: ...Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 LEGEND NEMA National Electrical Manufacturers Association Table 8D Fan Motor Data Alternate Motor SI UNIT 40RUA 07 40RUQ0 7 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40...

Page 29: ...5 5 5 5 5 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 9B Medium Static Drive Data 60 Hz English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA...

Page 30: ...single phase motor pulley pitch diameter is 7 in And resulting fan speed is 837 1096 rpm It is possible to adjust drive so that fan speed exceeds maximum allowable DO NOT exceed 1200 rpm 575 v unit h...

Page 31: ...0 Hz SI UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40RUQ 12 40RUS 12 40RUA 14 40RUS 14 40RUA 16 40RUQ 16 40RUS 16 MOTOR DRIVE Motor Pulley Pitch Diameter mm 86 4 111 8 86 4 111 8 86 4...

Page 32: ...11 827 2 51 886 2 92 6 000 542 1 29 578 1 43 649 1 74 721 2 11 791 2 55 855 3 00 914 3 46 6 800 604 1 83 637 1 99 700 2 32 763 2 70 826 3 15 888 3 64 946 4 15 7 500 660 2 42 690 2 59 747 2 95 804 3 3...

Page 33: ...78 10 15 1 00 11 48 1 27 12 70 1 57 13 78 1 87 14 76 2 18 2830 9 03 0 96 9 63 1 07 10 81 1 30 12 01 1 58 13 18 1 90 14 25 2 24 15 23 2 58 3210 10 07 1 37 10 62 1 48 11 66 1 73 12 71 2 01 13 77 2 35 1...

Page 34: ...1 07 617 1 37 696 1 74 767 2 13 830 2 53 888 2 94 6 000 555 1 34 590 1 48 659 1 79 730 2 17 798 2 59 860 3 04 918 3 49 6 800 620 1 91 651 2 06 712 2 39 774 2 78 836 3 22 896 3 71 952 4 21 7 500 677 2...

Page 35: ...51 14 27 1 78 2500 8 32 0 71 8 97 0 80 10 29 1 02 11 59 1 30 12 78 1 59 13 84 1 89 14 80 2 19 2830 9 25 1 00 9 83 1 10 10 99 1 33 12 16 1 62 13 29 1 93 14 34 2 27 15 30 2 60 3210 10 33 1 42 10 85 1 5...

Page 36: ...000 0 11 4 000 0 17 5 000 0 23 40RUA 14 40RUS 14 3 750 0 06 5 000 0 10 6 250 0 13 40RUA 16 40RUQ 16 40RUS 16 4 500 0 08 6 000 0 12 7 500 0 17 Legend and Notes for Tables 10B and 10D LEGEND ESP Externa...

Page 37: ...37 40RU...

Page 38: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Page 39: ...HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN...

Page 40: ...UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP OUTDOOR UNIT ENTERING WATER TEMP 40RUS ONLY OUTDOOR UNI...

Reviews: