background image

5

Table 1C — 40RUQ Physical Data, English — Heat Pump Units

UNIT 40RUQ*

07

08

12

16

NOMINAL CAPACITY (Tons)

6

7

1/2

10

15

OPERATING WEIGHT (lb)

Base Unit with TXV

385

385

427

713

Plenum

175

175

175

225

FANS

Qty...Diam. (in.)

1...15

1...15

1...15

2...15

Nominal Airflow (cfm)

2400

3000

4000

6000

Airflow Range (cfm)

1800---3000

2250---3750

3000---5000

4500---7500

Nominal Motor Hp (Standard Motor)

208/230---1---60

1.3

2.4

208/230---3---60 and 460---3---60

2.4

2.4

2.4

3.7

575---3---60

1.0

2.0

2.0

3.0

Motor Speed (rpm)

208/230---1---60

1725

1725

208/230---3---60 and 460---3---60

1725

1725

1725

1725

575---3---60

1725

1725

1725

1725

REFRIGERANT

R---410A

Operating charge (lb)

(approx per circuit)

{

3.0

3.0

2.0/2.0

3.0/3.0

DIRECT---EXPANSION COIL

Enhanced Copper Tubes, Aluminum Sine---Wave Fins

Max Working Pressure (psig)

650

Face Area (sq ft)

8.33

8.33

10.0

16.56

No. of Splits

1

1

2

2

No. of Circuits per Split

15

12

9

10

Split Type...Percentage

Face...50/50

Face...50/50

Rows...Fins/in.

3...15

4...15

4...15

4...15

PIPING CONNECTIONS,

Quantity...Size (in.)

DX Coil — Suction (ODF)

1...1

1/8

1...1

1/8

2...1

1/8

2...1

1/8

DX Coil — Liquid Refrigerant (ODF)

1...

5/8

1...

5/8

2...

5/8

2...

5/8

Steam Coil, In (MPT)

1...2

1/2

1...2

1/2

1...2

1/2

1...2

1/2

Steam Coil, Out (MPT)

1...1

1/2

1...1

1/2

1...1

1/2

1...1

1/2

Hot Water Coil, In (MPT)

1...1

1/2

1...1

1/2

1...1

1/2

1...2

Hot Water Coil, Out (MPT)

1...1

1/2

1...1

1/2

1...1

1/2

1...2

Condensate (PVC)

1...1

1/4 ODM/1 IDF

FILTERS

Throwaway — Factory Supplied

Quantity...Size (in.)

4...16 x 24 x 2

4...16 x 20 x 2

4...16 x 24 x 2

Access Location

Either Side

STEAM COIL

}

Max Working Pressure (psig at 260° F)

20

Total Face Area (sq ft)

6.67

6.67

6.67

13.33

Rows...Fins/in.

1...9

1...9

1...9

1...10

HOT WATER COIL

}

Max Working Pressure (psig)

150

Total Face Area (sq ft)

6.67

6.67

6.67

13.33

Rows...Fins/in.

2...8.5

2...8.5

2...8.5

2...8.5

Water Volume

(gal)

8.3

13.9

(ft

3

)

1.1

1.85

LEGEND

DX —

Direct Expansion

TXV —

Thermostatic Expansion Valve

{

Units are shipped without refrigerant charge.

}

Field installed accessory only.

40RU

Summary of Contents for 40RU

Page 1: ...property damage Consult a qualified installer service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessor...

Page 2: ...llation must conform with local building codes and with the NEC National Electrical Code or ANSI American National Standards Institute NFPA National Fire Protection Association latest revision Refer t...

Page 3: ...6 67 8 33 10 0 13 25 17 67 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins in 15 15 15 15 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 4: ...62 0 77 0 93 0 93 1 64 No of Splits 1 1 2 2 2 No of Circuits per Split 12 15 9 12 16 Split Type Percentage Face 50 50 Fins m 591 591 670 591 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction OD...

Page 5: ...its per Split 15 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins in 3 15 4 15 4 15 4 15 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid...

Page 6: ...er Split 12 12 9 10 Split Type Percentage Face 50 50 Face 50 50 Rows Fins m 3 591 3 591 3 591 4 591 PIPING CONNECTIONS Quantity Size in DX Coil Suction ODF 1 11 8 1 11 8 2 11 8 2 11 8 DX Coil Liquid R...

Page 7: ...ace Area sq ft Upper 8 3 9 9 8 3 8 3 Face Area sq ft Lower 5 5 8 3 Rows Fins in 3 15 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out...

Page 8: ...a sq m Upper 0 77 0 91 0 77 0 77 Face Area sq m Lower 0 51 0 77 Rows Fins m 3 591 PIPING CONNECTIONS Quantity Size in Chilled Water In 1 13 8 ODF 2 13 8 ODF 2 13 8 ODM 2 13 8 ODM Chilled Water Out 1 1...

Page 9: ...2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory supplied and field ins...

Page 10: ...c heat accessory Front 2 ft 6 in 762 mm Right Side 2 ft 6 in 762 mm Left Side 2 ft 6 in 762 mm Local codes or jurisdiction may prevail 4 Liquid piping not supplied by Carrier 5 Duct flange is factory...

Page 11: ...08 Only 5 208 230 3 60 Size 16 and Indoor Fan 3 Only 6 460 3 60 Design Rev Catalog Model Number 1 Design Revision original Brand Packaging 0 Standard Not Used A Place Holder Service Options 0 Non Pain...

Page 12: ...it with return air entering top panel of unit Condensate will not drain from unit Typical positioning and alternate return air locations are shown in Fig 6 Alternate return air locations can be used b...

Page 13: ...2 for part numbers Knockouts are provided in the unit corner posts for 40RU refrigerant piping See Fig 8 which also lists recommended knockouts and access holes to use for each 40RU unit size Recommen...

Page 14: ...R LINE Single Circuit Coil Piping Configuration RU 07 08 For single compressor condensing units Dual Circuit Coil Piping Configuration RU 12 16 For single compressor condensing units UPPER SPLIT AIRFL...

Page 15: ...NO CONNECTION TYPE CIRCUIT FITTINGS REQUIRED in 40RUA 07 40RUQ 07 1 Suction 11 8 Street Elbow 11 8 Nipple 105 8 L 11 8 Long Radius Elbow 3 Liquid 5 8 Street Elbow 5 8 Nipple 85 8 L 5 8 Long Radius El...

Page 16: ...Radius Elbow 11 8 Nipple 13 L 11 8 Long Radius Elbow 40RUA 16 1 Suction Lower 11 8 Street Elbow 11 8 Nipple 723 4 L 11 8 Long Radius Elbow 2 Liquid Lower 5 8 Street Elbow 5 8 Nipple 13 8 L 5 8 Long Ra...

Page 17: ...n sizes For ease in brazing it it recommended that all internal solder joints be made before unit is placed in final position Knockouts are provided in the unit corner posts for 40RUS refrigerant pipi...

Page 18: ...or sump Provide service clearance around drain line to permit removal of unit panels Observe all local sanitary codes C10692 Fig 14 Drain Pan Slope Adjustment As shipped the unit s condensate drain pa...

Page 19: ...ocal codes See Fig 15 17 and the unit label diagram For units with motor sizes less than 5 Hp 3 7 kW connect power wiring to unit with no 10 ring terminal For units with motor sizes of 5 Hp 3 7 kW or...

Page 20: ...Legend and Notes on page 21 Table 5 Electrical Data Alternate Motors UNIT V PH Hz VOLTAGE LIMITS FAN MOTOR POWER SUPPLY Hp kW FLA Minimum Circuit Amps MOCP 40RUA 07 40RUQ 07 208 230 1 60 187 253 2 4 1...

Page 21: ...lation with Accessory Electric Heaters Size the Field Power Wiring between the heater TB1 and the 40RU indoor fan motor per NEC Article 430 28 1 or 2 depends on length of conduit between heater enclos...

Page 22: ...to the supply duct using a canvas connection to prevent vibration It is important that this connection be properly fabricated to prevent high air friction losses and air noise RETURN CONNECTIONS When...

Page 23: ...TXV for Superheat 40RUA and RUQ only The unit mounted thermostatic expansion valve s is are factory set to provided superheat at the bulb location in 10_F to 15_F 5 5_C to 8 3_C range Actual system l...

Page 24: ...an and fan shaft assembly are not properly centered blades may scrape against the blower side scroll plate or may create an objectionable whistling noise It may be necessary to adjust individual fan w...

Page 25: ...of motor terminal box cover for proper reversing procedure of single phase motor C10701 Fig 26 Fan Rotation Fan Pulley Alignment Align as follows 1 Loosen setscrews on pulleys 2 Align pulleys visuall...

Page 26: ...or compressed air when coil is dry If coil is wet or if water is to be used for cleaning guard against splashing water on electrical components or damaging surrounding area Clean coil baffles as appli...

Page 27: ...HZ Shaft Dia in 5 8 7 8 7 8 7 8 7 8 LEGEND NEMA National Electrical Manufacturers Association Table 8B Fan Motor Data Alternate Motor English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12...

Page 28: ...Shaft Dia mm 15 9 22 2 22 2 22 2 22 2 LEGEND NEMA National Electrical Manufacturers Association Table 8D Fan Motor Data Alternate Motor SI UNIT 40RUA 07 40RUQ0 7 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40...

Page 29: ...5 5 5 5 5 SHAFTS CENTER DISTANCE in 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 10 44 12 32 Table 9B Medium Static Drive Data 60 Hz English UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA...

Page 30: ...single phase motor pulley pitch diameter is 7 in And resulting fan speed is 837 1096 rpm It is possible to adjust drive so that fan speed exceeds maximum allowable DO NOT exceed 1200 rpm 575 v unit h...

Page 31: ...0 Hz SI UNIT 40RUA 07 40RUQ 07 40RUA 08 40RUQ 08 40RUS 08 40RUA 12 40RUQ 12 40RUS 12 40RUA 14 40RUS 14 40RUA 16 40RUQ 16 40RUS 16 MOTOR DRIVE Motor Pulley Pitch Diameter mm 86 4 111 8 86 4 111 8 86 4...

Page 32: ...11 827 2 51 886 2 92 6 000 542 1 29 578 1 43 649 1 74 721 2 11 791 2 55 855 3 00 914 3 46 6 800 604 1 83 637 1 99 700 2 32 763 2 70 826 3 15 888 3 64 946 4 15 7 500 660 2 42 690 2 59 747 2 95 804 3 3...

Page 33: ...78 10 15 1 00 11 48 1 27 12 70 1 57 13 78 1 87 14 76 2 18 2830 9 03 0 96 9 63 1 07 10 81 1 30 12 01 1 58 13 18 1 90 14 25 2 24 15 23 2 58 3210 10 07 1 37 10 62 1 48 11 66 1 73 12 71 2 01 13 77 2 35 1...

Page 34: ...1 07 617 1 37 696 1 74 767 2 13 830 2 53 888 2 94 6 000 555 1 34 590 1 48 659 1 79 730 2 17 798 2 59 860 3 04 918 3 49 6 800 620 1 91 651 2 06 712 2 39 774 2 78 836 3 22 896 3 71 952 4 21 7 500 677 2...

Page 35: ...51 14 27 1 78 2500 8 32 0 71 8 97 0 80 10 29 1 02 11 59 1 30 12 78 1 59 13 84 1 89 14 80 2 19 2830 9 25 1 00 9 83 1 10 10 99 1 33 12 16 1 62 13 29 1 93 14 34 2 27 15 30 2 60 3210 10 33 1 42 10 85 1 5...

Page 36: ...000 0 11 4 000 0 17 5 000 0 23 40RUA 14 40RUS 14 3 750 0 06 5 000 0 10 6 250 0 13 40RUA 16 40RUQ 16 40RUS 16 4 500 0 08 6 000 0 12 7 500 0 17 Legend and Notes for Tables 10B and 10D LEGEND ESP Externa...

Page 37: ...37 40RU...

Page 38: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog...

Page 39: ...HOURS Y N INDOOR UNIT HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N ARE PROPER AIR FILTERS IN PLACE Y N HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT Y N DO THE FAN...

Page 40: ...UNIT AIR TEMP INDOOR UNIT ENTERING AIR DB TEMP INDOOR UNIT ENTERING AIR WB TEMP INDOOR UNIT LEAVING AIR DB TEMP INDOOR UNIT LEAVING AIR WB TEMP OUTDOOR UNIT ENTERING WATER TEMP 40RUS ONLY OUTDOOR UNI...

Reviews: