Do not vent refrigerant to atmosphere. Recover during system
repair or final unit disposal.

Step 6—Make Electrical Connections

Be sure field wiring complies with local and national fire, safety
and electrical codes, and voltage to system is within limits shown
on unit rating plate. Contact local power company for correction of
improper voltage. See unit rating plate for recommended circuit
protection device.

According to NEC, ANSI/NFPA 70, and local codes, the
cabinet must have an uninterrupted or unbroken ground, to
minimize personal injury if an electrical fault should occur.
The ground may consist of electrical wire or metal conduit
when installed in accordance with existing electrical codes.
Failure to follow this warning could result in an electric
shock, fire, or death.

NOTE:

Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage or phase imbalance may
fluctuate above or below permissible limits.

NOTE:

Use copper wire only between disconnect switch and

unit.

NOTE:

Install branch circuit disconnect per NEC of adequate

size to handle unit starting current. Locate disconnect within sight
from and readily accessible from unit, per Section 440-14 of NEC.

ROUTE GROUND AND POWER WIRES — Remove access
panel and control box cover to gain access to unit wiring. Extend
wires from disconnect through power wiring hole provided and
into unit control box. (See Fig. 2.)

CONNECT GROUND AND POWER WIRES

— Connect

ground wire to ground connection in control box for safety.
Connect power wiring to contactor as shown in Fig. 8.

CONNECT CONTROL WIRING — Route 24-v control wires
through control wiring grommet and connect leads to control
wiring terminal board. (See Fig. 9.)

Use No. 18 AWG color-coded, insulated (35° C minimum) wires.
If thermostat is located more than 100 ft from unit (as measured
along the control voltage wires), use No. 16 AWG color-coded
wires to avoid excessive voltage drop.

Use furnace transformer, fan-coil transformer, or accessory trans-
former for control power, 24-v/40va minimum.

NOTE:

Use of available 24-v accessories may exceed the mini-

mum 40va power requirement. Determine total transformer load-
ing and increase the transformer capacity or split the load with an
accessory transformer as required.

NOTE:

The defrost timer is factory set for 90-minute cycles. The

timer can be field set for 30- and 50-minute cycles depending on
defrost conditions in your geographical location.

Step 7—Install Electrical Accessories

Refer to the individual instructions packaged with the kits or
accessories when installing.

Fig. 5 —Typical TXV Installation

A88382

THERMOSTATIC
EXPANSION
VALVE

EQUALIZER
TUBE

SENSING
BULB

COIL

Fig. 6—Positioning of Sensing Bulb

A81032

2  O'CLOCK

10 O'CLOCK

SENSING BULB

STRAP

SUCTION TUBE

8  O'CLOCK

4  O'CLOCK

7

/

8

 O.D. & SMALLER

LARGER THAN

 

7

/

8

 O.D.

 

Fig. 7—Service Valve with Sweat Adapter Tube

A92464

PISTON  BODY

PISTON  RETAINER

INTERNAL  STRAINER

PISTON

FLARE ADAPTER

Fig. 8 —Line Power Connections

A91056

DISCONNECT
PER N. E. C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

4