background image

7

START-UP

PRELIMINARY CHECKS:
1) Check that all internal wiring connections are tight and

all barriers, covers and panels are in place.

2) Field electrical power source must agree with unit

name plate rating.

3) All service valves must be opened.

INITIAL CHARGE
1. Have charging manifold and refrigerant bottle properly

connected to Schrader valve.

2. Add charge to approximately 448kPa back pressure.

This is not full charge, but it is enough to start the system.

START SYSTEM
1. Check that field disconnect is closed.
2. Set room thermostat to below room temperature, and

unit compressor will start after 5 minutes delay.

3. Check back pressure when compressor runs. Add

charge to keep back pressure at approximately 448kPa.

AIR PURGE

Air does not function as refrigerant because it cannot be
condensed in the condenser. Air and moisture remaining
in the system have undesirable effects. Therefore, they
must be purged out completely.

AIR PURGING PROCEDURE

1.) Remove the blind caps of the three-way valves.
2.) Loosen the valve stem of the three-way liquid valve by

90

°

  for 5 seconds with a hex key wrench, then close

the valve stem quickly.

3.) Push the valve core of the three-way suction valve.
4.) Stop pushing as soon as the hissing stop.
5.) Open the three-way liquid valve for about 3 seconds,

then close quickly to check for gas leak.

6.) After checking for gas leak, open both three-way

valves all the way.

7.) Re-install the blind caps.

FIG. 12   SERVICES VALVE

     CAUTION

STEM VALVE MUST BE FULLY SEATED TO CLOSE SERVICE

PORT. THERE IS NO SCHRADER VALVE AT THE SERVICE

PORT AND FAILURE TO BACKSEAT THE VALVE COULD

RESULT IN LOSS OF SYSTEM CHARGE

OR PERSONAL INJURY.

REFRIGERANT CHARGING

     

  CAUTION

TO PREVENT PERSONAL INJURY, WEAR SAFETY
G L A S S E S  A N D   G L O V E S   W H E N   H A N D L I N G
REFRIGERANT. DO NOT OVERCHARGE SYSTEM.
THIS CAN CAUSE COMPRESSOR FAILURE.

IMPORTANT

For accurate system performance, charge by superheat
method as shown in Tables 4 and 5.

To check and adjust charge, follow the following procedures:-
1) Operate unit for a minimum of 15 minutes before

checking charge.

2) Measure suction pressure by attaching a gauge to

suction valve service port.

3) Measure suction line temperature by attaching a service

thermometer to unit suction line near suction valve.
Insulate thermometer for accurate readings.

4) Measure outdoor coil air inlet dry-bulb temperature

with a second thermometer.

5) Measure indoor coil air inlet wet-bulb temperature

with a sling psychrometer.

6) Refer to Table 4. Find air temperature entering outdoor

coil & wet-bulb temperature entering
indoor coil. At this intersection, note the superheat.

7) Refer to Table 5. Find superheat temperature and

suction pressure, note suction line temperature.

8) If unit has higher suction line temperature than charted

temperature add refrigerant until charted temperature
is reached.

9) If unit has lower suction line temperature than charted

temperature, bleed refrigerant until charted temperature
is reached.

10) If air temperature entering outdoor coil or pressure

at suction line changes, charge to new suction line
temperature indicated on chart.

11) This procedure is valid independent of indoor air quantity.

Summary of Contents for 38VTA040

Page 1: ...cloth and have fire extinguisher available for all brazing operations RECEIVING 38VTA condensing units Fig 1 are shipped individually packed in carton boxes When cartons are individually off loaded f...

Page 2: ...2 FIG 2 38VTA040 050 060 DIMENSIONAL DRAWING...

Page 3: ...l Oil charged l 1 36 1 95 1 77 LRA 50 0 65 5 74 0 RLA 7 9 10 0 10 0 Power Supply 400 3 50 CONDENSER FAN Type Propeller Number 1 Blade dia mm 609 Speed rpm 710 Drive Direct Drive FAN MOTOR Type Permane...

Page 4: ...tubes as directly as possible avoiding unnecessary turns and bends Condensing unit may be connected to evaporator sections using field supplied tubing of refrigerant grade correct size and condition S...

Page 5: ...electrical connection Ensure the ground cable is 20mm longer than others Do not bypass or vary the protective device setting since unit damage may result and the guarantee would be invalidated The ins...

Page 6: ...6 SCHEMATIC WIRING DIAGRAM FIG 10 38VTA040 050 060 c w 40LX040 050 060 FIG 11 38VTA040 050 060 c w 42AR ARM 036 048 060 38VTA040 050 060 c w 42GX 040 050 060...

Page 7: ...E FULLY SEATED TO CLOSE SERVICE PORT THERE IS NO SCHRADER VALVE AT THE SERVICE PORT AND FAILURE TO BACKSEAT THE VALVE COULD RESULT IN LOSS OF SYSTEM CHARGE OR PERSONAL INJURY REFRIGERANT CHARGING CAUT...

Page 8: ...setscrews Adjust fan depth as shown in Fig 14 Tighten setscrew and replace fan grille FIG 13 CLEANING COIL WITH WATER FIG 14 FAN POSITION MOUNTING SERVICE AND MAINTENANCE CAUTION BEFORE PERFORMING REC...

Page 9: ...41 43 45 47 49 51 2 37 39 41 43 45 47 49 51 53 4 39 41 43 45 47 49 51 53 55 6 41 43 45 47 49 51 53 55 57 8 43 45 47 49 51 53 55 57 59 10 45 47 49 51 53 55 57 59 61 12 47 49 51 53 55 57 59 61 63 14 49...

Page 10: ...GH OR LOW COMPRESSOR BEARINGS LOW REFRIGERANT CHARGE HIGH SUPERHEAT LOOSE LEAD AT FAN MOTOR MOTOR DEFECTIVE INCORRECT OUTDOOR FAN MOTOR CAPACITOR LOW SUCTION PRESSURE DIRTY AIR FILTERS DUCT RESTRICTED...

Page 11: ...11 MEMO...

Page 12: ...pecifications or designs without notice and without incurring obligations 38VTA502 001 03 04 38 VTA NEW Carrier International Sdn Bhd 3385 T Lot 4 Jalan P 6 43650 Bandar Baru Bangi Selangor Malaysia T...

Reviews: