background image

BALANCE POINT

This feature can be used in 2 different options: furnace interface or
electric heat staging. Refer to the Furnace Interface section for its
application. If heat pump is installed with a fan coil with
multistages of electric heat, this option can be used to stage the
banks of heat by outdoor ambient. This eliminates the need for
accessory outdoor thermostats.

When using this option to stage electric heat, the first stage is
energized by a W2 demand, and second stage is energized by a W3
demand. Select the W3 desired temperature by rotating BAL-
ANCE POINT pot. (See Fig. 9 or 11.) Temperatures that may be
selected are 10°, 15°, 20°, 25°, 30°, 35°, 40°, and 45°F. The pot is
factory set at 45°F.

LOW-SPEED HEATING WITH AUXILIARY HEAT

If system is operating in low-speed heating and there is a demand
for auxiliary heat (W2), the system changes to high-speed opera-
tion. W2 is energized unless low-voltage control wiring is config-
ured as shown in Fig. 12.

AUXILIARY HEAT (W2) LOCKOUT

In some areas, it is necessary to disable auxiliary heat, except for
defrost, until outdoor ambient is less than the structure’s balance
point. This is accomplished by using the low-voltage wiring shown
in Fig. 12. Wire the 24-vac W2 signal from indoor thermostat to
W3 of control, and W2 of control to W2 of indoor unit. When
outdoor ambient is less than setting of BALANCE POINT pot, the
24-vac signal energizes auxiliary heat (W2) of indoor unit.

EMERGENCY HEAT

If the 2-speed control receives a call for auxiliary heat (W2)
without a heat pump heating (Y1) call, second auxiliary stage (W3)
is energized. This ensures all available heat is energized if indoor
thermostat is switched to emergency heat.

COMPRESSOR PTC OVERLOAD PROTECTION

The control senses the resistance of the compressor internal
positive temperature coefficient (PTC) overloads. If PTC resis-
tance is out of range, control shuts unit off until resistance range is
acceptable. See Table 10 for compressor PTC ranges.

When control turns outdoor unit off due to out of range PTCs, unit
remains off for 15 minutes with outdoor fan running. After 15
minutes, control checks resistance every 5 minutes until it reaches
reset range. During this time, a malfunction signal appears at
control board. If a PTC trip occurs 3 times, the control locks out
outdoor unit operation and provides a malfunction signal at
control.

PRESSURE SWITCH PROTECTION

The outdoor unit is equipped with high- and low-pressure
switches, wired in series. If the control senses the opening of a
pressure switch, it provides a 5-minute time delay in outdoor unit
operation with outdoor fan running. A malfunction signal appears
on control when pressure switch opens. If pressure switch remains
open for 1 hr or longer, a malfunction signal is provided at L
terminal on indoor thermostat.

MAJOR COMPONENTS

2-Speed Control

The 2-speed control board controls the following functions:

High- and low-compressor contactor operation

Outdoor fan motor operation

Crankcase heater operation

Compressor protection

Pressure switch monitoring

Second-stage latching

Time delays

Time/temperature defrost

Defrost interval selection

Zoning

Furnace interface

Electric heat staging

Refer to other headings in the System Functions and Sequence of
Operation section for individual function information.

Header Pin Housing

The header pin housing is the plastic assembly which holds the
stripped lead ends for field connections. The 2-speed control
receives 24-vac low-voltage control system inputs through the
housing/pins. The housing also contains jumpers which the control
uses for system configuration, such as heat pump versus air
conditioner. Refer to Fig. 13 for header pin housing configuration.

2-Speed Compressor

The 2-speed compressor contains motor windings that provide
low-speed, 4 pole (1750 RPM) and high-speed, 2-pole (3500
RPM) operation. Refer to Table 11 for appropriate winding
resistances. Refer to unit wiring label for winding configurations.

Fig. 12—Low-Voltage Control Wiring

A93572

W2

W3

W3

W2

W2

TWO SPEED

THERMOSTAT

TWO SPEED

HEAT PUMP

FAN

COIL

CONTROL
LOGIC

Table 10—Compressor PTC Ranges

COMPRESSOR INTERNAL PTC RESISTANCE

Safe range (77°F)

1.5k to 7.8k ohms

To trip

26k to 34k ohms

To reset

8.4k to 10k ohms

Fig. 13—Header Pin Housing Configuration

A93576

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

JUMPER FOR 
HEAT PUMP ONLY

C - TRANSFORMER COMMON

R - TRANSFORMER LINE

W2 - FIRST STAGE AUXILIARY HEAT

O - REVERSING VALVE

Y2 - SECOND STAGE COOLING/HEAT PUMP

L - MALFUNCTION LIGHT

Y1 - FIRST STAGE COOLING/HEAT PUMP

W3 - SECOND STAGE AUXILIARY HEAT

4 - TON

5 - TON

IF NO JUMPER IS
INSTALLED, DEFAULT
IS 3 - TON

18

Summary of Contents for 38YDA

Page 1: ...rom improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 Ensure that vapor and liquid tube diameters are appropriate to...

Page 2: ...door operating ambient in cooling mode is 55 F and the maximum outdoor operating ambient in cooling mode is 125 F The maximum outdoor operating ambient in heating mode is 66 F Step 5 Elevate Unit Accu...

Page 3: ...uct Data Sheet for factory approved indoor units Outdoor unit contains correct system refrigerant charge for opera tion with indoor unit of same size when connected by 15 ft of field supplied or facto...

Page 4: ...for 2 speed units Do not attempt to operate unit below 55 F in cooling mode or modify control system for low ambient operation Compressor dam age may occur Available electrical accessories include lat...

Page 5: ...ate unit in a vacuum or at negative pressure Do not disable low pressure switch In scroll compressor applications Dome temperatures may be hot To prevent personal injury wear safety glasses protective...

Page 6: ...LE THERMOSTAT MODEL 2S TYPICAL FAN COIL TWO SPEED HEAT PUMP See notes 7 8 9 and 11 W2 G W2 O R W3 R L H R1 COOL HEAT STAGE 1 COOL HEAT STAGE 2 24 VAC HOT Y Y2 A D A97498 R C C Y1 W3 O TYPICAL FAN COIL...

Page 7: ...UMPER J2 JUMPER TWO SPEED HEAT PUMP See notes 7 8 9 11 and 23 DH Y1 Y1 W W1 O W2 Y1 W2 O W1 Y Y2 Y2 W2 W3 Y Y2 O W2 COOL HEAT STAGE 1 COOL HEAT STAGE 2 HEAT STAGE 3 RVS COOLING H A98628 R Y2 R Y2 C C...

Page 8: ...FURNACE TWO SPEED HEAT PUMP See notes 7 9 11 14 and 24 W R Y1 R O W2 G L W3 Y H R1 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT K A98587 24 VAC HOT 24 VAC COMM HEAT STAGE 3 R C G W W1 Y Y2 R C RVS COOLING...

Page 9: ...C Y2 W3 W2 R Y1 O C DHUM HUM B S1 S2 R C HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COMM N A HUMIDIFY See notes 7 11 14 15 16 17 18 and 25 N A OUTDOOR SENSOR CONNECTION Y Y2 HUM...

Page 10: ...W2 Y1 W2 24 VAC COMM N A OUTDOOR SENSOR CONNECTION C B S1 S2 CARRIER PROGRAMMABLE THERMOSTAT MODEL 2S G H R1 FAN HEAT STAGE 3 COOL HEAT STAGE 2 RVS COOLING 24 VAC HOT P A97497 24 VAC HOT 24 VAC COM HE...

Page 11: ...CE WITH ICM BLOWER MOTOR TWO SPEED HEAT PUMP See notes 6 7 9 11 12 14 21 and 24 R Y1 R O G L W3 W W1 Y Y2 W2 Y1 COOL HEAT STAGE 2 FAN HEAT STAGE 3 RVS COOLING 24 VAC HOT W A97496 R C C W2 TWO STAGE VA...

Page 12: ...3 W2 O C DHUM HUM B S1 S2 R W2 O Y1 R COM HUM PL9 10 DEHUM HEAT STAGE 3 HEAT COOL STAGE 1 HEAT COOL STAGE 2 RVS COOLING FAN 24 VAC HOT 24 VAC COM DEHUMIDIFY HUMIDIFY N A OUTDOOR SENSOR CONNECTIONS Y Y...

Page 13: ...t pump MUST have a high pressure switch for dual fuel applications 15 Outdoor air temperature sensor must be attached in all dual fuel applications 16 Thermidistat Dip Switch 1 should be set in the ON...

Page 14: ...w Selection for 58MVP Furnaces CFM 38YDA UNIT SIZE HIGH SPEED A C SETUP SWITCH POSITION FURNACE MODEL HEATING SIZE LOW SPEED CF SETUP SWITCH POSITION 060 080 100 A C 1 A C 2 A C 3 High Low High Low Hi...

Page 15: ...ersects measured liquid service valve pressure 6 To obtain required subcooling temperature at a specific liquid line pressure add refrigerant if liquid line temperature is higher than indicated or rec...

Page 16: ...door coil heat and minimize the steam cloud effect SECOND STAGE LATCHING Mechanical thermostats operate with a staging differential of 2 F droop Carrier electronic thermostats are droopless meaning th...

Page 17: ...ature The cycle terminates when coil thermistor reaches 80 F 5 or defrost period reaches a maximum of 10 minutes FURNACE INTERFACE This feature provides a heat pump lockout upon a demand for auxiliary...

Page 18: ...appears at control board If a PTC trip occurs 3 times the control locks out outdoor unit operation and provides a malfunction signal at control PRESSURE SWITCH PROTECTION The outdoor unit is equipped...

Page 19: ...s the resistance decreases A thermistor is used to sense outdoor ambient Refer to Fig 14 for resistance values versus temperature If outdoor ambient thermistor should fail a malfunction signal appears...

Page 20: ...e Training plus hands on the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting fewer callbacks Course descriptions and schedules are in our catalo...

Reviews: