background image

1. Install suction tube adapter.

2. Install liquid flare-to-sweat adapter.

3. Install TXV on liquid flare-to-sweat adapter.

4. Connect external equalizer tube to fitting on suction tube

adapter.

5. Position sensing bulb on horizontal portion of suction tube

adapter. Secure using supplied hardware. Insulate bulb after
installation.

6. Leak check all connections.

DO NOT BURY MORE THAN 36 IN. OF REFRIGERANT
TUBING IN GROUND. If any section of tubing is buried,
there must be a 6-in. vertical rise to the valve connections on
the outdoor unit. If more than the recommended length is
buried, refrigerant may migrate to cooler buried section
during extended periods of unit shutdown, causing refrigerant
slugging and possible compressor damage at start-up.

Step 5—Make Piping Connections

Outdoor units may be connected to indoor sections using accessory
tubing package or field-supplied refrigerant grade tubing of correct

size and condition. For tubing requirements beyond 50 ft, consult
Long-Line Application Guideline which is available at your local
distributor.

NOTE:

In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

INSTALLATION RECOMMENDATIONS

1. Locate the unit away from windows.

2. Ensure that vapor and liquid line diameters are appropriate to

the capacity of the unit. (See Table 1.)

3. Run refrigerant tubes as directly as possible by avoiding

unnecessary turns and bends.

4. Leave some slack between the structure and the unit to absorb

vibration.

5. When passing refrigerant tubes through the wall, seal the

opening with RTV or other pliable silicon-based caulk. (See
Fig. 3.)

6. Avoid direct lineset contact with water pipes, ductwork, floor

joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with a

rigid wire or strap which comes in direct contact with the
tubing. (See Fig. 3.)

Fig. 2 —Unit Reference Drawing

UNIT

SIZE

A

B

C

D

In.

In.

In.

In.

018—048

34-15/16

30

4

9-3/4

A92022

AIR DISCHARGE

AIR DISCHARGE

AIR DISCHARGE

AIR IN

AIR IN

UNIT RATING 

PLATE

1.  ALLOW 30

″ 

CLEARANCE TO SERVICE END OF

     UNIT, 48

″ 

ABOVE UNIT, 6

″ 

ON ONE SIDE, 12

     ON REMAINING SIDE, AND 24

″ 

BETWEEN

     UNITS FOR PROPER AIRFLOW.
2.  MINIMUM OUTDOOR OPERATING AMBIENT IN COOLING MODE IS
     55° F (UNLESS LOW AMBIENT CONTROL IS USED) MAX. 125° F.

NOTES:

ACCESS

PANEL

AIR IN

C

L

A

B

D

C

3

/

16

3/8" DIA TIEDOWN KNOCKOUTS

(2) PLACES

3.   MAXIMUM OUTDOOR OPERATING AMBIENT IN HEATING MODE IS 66° F.
4.   SERIES DESIGNATION IS THE 13TH POSITION  OF THE UNIT
      MODEL NUMBER.

INDIANAPOLIS IN

46206

313948-401

REV A

MAX CKT-BKR

MAX HACR CKT-BKR

MAX FUSE

TYPE

MINIMUM CIRCUIT AMPS

LO

HI

DESIGN/TEST PRESSURE GAGE

FLA

HZ

PH

VOLTS AC

LRA

RLA

HZ

PH

VOLTS AC

MAX

PH

LBS

PISTON

MODEL

PROD

SERIAL

N/A

USA

N/A

CANADA

MAX OVERCURRENT PROTECTIVE DEVICE

kPa

kPa

PSI

PSI

FAN MOTOR

COMPRESSOR

SUITABLE FOR OUTDOOR USE

MIN

HZ

Kg

VOLTS

POWER SUPPLY

ID

OD

FACTORY CHARGED R-22

®

®

PERMISSIBLE VOLTAGE AT UNIT

CARRIER CORP

LIQUID 
CONNECTION

FIELD CONTROL 
SUPPLY CONNECTION

VAPOR 
CONNECTION

FIELD POWER 
SUPPLY  CONNECTION

2

Reviews: