background image

1. Install suction tube adapter.

2. Install liquid flare-to-sweat adapter.

3. Install TXV on liquid flare-to-sweat adapter.

4. Connect external equalizer tube to fitting on suction tube

adapter.

5. Position sensing bulb on horizontal portion of suction tube

adapter. Secure using supplied hardware. Insulate bulb after
installation. (See Fig. 6.)

6. Check all connections for leaks.

FAN COILS

If unit is installed with an 40FKA, FK4 or FC4 fan coil, no TXV
change is necessary since these fan coils are factory-equipped with
proper TXV.

If TXV installation is required, refer to TXV kit Installation
Instructions for details on TXV installation.

Step 7—Make Piping Connections

Relieve pressure and recover all refrigerant before system
repair or final unit disposal to avoid personal injury or death.
Use all service ports and open all flow-control devices,
including solenoid valves.

To prevent compressor damage DO NOT bury more than 36
in. of refrigerant tubing. If ANY tubing is buried, provide
6-in. vertical rise at service valve.

Outdoor units may be connected to indoor section using accessory
tubing package or field-supplied refrigerant grade tubing of correct
size and condition. Tubing diameters listed in Table 1 are adequate
for equivalent lengths up to 100 ft. DO NOT INSTALL EQUIVA-
LENT INTERCONNECTING TUBING LENGTHS GREATER
THAN 100 FT. Do not increase or decrease interconnecting tubing
diameters.

If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.

OUTDOOR UNIT CONNECTED TO FACTORY-APPROVED
INDOOR UNIT

See Product Data Sheet for factory-approved indoor units.

Outdoor unit contains correct system refrigerant charge for opera-
tion with indoor unit of same size when connected by 15 ft of
field-supplied or factory-accessory tubing. Check refrigerant
charge for maximum efficiency.

REFRIGERANT TUBING

Connect tubing to fittings on outdoor unit vapor and liquid service
valves. (See Table 1.) Use refrigerant grade tubing.

SWEAT CONNECTION

To prevent damage to unit or service valves observe the
following:
• Use a brazing shield.
• Wrap service valves with wet cloth or use a heat sink
material.

Service valves are closed from factory and ready for brazing. After
wrapping service valve with a wet cloth, tubing set can be brazed
to service valve using either silver bearing or non-silver bearing
brazing material. Consult local code requirements. Refrigerant
tubing and indoor coil are now ready for leak testing. This check
should include all field and factory joints.

FINAL TUBING CHECK

IMPORTANT:

Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal. Pay close
attention to feeder tubes, making sure wire ties on feeder tubes are
secure and tight.

Fig. 5—TXV Installed

A91277

THERMOSTATIC
EXPANSION
VALVE

EQUALIZER
TUBE

SENSING
BULB

COIL

Fig. 6—Positioning of Sensing Bulb

A81032

2  O'CLOCK

10  O'CLOCK

SENSING  BULB

STRAP

SUCTION  TUBE

8  O'CLOCK

4  O'CLOCK

7

8

 IN. OD &  SMALLER

LARGER  THAN 

 

7

8

 IN. OD

 

Table 1—Refrigerant Connections and

Recommended Liquid and Vapor Tube

Diameters (In.)

UNIT

SIZE

LIQUID

VAPOR

Connection

Diameter

Tube

Diameter

Connection

Diameter

Tube

Diameter

036, 048

3/8

3/8

7/8

7/8

060

3/8

3/8

7/8

1-1/8

NOTES:
1. Tube diameters are for lengths up to 100 equivalent ft.
2. Do not increase or decrease tubing sizes.

3

Summary of Contents for 38YDA

Page 1: ...rom improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to...

Page 2: ...door operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating ambient in heating mode is 66 F Step 5 Elevate Unit Accu...

Page 3: ...uct Data Sheet for factory approved indoor units Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or facto...

Page 4: ...for 2 speed units Do not attempt to operate unit below 55 F in cooling mode or modify control system for low ambient operation Compressor dam age may occur Available electrical accessories include lat...

Page 5: ...ate unit in a vacuum or at negative pressure Do not disable low pressure switch In scroll compressor applications Dome temperatures may be hot To prevent personal injury wear safety glasses protective...

Page 6: ...LE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED HEAT PUMP See notes 7 8 9 and 11 W2 G W2 O R W3 R L H R1 COOL HEAT STAGE 1 COOL HEAT STAGE 2 24 VAC HOT Y Y2 A D A97498 R C C Y1 W3 O TYPICAL FAN COIL...

Page 7: ...UMPER J2 JUMPER TWO SPEED HEAT PUMP See notes 7 8 9 11 and 23 DH Y1 Y1 W W1 O W2 Y1 W2 O W1 Y Y2 Y2 W2 W3 Y Y2 O W2 COOL HEAT STAGE 1 COOL HEAT STAGE 2 HEAT STAGE 3 RVS COOLING H A98628 R Y2 R Y2 C C...

Page 8: ...FURNACE TWO SPEED HEAT PUMP See notes 7 9 11 14 and 24 W R Y1 R O W2 G L W3 Y H R1 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT K A98587 24 VAC HOT 24 VAC COMM HEAT STAGE 3 R C G W W1 Y Y2 R C RVS COOLING...

Page 9: ...C Y2 W3 W2 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COMM N A HUMIDIFY See notes 7 11 14 15 16 17 18 and 25 N A OUTDOOR SENSOR CONNECTION Y Y2 HUM...

Page 10: ...W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 FAN HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING 24 VAC HOT P A97497 24 VAC HOT 24 VAC COM HE...

Page 11: ...CE WITH ICM BLOWER MOTOR TWO SPEED HEAT PUMP See notes 6 7 9 11 12 14 21 and 24 R Y1 R O G L W3 W W1 Y Y2 W2 Y1 COOL HEAT STAGE 2 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT W A97496 R C C W2 TWO STAGE VA...

Page 12: ...3 W2 O C DHUM HUM B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 HEAT COOL STAGE 1 HEAT COOL STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y...

Page 13: ...t pump MUST have a high pressure switch for dual fuel applications 15 Outdoor air temperature sensor must be attached in all dual fuel applications 16 Thermidistat Dip Switch 1 should be set in the ON...

Page 14: ...w Selection for 58MVP Furnaces CFM 38YDA UNIT SIZE HIGH SPEED A C SETUP SWITCH POSITION FURNACE MODEL HEATING SIZE LOW SPEED CF SETUP SWITCH POSITION 060 080 100 A C 1 A C 2 A C 3 High Low High Low Hi...

Page 15: ...ersects measured liquid service valve pressure 6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line temperature is higher than indicated or rec...

Page 16: ...door coil heat and minimize the steam cloud effect SECOND STAGE LATCHING Mechanical thermostats operate with a staging differential of 2 F droop Carrier electronic thermostats are droopless meaning th...

Page 17: ...ature The cycle terminates when coil thermistor reaches 80 F 5 or defrost period reaches a maximum of 10 minutes FURNACE INTERFACE This feature provides a heat pump lockout upon a demand for auxiliary...

Page 18: ...appears at control board If a PTC trip occurs 3 times the control locks out outdoor unit operation and provides a malfunction signal at control PRESSURE SWITCH PROTECTION The outdoor unit is equipped...

Page 19: ...s the resistance decreases A thermistor is used to sense outdoor ambient Refer to Fig 14 for resistance values versus temperature If outdoor ambient thermistor should fail a malfunction signal appears...